Page 2
Poseidon 4002 – Manual HW group www.HW-group.com...
Page 3
Poseidon 4002 – Manual HW group Poseidon 4002 MANUAL POWER input INPUTS OUTPUTS 12VDC supply Binary inputs 1–6 Two 50V rated switch- (jack or terminals) (for contacts) over relay contacts POWER OUT ETHERNET 12V supply for sensors 10 or 100/10 Mbps...
Poseidon 4002 – Manual HW group 1-Wire sensors wiring Recommended connections GSM modem RS-232 Remote reset PowerEgg Smoke detector - Power detector - Power control Control Closed Door detector Temperatue probe 3m Water Leak detector °C Temperature probe for Rack montage AirFlow detector °C...
Poseidon 4002 – Manual HW group First steps 1) Connecting the cables Turn the unit upside down and write down its MAC address Poseidon 4002 that is printed on the label. Set the switches: DIP1=Off, DIP2=Off. Connect the unit to the Ethernet (with a patch cable to a switch, cross-over cable to a PC), RJ-45 port.
Poseidon 4002 – Manual HW group First steps Configure network parameters IP address / HTTP port (80 by default) Network mask Gateway IP address for your network Device name (optional) Click the Apply Changes button to save the settings.
Page 7
Poseidon 4002 – Manual HW group First steps 4) WWW interface of the device To open the WWW interface of the device: Enter the IP address into a web browser Click the IP address in UDP Config Click the underlined IP address in UDP SETUP ...
Poseidon 4002 – Manual HW group Flash SETUP To open the FLASH interface, FLASH support needs to be installed on your PC. If the computer is connected to the Internet, the needed plug-in is downloaded automatically. General: Overview of current readings ...
Page 9
Poseidon 4002 – Manual HW group Email & SMS Sends a test e-mail and shows the connection log Sends a test SMS and shows the connection log To send e-mail, check: To send SMS, check: 1) Correct Gateway IP address...
Page 10
Poseidon 4002 – Manual HW group Sensors Sends a SNMP trap if the “Safe Enter sensor name, will be Range” for this sensor is exceeded shown in E-mail, SMS or SNMP traps Sends a SMS if the “Safe Range” for this sensor is exceeded...
Page 11
Poseidon 4002 – Manual HW group Inputs Enter sensor name (will be ALARM CONTACT STATUS: shown in E-mail, SMS or Active if On SNMP traps) Alarm when the contact REACTION TO CONTACTS: closes (1 = On) Inactive Active if Off ...
Page 12
Poseidon 4002 – Manual HW group Outputs Choose output mode Manual mode: Local Condition mode: Output controlled over the Output activated by the “Htemp Rack 19” sensor if WEB or M2M protocols the temp exceeds 30°C Output mode: Manual Output can be controlled in the Flash interface, or from any application using M2M protocols (XML, SNMP, Modbus/TCP).
Page 13
Poseidon 4002 – Manual HW group GSM modem (local or remote) Select Disabled to use a remote GSM modem. Select GSM Modem for a local modem. Address of the remote GSM modem (SMS GW). Select Local or Remote GSM modem.
Poseidon 4002 – Manual HW group Software Applications HWg-PDMS HWg-PDMS is a Windows application for data logging and quick export of reports to MS Excel. Sensor readings from connected devices are stored in a database. Readings are received over XML (http) or e-mail. Works with the PD Trigger application to process alarms.
Page 15
CapTemp and MonTemp CapTemp and MonTemp is a pair of utilities to monitor production processes. The programs can supervise all sensors from HW group (temperature and humidity sensors, contacts, etc) as well as sensors by other manufacturers. CapTemp logs the readings into an...
Poseidon 4002 – Manual HW group Relay outputs POWER OUT NO NC NO and NC labels apply to Off (0) state, or device turned off When the output is On (1), a “Normally Open” (NO) relay contact is closed ...
Page 20
Poseidon 4002 – Manual HW group M2M interface This product can be used with third-party SW applications. For a description of the interfaces (XML format, detailed description of SNMP, mapping of Modbus/TCP variables), see the detailed “Poseidon family” manual. ...
Poseidon 4002 – Manual HW group Updating the firmware over the WEB http://x.x.x.x/upload/. Upload the firmware in a .hwg file over http to Connection problems etc. must be avoided during file transfer. If the update fails, upload the firmware over RS-232.