Lennox CBX32MV Installation Instructions Manual page 29

Multi?position air handler
Hide thumbs Also See for CBX32MV:
Table of Contents

Advertisement

Power−up
Unit Size Code (number or letter) displayed represents unit size code (air handler model size and capacity).
If three horizontal bars display, then Air Handler Control (AHC) does not recognize unit size code.
To enter unit size code
configuration mode; PUSH and
HOLD button next to single
character LED display until dash
symbol appears, RELEASE button.
Solid dash starts blinking
on single character LED
display.
PUSH and HOLD button until the solid P
symbol is displayed on the single
character LED display, then RELEASE
button. This mode allows the user to
select a unit size code (number or letter)
that matches the air handler model size
and capacity.
IMPORTANT
Field replacement controls may need to be
manually configured to validate air handler unit size code.
Solid P starts
blinking on single
character LED
display.
PUSH and HOLD button to allow AHC to display unit size
code (letter or number) for each different air handler model
for three seconds.
Configuring Unit Size Codes (Model Number)
AHC in IDLE mode
Yes
(No heating, cooling or indoor fan operation)
_
_
P
P
Figure 23. Configure Unit Size Codes
Page 29
No
Turn room thermostat to
OFF
UNIT SIZE
AIR HANDLER
CODE
MODEL
0
CBX32MV−018/024
1
CBX32MV−024/030
2
CBX32MV−036
3
CBX32MV−048
4
CBX32MV−060
5
CBX32MV−068
6
CBX40UHV−024
7
CBX40UHV−030
8
CBX40UHV−036
9
CBX40UHV−042
L
CBX40UHV−048
U
CBX40UHV−060
1.
When the correct Unit Sized Code is displayed, RELEASE
push button. Selected code will flash for 10 second period.
2.
During that 10 second period, HOLD push button until code
stops blinking (three seconds minimum).
3.
Air Handler Control will store code in memory and exit current
active mode. LED display will go blank and then the Unit Size
Code will display for 2 to 5 seconds.
NOTE − If 10 second period expires, or push button is held less than
three seconds, control will automatically exit current ative mode and
go into IDLE Mode without storing unit size code. If this occurs, then
Unit Size Code configuring procedure must be repeated.
NO
LED displays correct
Unit Size Code.
- -
-
YES
Unit enters IDLE
Mode.
CBX32MV SERIES

Advertisement

Table of Contents
loading

This manual is also suitable for:

Variable speed air handlers cbx32mv

Table of Contents