UPG YZE03811 SERIES Installation Manual

UPG YZE03811 SERIES Installation Manual

Outdoor split-system

Advertisement

INSTALLATION MANUAL
R-410A
OUTDOOR SPLIT-SYSTEM
HEAT PUMP
MODELS: 18 SEER - YZE03811 SERIES
3 TON
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
UNIT INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
INSTALLATIONS REQUIRING TXV . . . . . . . . . . . . . . . . . . . . . . . . . . 5
ELECTRICAL CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Typical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Tubing Hanger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Underground Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Heat Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Typical Field Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
CFM Selection Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Two-Stage Variable Speed Furnaces . . . . . . . . . . . . . . . . . . . . . . . . . 7
Two-Stage Variable Speed Furnaces . . . . . . . . . . . . . . . . . . . . . . . . . 8
Defrost Initiate Curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
SECTION I: GENERAL
The outdoor units are designed to be connected to a matching indoor
coil with sweat connect lines. Sweat connect units are factory charged
with refrigerant for the smallest rated indoor coil plus 15 feet of field
supplied lines.
Matching indoor coils are available with a thermal expansion valve or
an orifice liquid feed sized for the most common usage. The orifice size
and/or refrigerant charge may need to be changed for some indoor-out-
door unit combinations, elevation differences or total line lengths. Refer
to Application Data covering "General Piping Recommendations and
Refrigerant Line Length" (Part Number 036-61920-001).
SECTION II: SAFETY
This is a safety alert symbol. When you see this symbol on
labels or in manuals, be alert to the potential for personal
injury.
Understand and pay particular attention to the signal words DANGER,
WARNING, or CAUTION.
DANGER indicates an imminently hazardous situation, which, if not
avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation, which, if not
avoided, could result in death or serious injury.

TABLE OF CONTENTS

EVACUATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
SYSTEM CHARGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
SYSTEM OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
INSTRUCTING THE OWNER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
LIST OF FIGURES
Variable Speed Air Handler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Variable Speed Air Handler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Variable Speed Modulating Furnace . . . . . . . . . . . . . . . . . . . . . . . . .11
Variable Speed Modulating Furnace . . . . . . . . . . . . . . . . . . . . . . . . .12
Heat Pump Flow Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
LIST OF TABLES
R-410A Saturation Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
CAUTION indicates a potentially hazardous situation, which, if not
avoided may result in minor or moderate injury. It is also used to
alert against unsafe practices and hazards involving only property dam-
age
Improper installation may create a condition where the operation of
the product could cause personal injury or property damage.
Improper installation, adjustment, alteration, service or mainte-
nance can cause injury or property damage. Refer to this manual
for assistance or for additional information, consult a qualified con-
tractor, installer or service agency.
This product must be installed in strict compliance with the
enclosed installation instructions and any applicable local, state,
and national codes including, but not limited to building, electrical,
and mechanical codes.
R-410A systems operate at higher pressures than R-22 systems.
Do not use R-22 service equipment or components on R-410A
equipment. Service equipment
ISO 9001
Certified Quality
Management System
LISTED
Must Be Rated
for R-410A.
361819-YIM-A-0208

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the YZE03811 SERIES and is the answer not in the manual?

Questions and answers

Summary of Contents for UPG YZE03811 SERIES

  • Page 1: Table Of Contents

    HEAT PUMP ISO 9001 Certified Quality Management System MODELS: 18 SEER - YZE03811 SERIES 3 TON LISTED TABLE OF CONTENTS GENERAL ..........1 EVACUATION .
  • Page 2: Unit Installation

    361819-YIM-A-0208 SECTION III: UNIT INSTALLATION INSPECTION LOCATION As soon as a unit is received, it should be inspected for possible dam- age during transit. If damage is evident, the extent of the damage Before starting the installation, select and check the suitability of the should be noted on the carrier’s delivery receipt.
  • Page 3: Tubing Hanger

    361819-YIM-A-0208 GROUND INSTALLATION PIPING CONNECTIONS The unit may be installed at ground level on a solid base that will not shift or settle, causing strain on the refrigerant lines and possible leaks. Maintain the clearances shown in Figure 1 and install the unit in a level position.
  • Page 4: Underground Installation

    361819-YIM-A-0208 TO INDOOR COIL TO OUTDOOR UNIT LIQUID LINE INSULATED VAPOR LINE CONDUIT FIGURE 3: Underground Installation PRECAUTIONS DURING BRAZING OF LINES All outdoor unit and evaporator coil connections are copper-to-copper and should be brazed with a phosphorous-copper alloy material such as Silfos-5 or equivalent.
  • Page 5: Installations Requiring Txv

    361819-YIM-A-0208 If bulb installation is made on a vertical run, the bulb should be located at least 16 inches from any bend, and on the tub- ing sides opposite the plane of the bend. The bulb should be positioned with the bulb tail at the top, so that the bulb acts as Never attempt to repair any brazed connections while the system is a reservoir.
  • Page 6: Cfm Selection Board

    361819-YIM-A-0208 FIELD CONNECTIONS CONTROL WIRING blower motor will operate at lower speed until the dehumidification con- trol is satisfied. A 40-60% relative humidity level is recommended to Route low voltage wiring into bottom of control box as shown in achieve optimum comfort. Figure 5.
  • Page 7: Thermostat Wiring - Two-Stage Heat Pumps

    361819-YIM-A-0208 For additional connection diagrams for all UPG equipment refer to “Low Voltage System Wiring” document available online at www.upgnet.com in the Product Catalog Section. HP 24A Two Stage Heat Pump – Two Stage Variable Speed Furnace (With Hot Heat Pump Operation)
  • Page 8: Thermostat Wiring - Two-Stage Heat Pump

    361819-YIM-A-0208 HP 24C Two Stage Heat Pump – Two Stage Variable Speed Furnace (With Hot Heat Pump Operation) ID MODELS OD MODELS PV(8/9) (F/L)*(8/9)V (G/L)(8/9)V THERMOSTAT THERMOSTAT TWO STAGE *DN22H00124 TWO STAGE *PP32U70124 VARIABLE SPEED *DP22U70124 HEAT PUMP FURNACE TWO STAGE YORKGUARD VI VARIABLE SPEED CONTROL...
  • Page 9: Thermostat Wiring - Two-Stage Heat Pump - Variable Speed Air Handler

    361819-YIM-A-0208 HP 27A Two Stage Heat Pump – Variable Speed Air Handler (With Hot Heat Pump Operation) ID MODELS OD MODELS THERMOSTAT *PP32U71124 VARIABLE SPEED TWO STAGE *PP32U72124 AIR HANDLER HEAT PUMP VARIABLE SPEED YORKGUARD VI AIR HANDLER CONTROL CONTROL 24 –...
  • Page 10: Thermostat Wiring - Two-Stage Heat Pump - Variable Speed Air Handler

    361819-YIM-A-0208 HP 27C Two Stage Heat Pump – Variable Speed Air Handler (With Hot Heat Pump Operation) ID MODELS OD MODELS THERMOSTAT THERMOSTAT *DN22H00124 VARIABLE SPEED TWO STAGE *PP32U70124 *DP22U70124 AIR HANDLER HEAT PUMP VARIABLE SPEED YORKGUARD VI AIR HANDLER CONTROL CONTROL 24 –...
  • Page 11: Thermostat Wiring - Two-Stage Heat Pump - Variable Speed Modulating Furnace

    361819-YIM-A-0208 HP 28A Two Stage Heat Pump – Variable Speed Modulating Furnace (With Hot Heat Pump Operation) ID MODELS OD MODELS PC(8/9) FC(8/9)C FL(8/9)C THERMOSTAT VARIABLE SPEED *PP32U71124 TWO STAGE MODULATING *PP32U72124 HEAT PUMP FURNACE VARIABLE SPEED YORKGUARD VI MODULATING CONTROL FURNACE CONTROL 24 –...
  • Page 12: Thermostat Wiring - Two-Stage Heat Pump - Variable Speed Modulating Furnace

    361819-YIM-A-0208 HP 28C Two Stage Heat Pump – Variable Speed Modulating Furnace (With Hot Heat Pump Operation) ID MODELS OD MODELS PC(8/9) FC(8/9)C FL(8/9)C THERMOSTAT THERMOSTAT VARIABLE SPEED *DN22H00124 TWO STAGE *PP32U70124 MODULATING *DP22U70124 HEAT PUMP FURNACE VARIABLE SPEED YORKGUARD VI MODULATING CONTROL FURNACE CONTROL...
  • Page 13: Evacuation

    361819-YIM-A-0208 SECTION VI: EVACUATION It will be necessary to evacuate the system to 500 microns or less. If a leak is suspected, leak test with dry nitrogen to locate the leak. Repair Refrigerant charging should only be carried out by a qualified air the leak and test again.
  • Page 14: Defrost Initiate Curves

    361819-YIM-A-0208 SECTION VIII: SYSTEM OPERATION The indoor blower (furnace or air handler) will be operating, dis- charging warm air from the ducts. For more information on the control operation, refer to “Operation The vapor line at the outdoor unit will feel warm to the touch. Instructions - DEMAND DEFROST CONTROL BOARD in this Booklet.
  • Page 15: Wiring Diagram

    361819-YIM-A-0208 SECTION X: WIRING DIAGRAM FIGURE 14: Wiring Diagram Unitary Products Group...
  • Page 16 Subject to change without notice. Printed in U.S.A. 361819-YIM-A-0208 Copyright © by Unitary Products Group. 2008. All rights reserved. Supersedes: 128596-YIM-A-0505 Unitary 5005 Norman Product York Group Drive 73069...