INSTALLATION AND MAINTENANCE INSTRUCTIONS
DH100ACDCI Ionization
Air Duct Smoke Detector
Before Installing
Please thoroughly read the System Sensor Guide for Proper Use
of Smoke Detectors in Duct Applications (A05-1004), which
provides detailed information on detector spacing, placement,
zoning, wiring, and special applications. Copies of this manual
are available online at www.systemsensor.com or via System
Sensor's toll free fax-back service, Documents on Demand at
800/736-7672. NFPA Standards 72 and 90A should also be refer-
enced for detailed information.
NOTICE: This manual shall be left with the owner/user of
this equipment.
IMPORTANT: This detector must be tested and maintained reg-
ularly following NFPA 72 requirements. The detector should be
cleaned at least once a year.

Table of Contents

[1] General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
[2] Limitations of Duct Smoke Detectors . . . . . . . . . . . . . . . . . 1
[3] Contents of the Duct Smoke Detector Kit . . . . . . . . . . . . . . 1
[5] Installation Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
[7] Detector Cleaning Procedures . . . . . . . . . . . . . . . . . . . . . . 5
[8] Board Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
[9] Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

[1] General Description

An HVAC system supplies conditioned air to virtually every area
of a building. Smoke introduced into this air duct system will be
distributed to the entire building. Smoke detectors designed for
use in air duct systems are used to sense the presence of smoke
in the duct.
Model DH100ACDCI Air Duct Smoke Detectors utilizes ioniza-
tion technology for the detection of smoke. This smoke detection
method, when combined with an efficient housing design, sam-
ples air passing through the duct and allows detection of a de-
veloping hazardous condition. When sufficient smoke is sensed,
an alarm signal is initiated and appropriate action can be taken
to shut off fans, blowers, change over air handling systems, etc.
These actions can facilitate the management of toxic smoke and
fire gases throughout the areas served by the duct system.
The DH100ACDCI detector is designed to operate on 24 VDC/VAC,
120 VAC, or 240 VAC. Alarm and supervisory relay contacts are
available for control panel interface (alarm initiation), HVAC con-
trol, and other auxiliary functions. Auxiliary relays are also pro-
vided for fan shut down or signaling of up to 9 other detectors
in the loop for multiple fan shut down. These detectors are not
designed for 2-wire applications.
For testing, the alarm can be enabled by a magnet activated test
switch or by the optional remote test station. The duct smoke
detector latches into alarm state when an alarm occurs. A green
LED flashes to indicate power, a red LED signals local alarm
indication, and optional accessories offer a variety of annuncia-
tion capabilities.
D100-68-00
The DH100ACDCI can be reset by a momentary power interrup-
tion, the reset button on the front cover, the control panel, or
remote reset accessory. The DH100ACDCI incorporates a cover
tamper feature that provides a trouble signal after 7 minutes if
the cover is removed or improperly installed. Proper installation
of the cover removes the trouble condition.

[2] Limitations Of Duct Smoke Detectors

The National Fire Protection Association has established that
DUCT DETECTORS MUST NOT BE USED AS A SUBSTITUTE FOR
OPEN AREA DETECTOR PROTECTION as a means of providing
life safety. Nor are they a substitute for early warning in a build-
ing's regular fire detection system.
System Sensor supports this position and strongly recom-
Page
mends that the user read NFPA Standards 90A, 72, and 101. The
DH100ACDCI Air Duct Smoke Detectors are listed per UL 268A.
This device will not operate without electrical power. Fire situa-
tions may cause an interruption of power. The system safeguards
should be discussed with your local fire protection specialist.
This device will not sense smoke unless the ventilation system is
operating and the cover is installed.
For this detector to function properly, it MUST be installed accord-
ing to the instructions in this manual. Furthermore, the detector
MUST be protected from the elements and operated within ALL
electrical and environmental specifications listed in this manual.
Failure to comply with these requirements may prevent the detec-
tor from activating when smoke is present in the air duct.

[3] Contents Of The Duct Smoke Detector Kit

1. Complete housing base and cover assembly
1
2. Two #10 x 1
/
4
3. Two sampling tube filters
4. One test magnet
5. Drilling template
6. Two foam gaskets
7. F our #6-self tapping mounting screws for the metal sampling
tube and optional exhaust tube extension
8. One sampling tube end cap
9. One plastic sampling tube
10. One #8 self-tapping screw for the plastic sampling tube
NOTE: For ducts over 1
ordered to complete the installation. They must be the correct
length for the width of the duct where they will be installed. See
Table 1 on page 3 to determine the sampling tube required for dif-
ferent duct widths.
1
3825 Ohio Avenue, St. Charles, Illinois 60174
800/736-7672, FAX: 630-377-6495
www.systemsensor.com
WARNING
˝ sheet metal screws for mounting
1
feet, longer sampling tubes must be
2
I56-1684-007R

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the DH100ACDCI and is the answer not in the manual?

Questions and answers

Summary of Contents for innovair DH100ACDCI

  • Page 1: Table Of Contents

    [3] Contents Of The Duct Smoke Detector Kit use in air duct systems are used to sense the presence of smoke in the duct. 1. Complete housing base and cover assembly 2. Two #10 x 1 ˝ sheet metal screws for mounting Model DH100ACDCI Air Duct Smoke Detectors utilizes ioniza- 3. Two sampling tube filters tion technology for the detection of smoke. This smoke detection 4. One test magnet method, when combined with an efficient housing design, sam- 5. Drilling template ples air passing through the duct and allows detection of a de- 6. Two foam gaskets...
  • Page 2: Exploded View Of Duct Smoke Detector Components

    DETECTOR BOARD SAMPLING TUBE FILTERS DETECTOR COVER [5] Installation Sequence [5.1] Verify Duct Air Flow Direction And Velocity H0401-00 COVER MOUNTING SCREWS Model DH100ACDCI detectors are designed to be used in air han- [5.3] Secure The Detector Housing To The Duct dling systems having air velocities of 500 to 4000 feet per minute. Be sure to check engineering specifications to ensure that the air Slide the foam gaskets over the tube bushings as shown in Figure 3. velocity in the duct falls within these parameters. If necessary, use Use the two 1 ˝ long sheet metal screws to screw the detector hous- a velocity meter to check the air velocity in the duct. ing to the duct. [5.2] Drill The Mounting Holes CAUTION: Do not overtighten the screws.
  • Page 3 Table 1. Sampling tubes recommended for different Figure 5. Tube mounting configurations with varying duct widths: air flow direction: DOTS INDICATE POSITION OF Outside Duct Width Sampling Tube Recommended* SAMPLING TUBE HOLES 1 to 2 ft. ST-1.5 AIR FLOW AIR FLOW 2 to 4 ft. ST-3 DIRECTION DIRECTION DETECTOR...
  • Page 4: Duct Smoke Detector Maintenance And Test Procedures

    Wiring Instructions tions caused by the air velocity. The location of the detector’s The DH100ACDCI detectors are designed for easy wiring. The sampling tube should be such that there is uniform airflow in the housing provides a terminal strip with clamping plates. Wiring cross section area. connections are made by stripping about 3⁄8-inch of insulation...
  • Page 5: Detector Cleaning Procedures

    3. Pull gently on the board to remove it. Please note that the magnetic coil supplied with the RTS451 4. T o replace the board, align the board mounting features, holes, and RTS451KEY is not required when these accessories are and the interconnect terminals. Push the board into place. used with the DH100ACDCI detectors. The functionality of the 5. Secure board with the two mounting screws. magnetic coil has been designed into the circuitry of the new In- 6. Re-connect wiring to terminal block. novair™ duct smoke detectors. D100-68-00 I56-1684-007R...
  • Page 6 Sup. COM Power Common Aux. Power – Aux. Power – NOTE: Wiring diagram shown is for DH100ACDCI 4-wire duct Reset smoke detector system equipped without a control panel. NOTE: A trouble condition is indicated when the green LED is not illuminated.
  • Page 7 12.5mA Max. 30mA Max. 15mA Max. PA400 10mA Max. RA400Z 7.5mA Max. RTS451/RTS451KEY 12mA* 30mA Max. SSK451 5mA Max. 9mA Max. *NOTE: When a unit is powered at the 120VAC or 220/240VAC input, any combination of accessories may be used such that the given accessory loads are: 60 mA or less in the standby state; 110 mA or less in the alarm state. Figure 12. Wiring diagram for DH100ACDCI to SSK451: FIELD INSTALLED JUMPER FOR TEMPORAL PATTERN COMMON 3 TEMPORAL SELECT 2 ALARM SIGNAL 1 ALARM SIGNAL SUPERVISORY SIGNAL 4 SUPERVISORY CONTACT RESET 7 RESET TEST 8 TEST POWER (-) 6 AUX. POWER (-) POWER (+) 5 AUX. POWER (+)
  • Page 8: Specifications

    [9] Model DH100ACDCI Air Duct Smoke Detector Specifications Operating Temperature: 32° to 131° F 0° to 55° C Storage Temperature: –22° to 158° F –30° to 70° C Humidity: 10% to 93% R.H. non-condensing Air Velocity: 500 to 4000 ft./min. 2.5 to 20.3 m/sec. Dimensions: 14.38˝ L x 5.5˝ W x 2.75˝ D 37cm L x 14cm W x 7cm D Weight: 3.75 pounds 1.7 kg Electrical Specifications Power supply voltage: 20-29 VDC 24 VAC 50-60-Hz 120 VAC 50-60 Hz 220/240 VAC 50-60 Hz Input capacitance: 270 µF max. 270 µF max. Reset voltage: 3.0 VDC min. 2.0 VAC min. 10 VAC min. 20 VAC min.