Wiring Guidelines - LG ARNU 073 SER2 Engineering Manual

Multi v wall-mounted indoor unit
Table of Contents

Advertisement

general Power Wiring / communications cable guidelines
• Follow manufacturer's circuit diagrams displayed on the inside of the control box cover.
• Have a separate power supply for the indoor units.
• Provide a circuit breaker switch between the power source and the indoor unit.
• Confirm power source specifications.
• Confirm that the electrical capacity is sufficient.
• Starting current must be maintained ±10 percent of the rated current marked on the name plate.
• Confirm wiring / cable thickness specifications:
• Power wiring is field supplied. Wire size is selected based on the larger MCA value, and must comply with the applicable local and
national codes.
• Communication cable must be a minimum of 18 AWG, two-conductor, stranded, shielded, and must comply with the applicable local
and national codes. Ensure the communication cable is properly grounded at the master outdoor unit only. Do not ground the ODU-IDU
communication cable at any other point.
• It is recommended that a circuit breaker is installed, especially if conditions could become wet or moist.
• Include a disconnect in the power wiring system, add an air gap contact separation of at least 1/8 inch in each active (phase) conductor.
• Any openings where the field wiring enters the cabinet must be completely sealed.
• Terminal screws may loosen during transport. Properly tighten the terminal connections during installation or risk electric shock,
physical injury or death.
• Loose wiring may cause unit the wires to burnout or the terminal to overheat and catch fire. There is a risk of electric shock,
physical injury or death.
• Terminal screws may loosen during transport. Properly tighten the terminal connections during installation or risk equipment
malfunction or property damage.
• Loose wiring may cause unit malfunction, the wires to burnout or the terminal to overheat and catch fire. There is a risk of equip-
ment malfunction or property damage.
A voltage drop may cause the following problems:
• Magnetic switch vibration, fuse breaks, or disturbance to the normal function of an overload protection device.
• Compressor will not receive the proper starting current.
Power Wiring and communications cable connections
1. Insert the power wiring / communications cable from the outdoor unit or heat recovery unit (Heat Recovery systems only) using the desig-
nated path in the indoor unit.
2. Connect each wire to its appropriate terminal on the indoor unit control board. Verify that the color and terminal numbers from the outdoor
unit or heat recovery unit (Heat Recovery systems only) wiring match the color and terminal numbers on the indoor unit.
3. Secure the power wiring / communications cable.
Figure 41: Location of Power Wiring / Communications Cable Terminals in
SE and S8 Frame Standard Wall-Mounted Indoor Units.
Lock nut
Conduit
Conduit
mounting
plate
1(L1) 2(L2)
3(A)
4(B)
Power Supply
Communication
High Voltage
(208/230V)
Lock nut
Conduit
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
aPPlIcatIon guIdelIneS
Figure 42: Location of Power Wiring / Communications Cable Terminals
in SB and SC Frame Standard Wall-Mounted Indoor Units.
Lock nut
Conduit
Conduit
mounting
plate
3(A)
4(B)
1(L)
2(N)
Conduit
mounting
plate
Communication
Power Supply
High Voltage
(208/230V)

Wiring Guidelines

Lock nut
Conduit
Conduit
mounting
plate
GuIdElInES | 59

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents