Micro Mod 53SL5100B Instruction Manual

Micro Mod 53SL5100B Instruction Manual

Micro-dci single-loop controller
Table of Contents

Advertisement

Quick Links

Micro-DCI Single-Loop Controller
Instruction Manual
53SL5100B

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 53SL5100B and is the answer not in the manual?

Questions and answers

Summary of Contents for Micro Mod 53SL5100B

  • Page 1 Micro-DCI Single-Loop Controller Instruction Manual 53SL5100B...
  • Page 2 53SL5100B Single-Loop Controller INSTRUCTION MANUAL MicroMod Automation & Controls, Inc. The Company MicroMod Automation & Controls is dedicated to improving customer efficiency by providing the most cost-effective, application-specific process solutions available. We are a highly responsive, application-focused company with years of expertise in control systems design and implementation.
  • Page 3: Table Of Contents

    53SL5100B Single-Loop Controller INSTRUCTION MANUAL INTRODUCTION ............................1 ..........................1 RODUCT VERVIEW ............................. 2 PECIFICATIONS INSTALLATION............................5 ............................5 NSPECTION ............................... 5 OCATION .............................. 5 OUNTING 2.3.1 General............................5 2.3.2 Mounting Procedure ........................6 & S ........................9 OWER IGNAL IRING 2.4.1...
  • Page 4 53SL5100B Single-Loop Controller INSTRUCTION MANUAL INSTRUMENT TUNING ......................... 71 10.1 P (PB)......................... 71 ROPORTIONAL CTION 10.2 I (TR).......................... 71 NTEGRAL CTION 10.3 D (TD) ........................71 ERIVATIVE CTION 10.4 I ..........................72 NSTRUMENT UNING EASY-TUNE ............................75 11.1 G ........................75...
  • Page 5 53SL5100B Single-Loop Controller INSTRUCTION MANUAL IMPORTANT NOTICE All software, including design, appearances, algorithms and source code is copyrighted by MicroMod Automation & Controls, Inc. and is owned by MicroMod or its suppliers.
  • Page 7: Introduction

    53SL5100B Single-Loop Controller INSTRUCTION MANUAL 1 INTRODUCTION 1.1 Product Overview The 53SL5100 Controller is capable of functioning as any one of four selectable application-specific instruments. The instrument application is selected with the front panel push buttons by entering the appropriate number (1 through 4 respectively) into a designated database location. The four instrument selections are: 1.
  • Page 8: Specifications

    53SL5100B Single-Loop Controller INSTRUCTION MANUAL 1.2 Specifications Item Specification(s) Power Range (as specified in model number) 22 - 26 V dc 108 - 132 V rms 216 - 264 V rms 50/60 Hz Power Consumption (ac/dc operation) 36 VA maximum Internal Power Supply: 25 V dc ±...
  • Page 9 53SL5100B Single-Loop Controller INSTRUCTION MANUAL Item Specification(s) Environmental Characteristics Controlled Environment Enclosed temperature controlled location (Class A and B per ISA- S71.01 1985) Ambient Temperature Limits 4 -52°C (40 - 125°F) Relative Humidity Limits 10 - 90% maximum Temperature Effects on Accuracy ±...
  • Page 10 53SL5100B Single-Loop Controller INSTRUCTION MANUAL...
  • Page 11: Installation

    53SL5100B Single-Loop Controller INSTRUCTION MANUAL 2 INSTALLATION 2.1 Inspection A list of all items in the shipment is attached to the shipping container. Inspect the equipment upon arrival for damage that may have occurred during shipment. All damage claims should be reported to the responsible shipping agent before installation is attempted.
  • Page 12: Mounting Procedure

    53SL5100B Single-Loop Controller INSTRUCTION MANUAL 2.3.2 Mounting Procedure For single and multiple case mounting the instruments are furnished with a trim collar (mounting frame). Figure 2-2 illustrates the installation and use of the trim collar (mounting frame). Trim collars (mounting frames) are available in various sizes and are supplied to conform with the particular panel cut-out.
  • Page 13 53SL5100B Single-Loop Controller INSTRUCTION MANUAL NOTES: DIMENSIONS ARE IN INCHES. DIMENSIONS IN BRACKETS ( ) ARE IN MILLIMIETERS. DIMENSIONS GUARANTEED ON CERTIFIED PRINTS ONLY. CASE MOUNTING HARDWARE SUPPLIED UNLESS OTHERWISE SPECIFIED. THIS DRAWING IS THIRD-ANGLE PROJECTION AS SHOWN UNLESS OTHERWISE INDICATED ALL TOLERANCES ARE ±...
  • Page 14 53SL5100B Single-Loop Controller INSTRUCTION MANUAL Figure 2-2. Single or Multiple Panel Mounting Figure 2-3. Intercase Spacing...
  • Page 15: Power & Signal Wiring

    53SL5100B Single-Loop Controller INSTRUCTION MANUAL 2.4 Power & Signal Wiring PREPARATORY: The 53SL5100 can be configured for one to four analog inputs (ANI0-3), one analog output (ANO0), two control contact inputs (CCI0 and 1), two control contact outputs (CCO0 and 1) and Datalink network interconnectivity.
  • Page 16 53SL5100B Single-Loop Controller INSTRUCTION MANUAL Figure 2-4. Controller Rear Power and Signal Terminal Boards...
  • Page 17 53SL5100B Single-Loop Controller INSTRUCTION MANUAL Figure 2-5. Datalink Installation Diagram...
  • Page 18: Power Wiring

    53SL5100B Single-Loop Controller INSTRUCTION MANUAL 2.4.1 Power Wiring Refer to the instrument model number to verify the power input requirements:  53SL511…. – AC Power  53SL512…. – DC Power 2.4.1.1 DC Power Reference Figure 2-4 and connect the remote 24 V dc power supply to the instrument as follows: 1.
  • Page 19: Datalink Communication

    53SL5100B Single-Loop Controller INSTRUCTION MANUAL 2.4.3 Datalink Communication Datalink is an interrogator/responder serial interface capable of supporting 32 instruments on a single network. It uses an RS485 physical interface. The Datalink wiring diagram for this instrument is provided as Figure 2-5. Complete coverage of the Datalink is provided in Instruction Bulletin 53SU5000.
  • Page 20 53SL5100B Single-Loop Controller INSTRUCTION MANUAL...
  • Page 21: Front Panel

    53SL5100B Single-Loop Controller INSTRUCTION MANUAL 3 FRONT PANEL The front panel of the instrument contains the display and all push buttons used to change display presentations and parameters. The front panel has a gas discharge 96 X 48 dot matrix display, a six pushbutton vertical keypad, and a four pushbutton horizontal keypad.
  • Page 22 53SL5100B Single-Loop Controller INSTRUCTION MANUAL The three bar graph display types for CS1-4 and the parameter display, with appropriate call outs, are illustrated in Figure 3-2 through Figure 3-5. Figure 3-6 and Figure 3-7 illustrate displays with alarm and configuration overlays.
  • Page 23 53SL5100B Single-Loop Controller INSTRUCTION MANUAL Figure 3-4. CS4, Automatic/Manual Station Figure 3-5. CS1 - CS4 Parameter Display...
  • Page 24 53SL5100B Single-Loop Controller INSTRUCTION MANUAL Figure 3-6. Alarm Overlay Figure 3-7. Configure Overlay...
  • Page 25: Front Panel Pushbuttons

    53SL5100B Single-Loop Controller INSTRUCTION MANUAL 3.2 Front Panel Pushbuttons The front panel pushbuttons are used to vary the display presentation, to select instrument operator or engineering modes, and to select local or remote setpoint levels. In engineering mode, (EMODE) they are also used to display and/or alter database parameters which are presented as single line datapoints in the configuration overlay.
  • Page 26 53SL5100B Single-Loop Controller INSTRUCTION MANUAL Push- button Title Operator Mode Engineering Mode Used to select between Remote setpoint control Remote/ and Local setpoint control. When in Remote, an Local R appears in the lower right of the display. When Not used...
  • Page 27: Displaying A Datapoint

    53SL5100B Single-Loop Controller INSTRUCTION MANUAL 3.3 Displaying a Datapoint The following procedure illustrates how to enter Engineering Mode (EMODE) and use the display function to access the contents of datapoint A001 (A1). The displayed contents will be PERCENT. Figure 3-9 and Figure 3-10 are supporting illustrations for the display procedure which is described in Table 3-2.
  • Page 28: Altering A Datapoint

    53SL5100B Single-Loop Controller INSTRUCTION MANUAL 3.4 Altering a Datapoint The following procedure illustrates how to enter EMODE and use the configuration function to alter the contents of datapoint B000 (B0) with a 97. Entering a 97 in B00 invokes the display test which strobes the display matrix dots on and off at 5 second intervals (approximate).
  • Page 29: Defaulting The Database

    53SL5100B Single-Loop Controller INSTRUCTION MANUAL Figure 3-11. Checkerboard Pattern Figure 3-12. Permiter Dots Illuminated 3.5 Defaulting the Database Defaulting the database sets all non-instrument-specific datapoint parameters to predetermined values, then suspends the instrument which is indicated by the logo presented on the display. When instrument operation is suspended, instrument algorithmic control ceases.
  • Page 30 53SL5100B Single-Loop Controller INSTRUCTION MANUAL Table 3-4. Defaulting the Database Step Press Shift Press to Target Result Once Result Locate Char. Puts instrument in engineering mode. MODE If DISPLAY appears instead of CONFIGURE press F2. Displays entry line: POINT .
  • Page 31: Responding To The Prompt: Key

    53SL5100B Single-Loop Controller INSTRUCTION MANUAL 3.6 Responding to the Prompt: KEY? When the password prompt KEY? appears, it indicates a password was set in the MicroTools software. The password can not be set via the front panel push buttons. A password key is a maximum of 10 numeric characters (numbers 0-9 only). It does not impede display functions in engineering mode but must be unlocked to perform configuration functions.
  • Page 32 53SL5100B Single-Loop Controller INSTRUCTION MANUAL...
  • Page 33: Configuration Parameters

    53SL5100B Single-Loop Controller INSTRUCTION MANUAL 4 CONFIGURATION PARAMETERS The configuration parameters provide the latitude to define the instrument’s personality attributes, so that while still functioning within its designed specifications, it can perform application requirements with greater refinement. Typical configuration parameters are the instrument’s indicator zero point and span, the display tag names, engineering units of the displayed process value, and alarm limits, etc.
  • Page 34: Configuring The Database Modules

    53SL5100B Single-Loop Controller INSTRUCTION MANUAL If the state of the database is unknown, the instrument can be returned to the factory standard configuration with two datapoint entries: 1. Set B00 to 98 to default the database. 2. Set B00 to 1 to start functioning as a Single Loop Controller.
  • Page 35 53SL5100B Single-Loop Controller INSTRUCTION MANUAL Table 4-4. Analog Input (ANI) Module Purpose: This module is used to configure input voltage characteristics (e.g., input voltage range), and how the input signals are interpreted (linear or square root representation). ANI0 ANI1 Title...
  • Page 36 53SL5100B Single-Loop Controller INSTRUCTION MANUAL Figure 4-1. ANI0-3 Figure 4-2. ANO0  NOTE: These figures are graphical representations of the signal conditioning that occurs on the instrument main board. They are provided for reference purposes only. Table 4-5. Analog Output (ANO) Module...
  • Page 37 53SL5100B Single-Loop Controller INSTRUCTION MANUAL Table 4-7. Contact Output Module (CCO) Purpose: This module allows the action of the CCO to be reversed (normally a closed contact = 1, but can be changed to = 0). Title Symbol Data-point Default...
  • Page 38 53SL5100B Single-Loop Controller INSTRUCTION MANUAL Table 4-8. Control Module Purpose: The primary purpose of this module is to set the instrument’s responsiveness, Alarm Limits 1 & 2, Alarm Dead Band, and the range limits (e.g., 0 - 100, -20 - 80, etc.).
  • Page 39 53SL5100B Single-Loop Controller INSTRUCTION MANUAL Table 4-8. Control Module (continued) Purpose: The primary purpose of this module is to set the instrument’s Alarm Index mode, Alarm Limits 1 & 2, and Alarm Dead Band. CON-0 ■   Title Symbol...
  • Page 40 53SL5100B Single-Loop Controller INSTRUCTION MANUAL Table 4-9. Parameter Display Module Purpose: This module provides quick pushbutton display access to any three selected datapoints (e.g., Alarm Limits 1 & 2 and Alarm Dead Band) without the necessity of entering Engineering mode and addressing the datapoints.
  • Page 41 53SL5100B Single-Loop Controller INSTRUCTION MANUAL Table 4-10. Communication Module Purpose: This module is used to configure the Datalink port parameters (e.g., baud rate, parity selection, etc.). Title Symbol Datapoint Default Attribute It identifies the address of this instrument on the Instrument Datalink network.
  • Page 42 53SL5100B Single-Loop Controller INSTRUCTION MANUAL Table 4-11. System Module Purpose: This module is used to set the instrument tag name and the display brightness. System Title Symbol Module Default Attribute Datapoint The operational algorithm of the unit is selected by the value of this parameter: 0 = Suspend mode.
  • Page 43: Single Loop (Pid) Controller

    53SL5100B Single-Loop Controller INSTRUCTION MANUAL 5 SINGLE LOOP (PID) CONTROLLER 5.1 Operation Overview In a standard feedback control loop, the Single Loop (PID) Controller functions as the primary processing unit. When the process is altered due to disturbances (e.g., flow rate changes), the controller gauges this change from the process variable (PV) feedback signal sent to it by a process measurement instrument (e.g., flow...
  • Page 44 53SL5100B Single-Loop Controller INSTRUCTION MANUAL It is the difference between the setpoint (SP) and received process variable (PV), augmented by the action of the tuning constants Proportional Band, Reset Time, and Rate Time, that determines the required output to the final element to restore the process. The output signal (Analog Output) to the final element is 4-20 mA dc.
  • Page 45 53SL5100B Single-Loop Controller INSTRUCTION MANUAL Figure 5-2. Single Loop Controller Block Diagram...
  • Page 46: Single Loop Controller Front Panel Pushbuttons

    53SL5100B Single-Loop Controller INSTRUCTION MANUAL 5.2 Single Loop Controller Front Panel Pushbuttons The front panel pushbuttons for the Single Loop Controller are illustrated in Figure 5-3 and defined in Table 5- 1. The pushbutton functions for the Single Loop Controller are identical to those provided in Section 3.
  • Page 47 53SL5100B Single-Loop Controller INSTRUCTION MANUAL Table 5-1. Controller Pushbuttons Push- button Title Operator Mode Engineering Mode Used to select between Remote setpoint control and Local setpoint control. When in Remote, an Remote/ Local R appears in the lower right of the display. When...
  • Page 48: Single Loop Controller Parameter Selections

    53SL5100B Single-Loop Controller INSTRUCTION MANUAL instrument between Operator mode and Engineering mode. 5.3 Single Loop Controller Parameter Selections Figure 5-4 illustrates how a Single Loop Controller would appear with only the default values and power applied, but no analog input or output signals. In Figure 5-5, ANO0 (TB1-10) is jumpered to ANI0 (TB1-2) to simulate process operation.
  • Page 49: Abbreviated Configuration Tables

    53SL5100B Single-Loop Controller INSTRUCTION MANUAL 5.3.1 Abbreviated Configuration Tables Table 5-1 through Table 5-8 are provided as a quick reference source for the contiguration datapoints. These tables do not have the definition column; therefore, for the initial instrument configuration, Section 4 should be referenced until each datapoint functionality can be recognized by its title.
  • Page 50 53SL5100B Single-Loop Controller INSTRUCTION MANUAL Table 5-6. Control (CON-0) Module CON-0 Title Symbol Datapoint Default Control Alarm Mode B335 Control Action L106 Reverse Valve L109 Manual Fallback Disable L120 Alarm Limit 1 C103 Alarm Limit 2 C104 Alarm Dead Band...
  • Page 51: Analog Backup Controller

    53SL5100B Single-Loop Controller INSTRUCTION MANUAL 6 ANALOG BACKUP CONTROLLER 6.1 Analog Backup Controller Operation Overview The Analog Backup Controller is used in operations where a remote computer is normally controlling the final element directly. In this process configuration, the controller functions as a signal selector and automatic backup unit to the computer.
  • Page 52 53SL5100B Single-Loop Controller INSTRUCTION MANUAL As illustrated in Figure 6-2, Analog Backup Controller Block Diagram, when a 2 is loaded into System Module datapoint B00 to indicate CS2, the signal designators are as follows: 1. ANI0 = Process Variable 2. ANI1 = Control Element Feedback 3.
  • Page 53: Analog Backup Controller Front Panel Pushbuttons

    53SL5100B Single-Loop Controller INSTRUCTION MANUAL 6.2 Analog Backup Controller Front Panel Pushbuttons The front panel push buttons for the Analog Backup Controller are illustrated in Figure 6-3 and defined in Table 6-1. Figure 6-3. Analog Backup Controller Pushbuttons...
  • Page 54 53SL5100B Single-Loop Controller INSTRUCTION MANUAL Table 6-1. Controller Pushbuttons Push- button Title Operator Mode Engineering Mode Used to select between Remote setpoint control and Remote/ Local setpoint control. When in Remote, an R Local Not used appears in the lower right of the display. When in Select Local, an L appears in the lower right of the display.
  • Page 55: Analog Backup Controller Parameter Selections

    53SL5100B Single-Loop Controller INSTRUCTION MANUAL 6.3 Analog Backup Controller Parameter Selections Figure 6-4 illustrates how an Analog Backup Controller would appear with only the default values and power applied., but no analog input or output signals. In Figure 6-4, ANO0 (TB1-10) is jumpered to ANI0 (TB1-2) to simulate process operation.
  • Page 56: Abbreviated Configuration Tables

    53SL5100B Single-Loop Controller INSTRUCTION MANUAL 6.4 Abbreviated Configuration Tables Table 6-2 through Table 6-8 are provided as a quick reference source for the configuration datapoints. These tables do not have the definition column; therefore, for the initial instrument configuration, Section 4 should be referenced until each datapoint functionality can be recognized by its title.
  • Page 57 53SL5100B Single-Loop Controller INSTRUCTION MANUAL Table 6-6. Control (CON-0) Module CON-0 Title Symbol Datapoint Default Control Alarm Mode B335 Control Action L106 Reverse Valve L109 Manual Fallback Disable L120 Alarm Limit 1 C103 Alarm Limit 2 C104 Alarm Dead Band...
  • Page 58 53SL5100B Single-Loop Controller INSTRUCTION MANUAL...
  • Page 59: Ratio (Pid) Controller

    53SL5100B Single-Loop Controller INSTRUCTION MANUAL 7 RATIO (PID) CONTROLLER 7.1 Ratio (PID) Controller Operation Overview The Ratio (PID) Controller is used where one variable, called the controlled variable, must be automatically maintained in definite proportion to another variable, called the wild variable.
  • Page 60 53SL5100B Single-Loop Controller INSTRUCTION MANUAL As illustrated in Figure 7-2, Ratio (PID) Controller Block Diagram, when a 3 is loaded into System Module datapoint B00 to indicate CS3, the signal designators are as follows: 1. ANI0 = Controlled Variable 2. ANI1 = Wild Variable 3.
  • Page 61: Ratio (Pid) Controller Front Panel Pushbuttons

    53SL5100B Single-Loop Controller INSTRUCTION MANUAL 7.2 Ratio (PID) Controller Front Panel Pushbuttons The front panel push buttons for the Ratio (PID) Controller are illustrated in Figure 7-3 and defined in Table 7- Figure 7-3. Ratio (PID) Controller Pushbuttons...
  • Page 62 53SL5100B Single-Loop Controller INSTRUCTION MANUAL Table 7-1. Controller Pushbuttons Push- button Title Operator Mode Engineering Mode R indicates Ratio control whereby the controller maintains a set proportion between the wild variable line and the controlled Ratio/ variable line. Local Not used...
  • Page 63: Ratio Controller Parameter Selections

    53SL5100B Single-Loop Controller INSTRUCTION MANUAL toggle the instrument between Operator mode and Engineering mode. 7.3 Ratio Controller Parameter Selections Figure 7-4 illustrates how a Ratio Controller would appear with only the default values and power applied, but no analog input or output signals. In Figure 7-4, ANO0 (TB1-10) is jumpered to ANI0 (TB1-2) to simulate process operation.
  • Page 64: Abbreviated Configuration Tables

    53SL5100B Single-Loop Controller INSTRUCTION MANUAL 7.4 Abbreviated Configuration Tables Table 7-2 through Table 7-7 are provided as a quick reference source for the configuration datapoints. These tables do not have the definition column; therefore, for the initial instrument configuration, Section 4 should be referenced until each datapoint functionality can be recognized by its title.
  • Page 65 53SL5100B Single-Loop Controller INSTRUCTION MANUAL Table 7-6. Control (CON-0) Module CON-0 Title Symbol Datapoint Default Control Alarm Mode B335 Control Action L106 Reverse Valve L109 Manual Fallback Disable L120 Alarm Limit 1 C103 Alarm Limit 2 C104 Alarm Dead Band...
  • Page 66 53SL5100B Single-Loop Controller INSTRUCTION MANUAL...
  • Page 67: Automatic/Manual Station

    53SL5100B Single-Loop Controller INSTRUCTION MANUAL 8 AUTOMATIC/MANUAL STATION 8.1 Automatic/Manual Station Operation Overview The Automatic/Manual Station is a conventional single station selector. In Auto, the auto input (Analog Input 0) is passed directly through the station to the output (Analog Output 0). In Manual, the station functions as a manual loader, allowing the output to be controlled from the front panel pushbuttons.
  • Page 68 53SL5100B Single-Loop Controller INSTRUCTION MANUAL Figure 8-2. Automatic/Manual Station Block Diagram...
  • Page 69: Automatic/Manual Station Front Panel Pushbuttons

    53SL5100B Single-Loop Controller INSTRUCTION MANUAL 8.2 Automatic/Manual Station Front Panel Pushbuttons The front panel push buttons for the Automatic/Manual Station are illustrated in Figure 8-3 and defined in Table 8-1. Figure 8-3. Automatic/Manual Station Push Buttons...
  • Page 70 53SL5100B Single-Loop Controller INSTRUCTION MANUAL Table 8-1. Front Panel Pushbuttons Push- button Title Operator Mode Engineering Mode Remote/ Local Not used Not used Select For configure or a display function, the character Setpoint set displays one character at a time in...
  • Page 71: Automatic/Manual Station Parameter Selections

    53SL5100B Single-Loop Controller INSTRUCTION MANUAL 8.3 Automatic/Manual Station Parameter Selections Figure 8-4 illustrates how a Single Loop Controller might appear with only the default values and power applied, but no analog input or output signals. In Figure 8-4, ANO0 (TB1-lO) is jumpered to ANI0 (TB1-2) to simulate process operation.
  • Page 72 53SL5100B Single-Loop Controller INSTRUCTION MANUAL Table 7-6. Control (CON-0) Module CON-0 Title Symbol Datapoint Default Control Alarm Mode B335 Manual Fallback Disable L120 Alarm Limit 1 C103 Alarm Limit 2 C104 Alarm Dead Band C105 Controller Span C115 Controller Lower Range...
  • Page 73: Parameter Display

    53SL5100B Single-Loop Controller INSTRUCTION MANUAL 9 PARAMETER DISPLAY The parameter display can be accessed from any control strategy (CS1 - CS4) by pressing the F1 or F2 front panel push button. It provides convenient access to view and/or alter three parameter datapoint values that were selected when the display was configured.
  • Page 74 53SL5100B Single-Loop Controller INSTRUCTION MANUAL Figure 9-1. Parameter Display Edit Function...
  • Page 75: Parameter Display Configuration Settings

    53SL5100B Single-Loop Controller INSTRUCTION MANUAL 9.1 Parameter Display Configuration Settings Figure 9-2 is an illustration of the parmeter display with datapoint call outs. Table 9-2 is an abbreviated parameter display configuration table. Figure 9-2. Parameter Display Datapoint Selections Table 9-2. Parameter Display Module...
  • Page 76 53SL5100B Single-Loop Controller INSTRUCTION MANUAL...
  • Page 77: Instrument Tuning

    53SL5100B Single-Loop Controller INSTRUCTION MANUAL 10 INSTRUMENT TUNING Tuning the instrument is an iterative process to refine the Proportional Band (PB), Integral (also called Reset Time [TRI]), and Derivative (TD) parameters of the Control Module 0 (CON-0). The three parameter datapoints are C106, Proportional Band (PB);...
  • Page 78: Instrument Tuning

    53SL5100B Single-Loop Controller INSTRUCTION MANUAL 10.4 Instrument Tuning Table 10-1 provides summary information for the tuning parameters referenced in the three tuning methods that follow. The Trial and Error Method (Table 10-2) is usually preferred for processes that respond quickly, requiring no waiting to determine steady cycling process conditions.
  • Page 79 53SL5100B Single-Loop Controller INSTRUCTION MANUAL Table 10-1. Summary Information for Tuning Parameters Abbreviation Datapoint Min Value Max Value Parameter P.B. C106 1000% Proportional Band C107 0.02 minutes/rep. 200 minutes/rep. Reset C108 0.01 minutes 8 minutes Rate Table 10-2. Summary Information for Tuning Parameters...
  • Page 80 53SL5100B Single-Loop Controller INSTRUCTION MANUAL Figure 10-1. Typical Step Response Method...
  • Page 81: Easy-Tune

    53SL5100B Single-Loop Controller INSTRUCTION MANUAL 11 EASY-TUNE The EASY-TUNE algorithm is used to help determine the optimal tuning values for the Proportional Band (PB), Integral (TR), and Derivative (TD) parameters (called PID constants) in the Controller Module Mode 0 (CON-0). The three parameter datapoints are C106, Proportional Band (PB); C107, Reset Time (TR); and C108, Derivative Time (TD).
  • Page 82: Easy-Tune Parameters

    53SL5100B Single-Loop Controller INSTRUCTION MANUAL 11.3 EASY-TUNE Parameters All pertinent input parameters to the EASY-TUNE algorithm are obtained from Controller Module Mode 0, which must first be configured. The parameters that must be configured before initiating the EASY-TUNE sequence (B008 = 1) are items 1, 3, 5 through 10, in Table 11-1.
  • Page 83: Easy-Tune Sequence Status

    53SL5100B Single-Loop Controller INSTRUCTION MANUAL 11.4 EASY-TUNE Sequence Status Once initiated, the algorithm sets the instrument to Manual mode. After a period of settling time, a step change in instrument output is applied and the resulting process response is observed. As summarized in Table 11-2 and Table 11-3, datapoint 8387, EASY-TUNE Status, will numerically show the result of the EASY-TUNE algorithm.
  • Page 84 53SL5100B Single-Loop Controller INSTRUCTION MANUAL Figure 11-1. EASY-TUNE Sequence Diagram...
  • Page 85: Modifications To Tuning Criteria

    53SL5100B Single-Loop Controller INSTRUCTION MANUAL 11.5 Modifications to Tuning Criteria During EASY-TUNE sequence execution, each of the three algorithm variables: Time Constant (T ), Process Gain (K ), and Dead-Time (W ), are altered by 10% in the conservative direction, (instrument operating characteristics would be slower response, but less chance of oscillation and instability) before the tuning parameters are computed using the ITAE equations listed in Table 11-4.
  • Page 86 53SL5100B Single-Loop Controller INSTRUCTION MANUAL Figure 11-2. Process Step Response Curve...
  • Page 87: Aborting The Easy-Tune Sequence

    53SL5100B Single-Loop Controller INSTRUCTION MANUAL 11.6 Aborting the EASY-TUNE Sequence If the EASY-TUNE sequence is active and the instrument output is deliberately changed, the sequence will be aborted. The original instrument output and Manual or Auto mode will be restored. Datapoint B387, EASY- TUNE Status, will be set to 54.
  • Page 88 53SL5100B Single-Loop Controller INSTRUCTION MANUAL...
  • Page 89: Maintenance

    53SL5100B Single-Loop Controller INSTRUCTION MANUAL MAINTENANCE  NOTE: The factory set calibration constants for ANI0-3 and ANO0 are applicable only for the main printed circuit board supplied in the particular instrument. This data is recorded on a calibration sheet supplied with the instrument. The data should be retained to facilitate easy field recalibration in the event one or more of the constants is inadvertently changed.
  • Page 90: Calibration

    53SL5100B Single-Loop Controller INSTRUCTION MANUAL DC Power: 3A, 250 V, Slow Blow BEL Type 5TT3 For additional information, contact MicroMod Automation.  NOTE: When communicating with MicroMod for replacement of the main PCB, reference the unit’s serial number to ensure the correct replacement assembly is supplied. The necessary ordering information is provided on the instrument data tag and on the manufacturing specification sheet supplied with that particular controller.
  • Page 91 53SL5100B Single-Loop Controller INSTRUCTION MANUAL  If the F3 push button is pressed and held during controller reset, the controller is forced to the suspend state (FIX 0).
  • Page 92: Parts List

    53SL5100B Single-Loop Controller INSTRUCTION MANUAL 12.6 Parts List The parts list is provided in Table 5-1 and the parts breakdown is illustrated in Figure 5-1. Note that these boards are for the 53SL5100 Design Level B, not the 53SL5000 Design Level A. Contact MicroMod for more information on spare parts availability for the 53SL5100A.
  • Page 93 53SL5100B Single-Loop Controller INSTRUCTION MANUAL Figure 5-1. Illustrated Parts Breakdown...
  • Page 94 53SL5100B Single-Loop Controller INSTRUCTION MANUAL Figure 5-3. Communication ITB Pin Assignments...
  • Page 95 53SL5100B Single-Loop Controller INSTRUCTION MANUAL...
  • Page 96: Appendix A: Discrete Contact Output Cco's

    53SL5100B Single-Loop Controller INSTRUCTION MANUAL Appendix A: Discrete Contact Output CCO’s The discrete output CCOs are not mechanical contact closures but NPN Transistors that are analogous to single pole, single throw switches with one terminal connected to power common. This circuit type layout is commonly called an Open Collector Output.
  • Page 97 53SL5100B Single-Loop Controller INSTRUCTION MANUAL Figure A-1. CCO Circuit and its Equivalent Figure A-2. Circuits for Operating DC Relays...
  • Page 98 53SL5100B Single-Loop Controller INSTRUCTION MANUAL Figure A-3. Operating CCOs in Parallel Figure A-4. CCO with Solid State Relay Figure A-5. CCO Operating CCI Directly...
  • Page 99 53SL5100B Single-Loop Controller INSTRUCTION MANUAL...
  • Page 100: Appendix B : Communications

    53SL5100B Single-Loop Controller INSTRUCTION MANUAL Appendix B : Communications Two digital communication channels are provided with this instrument:  RS-232 serial configuration port, accessed via a 5 pin mini-DIN connector located under the pull- down door on the front panel (see Figure 1-2). It is used to configure instrument parameters for selected operational characteristics.
  • Page 101 53SL5100B Single-Loop Controller INSTRUCTION MANUAL Table B-1. Communication Module Purpose: This module is used to configure the Datalink port parameters (e.g., baud rate, parity selection, etc.). Title Datapoint Setup Default Attribute It identifies the address of this instrument on the Instrument Datalink network.
  • Page 102 53SL5100B Single-Loop Controller INSTRUCTION MANUAL Protocol The Datalink protocol requires the host to initiate all transactions. There are two basic categories for all of the Datalink message types: Interrogate - used to read data from an addressed instrument, and Change used to alter a value in an addressed instrument.
  • Page 103 53SL5100B Single-Loop Controller INSTRUCTION MANUAL 4. ACKNOWLEDGE - This message signals the addressed instrument that its last echoed change message was received correctly; the instrument performs the change requested. 01111110 80H + I.A. INSTRUMENT TO HOST: 1. RESPONSE - This message furnishes the data requested by the INTERROGATE command of the Host.
  • Page 104 53SL5100B Single-Loop Controller INSTRUCTION MANUAL + I.A. 4. Instrument performs the change requested at end of the current program scan.
  • Page 105 53SL5100B Single-Loop Controller INSTRUCTION MANUAL Calculating Data Addresses If communications software must be generated to accommodate unique Datalink applications requirements, then the instrument memory address scheme must be known for proper data bit (e.g., L data type) and data byte (e.g., B, C, H, and A data types) memory location determination.
  • Page 106 53SL5100B Single-Loop Controller INSTRUCTION MANUAL Table B-3. Instrument Memory Address Scheme (continued) Base Data Byte Memory Data Format Address Calculation Algorithm Type Size Address F00H Represents high precision floating Address = H Base + (5 X H Number) = point values that have a resolution...
  • Page 107: Appendix C: Database

    53SL5100B Single-Loop Controller INSTRUCTION MANUAL Appendix C: Database The database contains five datapoint types. Each datapoint type represents a specific data format: whole integers, alphanumeric text strings, etc. The datapoint types are defined in Table C-1 and the database is listed in alphanumeric order in Table C-2.
  • Page 108 53SL5100B Single-Loop Controller INSTRUCTION MANUAL Table C-2. Database Title Symbol Datapoint Default Attribute Control Tag Name Assignable 10 character name that appears with the control strategy (CS1-4) displays. CTAG A000 CON-0 Engineering Units The default is PERCENT, but is assignable as units of...
  • Page 109 53SL5100B Single-Loop Controller INSTRUCTION MANUAL Value Baud Rate Value Baud Rate 28800 28800 14400 14400 19200 9600 9600 4800 4800 2400 2400 1200 1200 EASY-TUNE Enable B008 n set to a 1, th e EAS Y-TUN lgorithm implemented. This parameter is left at 0 for norm instrument operation.
  • Page 110 53SL5100B Single-Loop Controller INSTRUCTION MANUAL PA1n: high when PV> PL1 PA2n: not affected PA1n: not affected PA2n: low when PV< PL1 PA1n: high when PV> PL1 PA2n: hi-hi when PV> PL2 PA1n: low when PV< PL1 PA2n: lo-lo when PV< PL2 PA1: Hi-Dev when D ev >...
  • Page 111 53SL5100B Single-Loop Controller INSTRUCTION MANUAL controller response in standard PID terms. Reset Time C107 This parameter represents the number of minutes per repeat for integral action. It modifies the controller response in standard PID terms. Rate Time C108 This parameter represents the min utes that proportional action is advanced (derivative action).
  • Page 112 53SL5100B Single-Loop Controller INSTRUCTION MANUAL Only) When open, a 4 - 24 V dc input signal = 1 when IINV = When closed, a < 1 V dc input signal = 1 when IINV = 0. When clos ed, a < 1 V dc input signal = 0 when IINV = 1.
  • Page 113 53SL5100B Single-Loop Controller INSTRUCTION MANUAL 0 when using MicroMod comm unications software or equipment. CCI Input Invert IINV L264 This bit reverses the action of CCI datapoint L000 (Contact Input); therefore, the action of this bit is explained in datapoint L000.
  • Page 114 53SL5100B Single-Loop Controller INSTRUCTION MANUAL...
  • Page 115 The Company’s policy is one of continuous product improvement and the right is reserved to modify the information contained herein without notice, or to make engineering refinements that may not be reflected in this bulletin. MicroMod Automation & Controls, Inc. assumes no responsibility for errors that may appear in this manual.

Table of Contents