Split Products Table of Contents Model Nomenclature Safety Storage Pre-Installation Equipment Selection Air Coil Match-ups Air Handler Selection Installation Water Connections 10-11 Ground Loop Applications 11-13 Open Loop - Ground Water Systems 14-15 Water Quality Standards Refrigeration Installation 17-22 Lineset Information Hot Water Generator 23-24 Electrical - Line Voltage...
R e s i d e n t i a l S p l i t - 6 0 H z R 2 2 & R 4 1 0 A R e v. : 5 J u n e , 2 0 0 8 Model Nomenclature: for Indoor Split Series Y D S UNIT TYPE:...
15 days of receipt of shipment. If not fi led 7. Locate and verify any hot water generator (HWG) or within 15 days, the freight company can deny the claim without other accessory kit located in the compressor section.
Indoor Coil Selection - GT-PX Split (50YDS) associated components, parts, and accessories which make Carrier Geothermal split system heat pumps are rated in up the installation shall be in accordance with the regulations the ARI directory with a specifi c indoor coil match. GT-PX...
Page 7
R e s i d e n t i a l S p l i t - 6 0 H z R 2 2 & R 4 1 0 A R e v. : 5 J u n e , 2 0 0 8 Equipment Selection Table 1b: GT-PX Air Handler Characteristics for Brands other than Above Models Nominal...
R e s i d e n t i a l S p l i t - 6 0 H z R 2 2 & R 4 1 0 A R e v. : 5 J u n e , 2 0 0 8 Equipment Selection Air Handler Selection Example Figure 1 shows a typical performance table for a heat pump air...
R e s i d e n t i a l S p l i t - 6 0 H z R 2 2 & R 4 1 0 A R e v. : 5 J u n e , 2 0 0 8 Installation NOTICE! Failure to remove shipping brackets from spring- 2.
R e s i d e n t i a l S p l i t - 6 0 H z R 2 2 & R 4 1 0 A R e v. : 5 J u n e , 2 0 0 8 Installation Figure 2: 50YDS/GT-GS Installation Existing Pad larger than 22"...
R e s i d e n t i a l S p l i t - 6 0 H z R 2 2 & R 4 1 0 A R e v. : 5 J u n e , 2 0 0 8 Installation Internal Flow Controller Mounting - Figure 5: Water Connections (Outdoor Compressor Section)
Page 12
R e s i d e n t i a l S p l i t - 6 0 H z R 2 2 & R 4 1 0 A R e v. : 5 J u n e , 2 0 0 8 Ground-Loop Heat Pump Applications Earth loop temperatures can range between 25 and Loop static pressure will fl...
Page 13
R e s i d e n t i a l S p l i t - 6 0 H z R 2 2 & R 4 1 0 A R e v. : 5 J u n e , 2 0 0 8 Ground-Loop Heat Pump Applications Table 1: Approximate Fluid Volume (U.S.
R e s i d e n t i a l S p l i t - 6 0 H z R 2 2 & R 4 1 0 A R e v. : 5 J u n e , 2 0 0 8 Ground-Water Heat Pump Applications - “Indoor”...
Page 15
300 psig and a cut-in pressure of 250 psig. This pressure switch can be ordered from Carrier Geothermal with a 1/4” internal fl are connection as part number 39B0005N02. CAUTION!
R e s i d e n t i a l S p l i t - 6 0 H z R 2 2 & R 4 1 0 A R e v. : 5 J u n e , 2 0 0 8 Water Quality Standards Table 3: Water Quality Standards 100 F (38...
R e s i d e n t i a l S p l i t - 6 0 H z R 2 2 & R 4 1 0 A R e v. : 5 J u n e , 2 0 0 8 Refrigeration Installation R-410A models are shipped with a fi...
Page 18
R e s i d e n t i a l S p l i t - 6 0 H z R 2 2 & R 4 1 0 A R e v. : 5 J u n e , 2 0 0 8 Refrigeration Installation Figure 10: Braze Instructions Figure 11: Air Coil Connection...
Page 19
R e s i d e n t i a l S p l i t - 6 0 H z R 2 2 & R 4 1 0 A R e v. : 5 J u n e , 2 0 0 8 Refrigeration Installation Figure 12a: Typical Split/Air Handler Installation (Indoor Compressor Section) Power...
Page 20
R e s i d e n t i a l S p l i t - 6 0 H z R 2 2 & R 4 1 0 A R e v. : 5 J u n e , 2 0 0 8 Refrigeration Installation Figure 13a: Typical Split/Air Handler Installation (Outdoor Compressor Section)
Page 21
R e s i d e n t i a l S p l i t - 6 0 H z R 2 2 & R 4 1 0 A R e v. : 5 J u n e , 2 0 0 8 Refrigeration Installation Evacuation Of The Lineset And Coil There are two methods of charging a refrigerant system.
R e s i d e n t i a l S p l i t - 6 0 H z R 2 2 & R 4 1 0 A R e v. : 5 J u n e , 2 0 0 8 Refrigeration Installation refrigerant so that the total charge calculated for the unit and Checking Superheat and Subcooling...
R e s i d e n t i a l S p l i t - 6 0 H z R 2 2 & R 4 1 0 A R e v. : 5 J u n e , 2 0 0 8 Hot Water Generator The HWG (Hot Water Generator) or desuperheater system, providing the maximum storage and temperate...
Page 24
R e s i d e n t i a l S p l i t - 6 0 H z R 2 2 & R 4 1 0 A R e v. : 5 J u n e , 2 0 0 8 Hot Water Generator Figure 17: Alternate HWG Piping with concentric/coaxial Water Tank Refi...
R e s i d e n t i a l S p l i t - 6 0 H z R 2 2 & R 4 1 0 A R e v. : 5 J u n e , 2 0 0 8 Hot Water Generator Module Refrigeration Installation - Outdoor Compressor Section Only 3.
Page 26
R e s i d e n t i a l S p l i t - 6 0 H z R 2 2 & R 4 1 0 A R e v. : 5 J u n e , 2 0 0 8 Hot Water Generator Module Refrigeration Installation - Outdoor Compressor Section Only CAUTION!
R e s i d e n t i a l S p l i t - 6 0 H z R 2 2 & R 4 1 0 A R e v. : 5 J u n e , 2 0 0 8 Electrical - Line Voltage All fi...
Page 28
R e s i d e n t i a l S p l i t - 6 0 H z R 2 2 & R 4 1 0 A R e v. : 5 J u n e , 2 0 0 8 Electrical - Line Voltage Table 8c: GT-S Outdoor (38WQS) Series Electrical Data Compressor...
R e s i d e n t i a l S p l i t - 6 0 H z R 2 2 & R 4 1 0 A R e v. : 5 J u n e , 2 0 0 8 Electrical - HWG Wiring Figure 21b: R-22 Indoor Compressor Section Line HWG Wiring - “Indoor”...
R e s i d e n t i a l S p l i t - 6 0 H z R 2 2 & R 4 1 0 A R e v. : 5 J u n e , 2 0 0 8 Electrical - Low Voltage Wiring ELECTRICAL - LOW VOLTAGE WIRING Figure 22c: GT-S Low Voltage Field Wiring...
Page 31
Figure 26: Taco SBV Valve Wiring 25 and 26 illustrate typical slow closing water control valve wiring for Taco 500 series (Carrier Geothermal P/N AVM…) and Taco ESP series valves. Slow closing valves take approximately 60 seconds to open (very little water will fl ow before 45 seconds).
300 psig and a cut-in pressure of 250 psig. This pressure switch can be ordered from Carrier Geothermal with a 1/4” Optional internal fl are connection as part number 39B0005N02.
R e s i d e n t i a l S p l i t - 6 0 H z R 2 2 & R 4 1 0 A R e v. : 5 J u n e , 2 0 0 8 CXM Controls CXM Control DDC operation.
Page 34
R e s i d e n t i a l S p l i t - 6 0 H z R 2 2 & R 4 1 0 A R e v. : 5 J u n e , 2 0 0 8 CXM Controls Safety Features –...
Page 35
R e s i d e n t i a l S p l i t - 6 0 H z R 2 2 & R 4 1 0 A R e v. : 5 J u n e , 2 0 0 8 CXM Controls CXM Control Start-up Operation The control will not operate until all inputs and safety controls...
Page 36
R e s i d e n t i a l S p l i t - 6 0 H z R 2 2 & R 4 1 0 A R e v. : 5 J u n e , 2 0 0 8 CXM Controls Table 10: Nominal resistance at CXM Thermostat Details...
R e s i d e n t i a l S p l i t - 6 0 H z R 2 2 & R 4 1 0 A R e v. : 5 J u n e , 2 0 0 8 Unit Starting and Operating Conditions Operating Limits 2.
Page 38
R e s i d e n t i a l S p l i t - 6 0 H z R 2 2 & R 4 1 0 A R e v. : 5 J u n e , 2 0 0 8 Unit Starting and Operating Conditions Unit and System Checkout Flow Controller pump(s): Verify that the pump(s) is wired...
R e s i d e n t i a l S p l i t - 6 0 H z R 2 2 & R 4 1 0 A R e v. : 5 J u n e , 2 0 0 8 Unit Operating Conditions Table 12a: Two-Stage R-410A Compressor Section Coax Table 13: Water Temperature Change Through Heat...
Page 41
R e s i d e n t i a l S p l i t - 6 0 H z R 2 2 & R 4 1 0 A R e v. : 5 J u n e , 2 0 0 8 Unit Operating Conditions Table 14a: Size 026 Two-Stage R-410A Typical Unit Operating Pressures and Temperatures Full Load Cooling - without HWG active...
Page 42
R e s i d e n t i a l S p l i t - 6 0 H z R 2 2 & R 4 1 0 A R e v. : 5 J u n e , 2 0 0 8 Unit Operating Conditions Table 14d: Size 064 Two-Stage R-410A Typical Unit Operating Pressures and Temperatures Full Load Cooling - without HWG active...
R e s i d e n t i a l S p l i t - 6 0 H z R 2 2 & R 4 1 0 A R e v. : 5 J u n e , 2 0 0 8 Preventive Maintenance Water Coil Maintenance Condensate Drain...
R e s i d e n t i a l S p l i t - 6 0 H z R 2 2 & R 4 1 0 A R e v. : 5 J u n e , 2 0 0 8 CXM Process Flow Chart WARNING! WARNING! HAZARDOUS VOLTAGE! DISCONNECT ALL...
R e s i d e n t i a l S p l i t - 6 0 H z R 2 2 & R 4 1 0 A R e v. : 5 J u n e , 2 0 0 8 Troubleshooting Form Customer: _____________________________________ Antifreeze: _________________...
Page 49
R e s i d e n t i a l S p l i t - 6 0 H z R 2 2 & R 4 1 0 A R e v. : 5 J u n e , 2 0 0 8 C a r r i e r : Tu r n t o t h e E x p e r t s...