VeriFire®, and VIEW® are all registered trademarks of Honeywell International Inc.HARSH™, NIS™, and NOTI•FIRE•NET™ are all trademarks; and Acclimate® Plus, FlashScan®, NION®, NOTIFIER®, ONYX®, ONYXWorks®, UniNet®, VeriFire®, and VIEW® are all registered trademarks of Honeywell International Inc. Echelon® is a registered trademark and LonWorks™ is a trademark of Echelon Corporation. ARCNET® is a registered trademark of Datapoint Corporation.
Page 4
•Brief description of content you think should be improved or corrected •Your suggestion for how to correct/improve documentation Send email messages to: FireSystems.TechPubs@honeywell.com Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical Services. DAA2 & DAX — P/N 53265:A1 8/24/2011...
2.4.1: Sig Sil Control ...........................42 2.4.2: Volume Control - Master and Auxiliary....................42 2.4.3: FFT Communication .........................42 2.4.4: Trouble Messages ..........................42 2.4.5: Read/Alter Status..........................42 Section 3: DAX Digital Audio Amplifiers ................43 3.1: DAX Overview ............................43 3.1.1: Description............................43 3.1.2: Features..............................43 3.1.3: Specifications.............................44 AC Power - TB7...........................44...
Page 6
Digital Audio Ports A and B.........................55 Speaker and Backup Circuits........................57 UL Power-limited Wiring Requirements....................64 3.3: DAX Configuration .............................65 3.3.1: Setting the Configuration Switches ....................65 EARTH FAULT (Switch 5) - DAX-35 Only ..................65 Address Switches..........................65 3.3.2: Programming .............................65 3.4: DAX Operation ............................65 3.4.1: Volume ..............................65 3.4.2: Trouble Messages ..........................65...
Page 7
In Riser Mode to CIM/CSM Series Canadian Room Isolator Modules..........116 UL Power-limited Wiring Requirements ...................119 C.3: Configuration ............................120 C.3.1: Setting the Configuration Switches ....................120 EFA and EFB (Switches 9 and 10).....................120 4WIRE (Switch 11) ..........................120 Address Switches..........................121 Volume Control ..........................121 C.4: Programming.............................121 DAA2 & DAX — P/N 53265:A1 8/24/2011...
Page 8
Table of Contents C.5: Operation ..............................121 C.5.1: Pushbutton Controls ........................121 C.5.2: Volume Control..........................122 C.5.3: Read/Alter Status ..........................122 C.5.4: FFT Communication ........................122 C.5.5: Trouble Messages ...........................122 C.6: Battery Calculations ..........................122 Index ............................124 DAA2 & DAX — P/N 53265:A1 8/24/2011...
Digital audio amplifiers are backed up by BDAs, or by another amplifier of the same digital type: that is, a DAA2 must be backed up by a BDA or another DAA2, a DAX must be backed up a BDA or another DAX, etc.
Related Documentation Table 1.4 Cautions and Warnings This manual contains cautions and warnings to alert the reader as follows: CAUTION: INFORMATION ABOUT PROCEDURES THAT COULD CAUSE PROGRAMMING ERRORS, RUNTIME ERRORS, OR EQUIPMENT DAMAGE. DAA2 & DAX — P/N 53265:A1 8/24/2011...
Page 11
Cautions and Warnings General Information WARNING: INDICATES INFORMATION ABOUT PROCEDURES THAT COULD CAUSE IRREVERSIBLE DAMAGE TO THE CONTROL PANEL, IRREVERSIBLE LOSS OF PROGRAMMING DATA, OR PERSONAL INJURY. DAA2 & DAX — P/N 53265:A1 8/24/2011...
Two Class A connections for high-level audio output, or alternately, four Class B connections. • Audio output activation via network control-by-event equations resident within the DVC. • Isolated alarm bus input, to be used for backup activation of alarm messages when normal digital communication is lost. DAA2 & DAX — P/N 53265:A1 8/24/2011...
Current Draw Calculations”, along with a worksheet to determine the actual AC draw. Recommended 12-14 AWG (1.6 mm O.D.) with 600 VAC insulation. Fuse: 8 amps, 250V, 5 x 20 mm, Fast-Acting, ceramic. Notifier p/n 12117. Secondary Power 5V and 24V AUX Outputs - TB2 ...
Class B 2-wire connections require a 3.9k ohm 1/2 watt resistor (P/N R-3.9K). Max. wiring resistance (including individual telephone zone to last handset) permitted is 50 ohms, 10,000 ft (3048 m) max. wiring distance at 14 AWG to last handset. DAA2 & DAX — P/N 53265:A1 8/24/2011...
Page 16
• 25V (DAA2-5025 and DAA2-7525). • 70V (DAA2-5070). Recommended wiring: 14-18 AWG twisted-pair (shielded recommended). Supervision: •Not supervised when inactive. Supervised by backup source when active. •Must be in the same room or enclosure. DAA2 & DAX — P/N 53265:A1 8/24/2011...
Refer to page 29 TB2 - Digital DAPA REF Dotted line indicates position of Audio Port A DAPA - the DAA2’s CPS-24 Power Refer to page 29 DAPA + Supply Board Figure 2.1 DAA2 Rear Board DAA2 & DAX — P/N 53265:A1 8/24/2011...
Page 18
+24V AUX COM - Future Use +5V AUX - Future Use CPS-24 Power Supply Board AC Fuse F4 AC INPUT Refer to EARTH page 25 GROUND Figure 2.2 DAA2’s CPS-24 Power Supply Board DAA2 & DAX — P/N 53265:A1 8/24/2011...
Page 19
+24V AUX: LED 5 +5V AUX: LED 6 LOGIC POWER: LED 1 TROUBLE: LED 2 EARTH FAULT: LED 3 GND FAULT: SW1 AC: LED 4 Figure 2.3 LED Indicator, Jumper and Switch Locations DAA2 & DAX — P/N 53265:A1 8/24/2011...
Call the factory if this LED is off for a prolonged period of time. BACKUP Yellow Illuminates for diagnostics of the BDA amplifier. FAIL CPS-24 Power Supply Board LED Name Color Description LED # Table 2.3 DAA2 LED Indicators (1 of 2) DAA2 & DAX — P/N 53265:A1 8/24/2011...
• Review the installation precautions at the front of this manual. • Installers should be familiar with the standards and codes specified in “Standards and Other Documents” on page 9. • Ensure all wiring will comply with national and local codes. DAA2 & DAX — P/N 53265:A1 8/24/2011...
NOTE: Digital amplifiers can produce significant heat during their duty cycles. Different cabinets can handle different amounts of heat. Refer to the Heat Dissipation Calculation document (53645) to determine dissipation figures for the equipment you are installing, and match it with an appropriate cabinet. DAA2 & DAX — P/N 53265:A1 8/24/2011...
Page 23
DAA2 Installation DAA2 Digital Audio Amplifiers DAA2 Mounting Locations Figure 2.4 EQCAB-D4 Backbox and EQDR-D4 Door DAA2 & DAX — P/N 53265:A1 8/24/2011...
Batteries for the DAA2 may be installed in any of the following configurations: • In a CHS-BH1 battery chassis (12AH batteries only), designed for use with the DAA2 chassis. • In the bottom of a CAB-4 series cabinet that holds the DAA2. DAA2 & DAX — P/N 53265:A1 8/24/2011...
Close the hinged cover for TB1 after wiring but before energizing. The DAA2 power supply requires connection to a separate dedicated AC branch circuit. Follow these guidelines when connecting the AC branch circuit: DAA2 & DAX — P/N 53265:A1 8/24/2011...
P/N 75560 (pos) P/N 75561 (neg) P/N 75621 (neg) Batteries in CHS-BH1, same Batteries in different cabinet cabinet row as DAA2 row than DAA2. Figure 2.9 Connecting Batteries to TB3 on the CPS-24 DAA2 & DAX — P/N 53265:A1 8/24/2011...
Page 27
TB3 on CPS-24 If batteries are not in the same cabinet as the DAA2s, wiring must be in conduit that is 20 ft. long (6.09 m) or less. Figure 2.11 Four DAA2s Sharing Batteries DAA2 & DAX — P/N 53265:A1 8/24/2011...
20mA across the terminals to activate. Nominal 24VDC. REF ALM REF ALM Figure 2.13 Alarm Bus Connections to NAC Refer to the SLC manual and specific panel or power supply manual for more information. DAA2 & DAX — P/N 53265:A1 8/24/2011...
Digital Audio Loop (DAL) for programming; alarm, control, trouble, automatic audio messages, address and firefighter telephone data; and live voice paging communications. Figure 2.15 illustrates an example of how a DAL can be formed using mixed wire and fiber connectors. DAA2 & DAX — P/N 53265:A1 8/24/2011...
(Refer to the FFT appendix in the DVC Digital Voice Command manual for more information on limits.) “Install FTM” selected - FireFighter Telephones must be wired to the output of the FTM modules. The telephone points will be SLC addresses. DAA2 & DAX — P/N 53265:A1 8/24/2011...
Page 31
An FHS firefighter handset may be used with the phone jacks in Figure 2.16. For a description of the DVC firefighter telephone network operation, refer to the FFT appendix in the DVC Digital Voice Command manual. DAA2 & DAX — P/N 53265:A1 8/24/2011...
Stereo input shown. Monophonic input may connect to either AUXA R or AUXA L. Figure 2.18 AUX A Auxiliary Audio Input Background music will be silenced while batteries greater than 26AH are being fully charged. DAA2 & DAX — P/N 53265:A1 8/24/2011...
• Ckt 3 (TB12) • Ckt 4 (TB13) - TB 13 may act as a 4-wire return for TB12 OUT 3 TB12 SHIELD OUT 4 TB13 SHIELD DAA2 Figure 2.19 Speaker Circuit Connections DAA2 & DAX — P/N 53265:A1 8/24/2011...
Page 34
20k ohm end-of-line resistor, OUT 3 p/n ELR-20K SHIELD TB13 20k ohm end-of-line resistor, OUT 4 p/n ELR-20K SHIELD One DAA2 Class A Circuit, Two Class B Circuits Figure 2.20 Normal Riser Mode Class Configurations DAA2 & DAX — P/N 53265:A1 8/24/2011...
Page 35
Do not use background music in this mode. The DAA2 will provide speaker circuit supervision only when idle. SLC Control Module SLC Control Module 20k ELR (Class B) DAA2 SLC Control Module TB10 Figure 2.22 DAA2 Riser Mode to Control Modules DAA2 & DAX — P/N 53265:A1 8/24/2011...
Page 36
DAA2 TB10 DAA2 and power DAA2 and power supply must share a supply must share a common ground. common ground. Supervised Speakers Unsupervised Speakers Figure 2.24 DAA2 Riser Mode to RSM-1A/AIM-1A Modules DAA2 & DAX — P/N 53265:A1 8/24/2011...
Page 37
VeriFire Tools programming. The speaker wiring from backup to primary is unsupervised when the backup amplifier is not active; therefore the backup and primary amplifiers must be in the same enclosure, or in conduit within the same room. DAA2 & DAX — P/N 53265:A1 8/24/2011...
Page 38
The BKUP1through BKUP4 terminals on the DAA2 may be used to connect a backup amplifier to one or more primary amplifiers. NOTE: Each backup terminal block contains two sets of terminals. One set may be used for “Backup In” applications, the other set for “Backup Through” applications. DAA2 & DAX — P/N 53265:A1 8/24/2011...
Page 39
TB17 to-many backup* Speaker Circuit OUT4, TB13 *Note: No end-of-line resistor is necessary at the last primary amplifier backup terminal. Figure 2.27 One-to-one or One-to-Many Backup Using BKUP Terminal Blocks DAA2 & DAX — P/N 53265:A1 8/24/2011...
Addresses one (1) through 32 may be used for digital communication. Address 00 and addresses above 32 will generate a DAA2 trouble. The default address setting for the DAA2 as it arrives from the factory is 00. DAA2 & DAX — P/N 53265:A1 8/24/2011...
Refer to the appropriate panel manual or the VeriFire Tools Read Status Service Form. A DAA2 speaker circuit may be disabled through NCA-2 and NFS2-3030 Alter Status panel programming and ACS programming. DAA2 & DAX — P/N 53265:A1 8/24/2011...
These Digital Audio Amplifiers are multi-featured amplifiers with digital audio functionality. They are designed to work with the DVC Digital Voice Command. NOTE: The term DAX is used in this manual to refer to all the DAX model versions listed in Table 3.1.
Utilizes wire sizes 12-18 AWG. Battery Fuse (F2) 10A. NOTE: 50 Watt DAX boards do not have an onboard battery charger. A UL 864 listed power supply rated for the battery requirements of the specific application is suitable for charging purposes.
DAX Digital Audio Amplifiers Speaker Circuits - TB4 and TB5 Power-limited outputs* * Exception: A DAX-3570 and DAX-5070 speaker circuit used with any Canadian Room Isolator modules is non-power-limited. DAX-5025/70 - Each circuit rated up to 50 watts.** DAX-3525/70 - Each circuit rated up to 35 watts.** **Total wattage may vary.
Yellow Illuminates steadily while audio amplifier failure is detected. Green Illuminates steadily while analog signal is on speaker circuit 2, or while 200Hz tone is on speaker circuit 2. Table 3.1 DAX LED Indicators (1 of 2) DAA2 & DAX — P/N 53265:A1 8/24/2011...
The DAX arrives from the factory already installed on its chassis. A BDA-25/70V, NCM, or HS-NCM can be mounted on it. (Refer to Figure 3.4). The DAX chassis mounts in an EQ Series cabinet, as well as in a CAB-4 Series cabinet.
EQ Series Cabinets and Doors The EQ Series cabinets come in B, C, and D sizes. The row spacing allows DAX amplifiers to be mounted in any row, and the doors are equipped with ventilated panels for heat dissipation. The cabinets were designed so that all DAX boards can be used in any or all cabinet rows.
Page 50
DAX Digital Audio Amplifiers DAX Installation DAX Mounting Locations Figure 3.3 EQCAB-D4 Backbox and EQDR-D4 Door DAA2 & DAX — P/N 53265:A1 8/24/2011...
Batteries for the DAX may be installed in any of the following configurations: • In the bottom of a CAB-4 series cabinet that holds the DAX. • In a cabinet adjacent to the cabinet that holds a DAX, with connections in conduit. DAA2 & DAX — P/N 53265:A1 8/24/2011...
AC Power WARNING: High Voltages Present. Use extreme caution when working with the DAX. High voltage and AC line-connected circuits are present. Turn off and remove all power sources. To reduce the risk of electric shock, make sure to properly ground the board.
Page 53
DAX-35: Up to four DAX-35s may share a set of batteries. • The ground fault switch on the DAX (SW5) must be set to “Disable” on all but one 35 watt DAX attached to the set of batteries. • In VeriFire Tools programming, “Disable Charger” must be checked in the “DAX Amplifier Programming Service - General II”...
Page 54
Connect all DAXs sharing a set of batteries directly to the batteries using 12 AWG. If the batteries are located outside of the DAX cabinet, the wiring must be in conduit that is no greater than 20 ft. (6.09 m) long.
DAX Installation DAX Digital Audio Amplifiers Alarm Bus The DAX general alarm connections are used to receive general alarm messages from an FACP via an SLC device, or via the Notification Appliance Circuit of an FACP or power supply. SLC to...
Page 56
Fiber and Wire/Fiber Connections DAX boards are wire, but may be converted partially or fully to fiber boards with the use of DS- FM or DS-SFM fiber option modules. Refer to Section 5, “Fiber Option Modules”, on page 75 for installation instructions.The fiber, or wire/fiber cabling between these ports provides a Digital...
DAX Installation DAX Digital Audio Amplifiers A DS-RFM fiber module must be used to connect a DAX to a multi-mode fiber DVC or DAA. Refer to “Fiber Option Modules” on page 75 for more information on this module. NOTE: If a fiber option module is installed at a DAP, that DAP may not also be used for a wire connection.
Page 58
When a DAX’s Speaker Riser Mode is programmed N (refer to the DVC Digital Voice ORMAL Command manual for programming description), the amplified signal from the DAX may be connected directly to speakers. Following are illustrations of Class A and Class B configurations (Figure 3.15).
Page 59
Digital Voice Command manual for programming), the amplified signal from the DAX may be routed to multiple speaker circuits using SLC control modules. Do not use background music in this mode. The DAX will provide speaker circuit supervision only when idle.
Page 60
FACP so that it interrupts the module’s 24VDC power for two seconds. NFS2-3030 example: Give the module’s 24VDC source a common ground with the DAX amplifier. Power the isolator module through a relay module that has Special Zone 14 in its CBE list. Special Function Zone 14 will activate for ten seconds when a reset is initiated at the panel.
Page 61
(Refer to the DVC Digital Voice Command manual for programming), the amplified signal from the DAX is routed to a CIM-2A module, which feeds the signal to one or two CSM-1A modules. A pre-announce tone of 800 Hz will clear a local silence.
Page 62
One-to-One Backup Using BDA-25/70V Figure 3.21 shows the installation of a BDA-25/70V backup digital amplifier onto the primary amplifier. Should the amplifier portion of the DAX fail, all its messages will still be played by the BDA as programmed. 2. Align BDA 1.
Page 63
BKUP2 amplifier for one- TB 11 to-many backup* TB11 TB11 *Note: No end-of-line resistor is necessary at the last primary amplifier backup terminal. Figure 3.22 One-to-one or One-to-Many Backup Using BKUP Terminal Blocks DAA2 & DAX — P/N 53265:A1 8/24/2011...
Canadian room isolator modules Non-power- limited Non-power- circuits limited circuits to Canadian room isolator modules DAX-3570 or DAX-5070 Figure 3.24 Backbox Wiring with DAX-3570 or DAX-5070 and Canadian Room Isolator Modules DAA2 & DAX — P/N 53265:A1 8/24/2011...
Address 00 and addresses above 32 will generate a DAX trouble. The default address setting for the DAX as it arrives from the factory is 00. 3.3.2 Programming The DAX is programmed through VeriFire Tools. Refer to the DVC Digital Voice Command...
An NCA-2, NFS2-3030, NFS-3030, and network workstation, as well as a computer running VeriFire Tools, will be able to read the status of a DAX and its speaker circuits. Refer to the appropriate panel manual or the VeriFire Tools Read Status Service Form.
The BDA-25V and BDA-70V backup digital amplifiers provide an economical means of backing up DAA2 and DAX amplifiers in a one-to-one primary/backup configuration. A BDA can also provide a second audio channel for a DAA2 when programmed as a primary amplifier in VeriFire Tools.
BDA Backup Digital Amplifiers Board Layout 4.2.3 When Used with DAX-50 • With BDA-25/70 card used as backup, 50 watts audio output from the DAX, or 50 watts audio output from the BDA. 4.2.4 When Used with DAX-35 • With BDA-25/70 card used as backup, 35 watts audio output from the DAX, or 35 watts audio output from the BDA.
BDA - refer to Power and Figure 4.4 on Control Harness page 70): Connections • J1 on BDA to J6 on DAA2 • J2 on BDA to J5 on DAA2 Figure 4.2 BDA-25V/70V Installation, DAA2 DAA2 & DAX — P/N 53265:A1 8/24/2011...
BDA Backup Digital Amplifiers Installation 4.4.2 DAX Figure 4.3 shows the installation of a BDA-25/70V onto a DAX amplifier. The BDA may be programmed and wired for backup. 1. Attach four standoffs at locations indicated. 2. Align BDA over standoffs.
This switch should be set to off-normal only when testing the system’s operation. Figure 4.6 FAIL TEST Switch Otherwise it should always be set to NORMAL. DAA2 & DAX — P/N 53265:A1 8/24/2011...
• All three charging capabilities available (see Table 2.2, “Battery Charging Capabilities,” on page 14). • Requires external backup with the same configuration (DAA2 Group 1 with a BDA). CHARGER Figure 4.9 One Group, Two Channel DAA2 & DAX — P/N 53265:A1 8/24/2011...
• BDA as backup. • Two charger settings available. See Table 2.2, “Battery Charging Capabilities,” on page 14 for settings. • Does not require external backup. Group 1 CHARGER Figure 4.12 One Group with Backup DAA2 & DAX — P/N 53265:A1 8/24/2011...
Charging Capabilities,” on page 14 for settings. Group 1 CHARGER Figure 4.13 One group, Two Channel 4.5.4 Operation Volume The volume of the BDA’s group can be changed using VeriFire Tools, NCA-2, ONYXWORKS, or direct-connect NFS2-3030. DAA2 & DAX — P/N 53265:A1 8/24/2011...
(with the exception of single- and multi-mode DVCs and DAAs). One or two fiber option modules may be connected to a DAX or DAA2 board to convert it from a board with two wire DAP ports to: •...
Green Illuminates while data is received on the digital audio port. Light will flicker, turning on when activity is detected and off when it is not. Table 5.2 DS-FM LED Indicators DAA2 & DAX — P/N 53265:A1 8/24/2011...
(included with option module) at module the three points indicated. 2. Align option module over the standoffs and plug into DAX at pin Pin Connectors connectors. 3. Screw module to standoffs with three screws (p/n 38134) included with option module.
Fiber Option Modules Installation 5.3.3 Single- or Multi-mode DVC (DVC-PCB or less) or DAA Installation Single-mode A DS-SFM must be used to connect a DAA2 or DAX to a single-mode fiber DVC or DAA. ST* Style Connections Single-mode Fiber DAL Cable...
** When the amplifier is active, the column A charger entry must be 0.79 or the column C entry must be 0.58, no matter what size the charger is. Table A.1 AC Draw Worksheet for DAA2-5025 DAA2 & DAX — P/N 53265:A1 8/24/2011...
Page 80
** When the amplifier is active, the column A charger entry must be 0.79 or the column C entry must be 0.58, no matter what size the charger is. Table A.2 AC Draw Worksheet for DAA2-5070 DAA2 & DAX — P/N 53265:A1 8/24/2011...
Page 81
** When the amplifier is active, the column A charger entry must be 0.79 or the column C entry must be 0.58, no matter what size the charger is. Table A.3 AC Draw Worksheet for DAA2-7525 DAA2 & DAX — P/N 53265:A1 8/24/2011...
2.09A allowed of 1.18A * A DAX-5025 used as a backup will draw the same power as a primary when it is active. Table A.4 AC Draw Worksheet for DAX-5025 DAX-5070 120V 50/60Hz 220-240V 50/60Hz 2.35A max.
Page 83
2.97A allowed of 1.66A * A DAX-3525 used as a backup will draw the same power as a primary when it is active. Table A.6 AC Draw Worksheet for DAX-3525 DAX-3570 120V 50/60Hz 220-240V 50/60Hz 3.06A max.
NOTE: Battery Sharing - When batteries are shared by two or more DAA2s, Table B.1 must be completed for each DAA2. The totals for Columns A and Columns B must be summed and entered into Table B.2 where indicated. DAA2 & DAX — P/N 53265:A1 8/24/2011...
Table B.4 Current Draw Calculations Per DAX NOTE: Battery Sharing - When batteries are shared by two or more DAXs, Table B.4 must be completed for each DAX. The totals for Columns A and Columns B must be summed and entered into Table B.5 where indicated.
They are designed for a networked or non-networked environment with the DVC Digital Voice Command. DAA models are compatible with other types of DAL devices (e.g. DAA2, DAX) on a wire, fiber, or mixed wire/fiber digital audio loop. A DS-RFM (for multi-mode DAAs) or DS-SFM (for single- mode DAAs) is required for a fiber DAA used on a DAL with other types of DAL devices.
Relay contacts that will activate on a trouble condition. • Backup amplifier function. • Programmable through VeriFire Tools. • Meets UL requirements for 800 Hz to 2.8 KHz bandwidth. Meets ULC requirements for 400 Hz to 4 KHz bandwidth. DAA2 & DAX — P/N 53265:A1 8/24/2011...
Fiber optic cable, multi-mode: 50/125 or 62.5/125 micrometers. Fiber optic cable, single-mode: 9/125 micrometers. Attenuation of cabling between two nodes (fiber-optic circuits are point-to-point) must not exceed the Maximum attenuation, specified below. To determine attenuation: DAA2 & DAX — P/N 53265:A1 8/24/2011...
Page 92
Speaker Circuits - TB10, TB11, TB12 and TB13 Power-limited outputs. DAA-5025/70 - 50 Watts dynamically shared among the four outputs. DAA-7525 - 75 Watts dynamically shared among the four outputs. Supervision determined by programming. DAA2 & DAX — P/N 53265:A1 8/24/2011...
Page 93
Recommended wiring: 12-18 AWG twisted -pair (shielded recommended). Class B (Style Y) or Class A (Style Z): Class B requires 20k end-of-line resistors (included, P/N ELR-20K). Class A requires 10k end-of-line resistors (included, P/N R-10K) on the return. DAA2 & DAX — P/N 53265:A1 8/24/2011...
It is silkscreened with Future Use Dotted rectangular area indicates case. DAA-PS Power Supply Board AC INPUT EARTH Refer to NEUTRAL page 103 Figure C.2 Connection Locations for Wire Version DAA Boards DAA2 & DAX — P/N 53265:A1 8/24/2011...
Page 95
LED Indicators. Refer to Table C.3 on page 98 +5V AUX TRBL E. FAULT Jumper JP2 Refer toTable C.4 on page 99 DAA Power Supply Board Figure C.3 LED Indicator, Jumper and Switch Locations DAA2 & DAX — P/N 53265:A1 8/24/2011...
This example shows a B board. It is silkscreened with PCB AUXB SHLD AUX B AUXB - AUXB + Refer to page 111 Figure C.4 Connection Locations for Fiber Version DAA Boards DAA2 & DAX — P/N 53265:A1 8/24/2011...
AMP FAIL Yellow Illuminates steadily while audio amplifier failure detected. ON 4 Green Illuminates steadily while analog signal is on speaker circuit 43, or while 200Hz tone is on speaker circuit 4. DAA2 & DAX — P/N 53265:A1 8/24/2011...
Page 98
– 4 blinks - CHARGER TROUBLE. Priority 4, lowest priority. If multiple troubles are present, the highest priority trouble will blink until cleared, then the next priority trouble will blink until cleared, etc. Table C.3 LED Indicators DAA2 & DAX — P/N 53265:A1 8/24/2011...
Verify stud height and cut if stud DAA row in backbox exceeds 0.375 in. (9.525 mm). See note and warning above. Figure C.6 Using Older Backboxes DAA2 & DAX — P/N 53265:A1 8/24/2011...
Figure C.2 on page 94 for how to determine board type. Batteries other than the 12 AH batteries in the DAA chassis must be accommodated in separate cabinets or battery backboxes. The following models are available: DAA2 & DAX — P/N 53265:A1 8/24/2011...
• In a CHS-BH1 battery chassis (12AH batteries only), designed for use with the DAA chassis. • In the bottom of a CAB-4 series cabinet that holds the DAA. • In a cabinet adjacent to the cabinet that holds a DAA, with connections in conduit. DAA2 & DAX — P/N 53265:A1 8/24/2011...
Close the hinged cover for TB1 after wiring but before energizing. The DAA power supply requires connection to a separate dedicated AC branch circuit. Follow these guidelines when connecting the AC branch circuit: • Label the branch circuit “Fire Alarm”. DAA2 & DAX — P/N 53265:A1 8/24/2011...
DAA in one of the rows. Shorter battery cables (18”, 0.5 m) are included with the CHS-BH1. For battery sharing, use 12 AWG wire either in the same cabinet, or in conduit for no more than 20 ft. (6.09 m.). DAA2 & DAX — P/N 53265:A1 8/24/2011...
Page 105
NOTE: This designation must be made for the 75 watt boards as well as the 50 watt boards. Only one DAA should have its JP2 set to Enable, and only one DAA should have a working charger. These DAAs do not have to be the same. DAA2 & DAX — P/N 53265:A1 8/24/2011...
Page 106
TB3 on CPS-24 If batteries are not in the same cabinet as the DAA2s, wiring must be in conduit that is 20 ft. (6.09 m) long or less. Figure C.14 Four DAAs Sharing 55AH Batteries DAA2 & DAX — P/N 53265:A1 8/24/2011...
Alarm Bus requires 16VDC at 20mA to activate. Figure C.16 Alarm Bus Connections to NAC Refer to the SLC manual and specific panel or power supply manual for more information. DAA2 & DAX — P/N 53265:A1 8/24/2011...
Page 108
To another DAA conversion charts for type V and type H modules. Figure C.17 Trouble Bus to FMM-1 Refer to the SLC manual and specific panel manual for more information on panel and SLC wiring. DAA2 & DAX — P/N 53265:A1 8/24/2011...
Fiber ports RXA, RXB, TXA and TXB allow digital communication with DVC fiber boards. When used with other types of DAL devices (e.g. DAA2, DAX) a DS-RFM or DS-SFM fiber option module is required on the DAL device. (Refer to Section 5 on page 75.
Class A or Class B for trouble supervision. Class B 2-Wire configurations require a 3.9K ohm 1/2 watt end-of-line resistor (P/N R-3.9K). There are two ways that FireFighter Telephones may be installed on a DAA FFT riser. Both configurations have a limit of 7 active phones. DAA2 & DAX — P/N 53265:A1 8/24/2011...
DVC Digital Voice Command manual for how to distinguish PCA from PCB board types. Check VeriFire or an appropriate network display to determine the software version. Auxiliary Inputs A and B The DAA provides two analog audio connections. One or the other may be used, not both. DAA2 & DAX — P/N 53265:A1 8/24/2011...
Class B connections. These connections dynamically share the 50W or 75W output capability of the DAA. A DAA may be wired using the “BKIN” and “BKOUT” terminals to back up an amplifier. If an amplifier fails, the signal automatically switches to the backup amplifier. DAA2 & DAX — P/N 53265:A1 8/24/2011...
Page 114
Up to 7 Up to 7 low-level low-level inputs inputs 10k ELR (Class A) Figure C.26 DAA Riser Mode to Additional Amplifiers Refer to the ACT-25 or ACT-70 installation document for more information. DAA2 & DAX — P/N 53265:A1 8/24/2011...
Page 115
Special Zone 14 in its CBE list. Special Zone 14 will activate for ten seconds when a reset is initiated at the panel.This period is used to disable the 24VDC for those 10 seconds to clear a local silence. DAA2 & DAX — P/N 53265:A1 8/24/2011...
DAA is routed to a CIM-2A module, which feeds the signal to one or two CSM-1A modules. A pre-announce tone of 800 Hz will clear a local silence. Only one Class A or Class B DAA speaker circuit may be installed when operating in this mode. DAA2 & DAX — P/N 53265:A1 8/24/2011...
Page 117
Backup Each DAA acts as a repeater for the digital audio signal. If a primary amplifier falls off-line, the backup will not receive the signal if it is further down the DAL chain. DAA2 & DAX — P/N 53265:A1 8/24/2011...
Page 118
Class A (Style Z), or all wired Class B (Style Y), or all wired with one Class A and two Class B circuits. DAA2 & DAX — P/N 53265:A1 8/24/2011...
0.25 inches (6.35 mm) from any non-power- limited circuit wiring. All power-limited and non-power-limited circuit wiring must enter and exit the cabinet through different knockouts and/or conduits. Power-limited circuits Non-power-limited circuits Figure C.33 Typical Backbox Wiring DAA2 & DAX — P/N 53265:A1 8/24/2011...
DAAs may be used on a DAL with other devices that have different earth fault detection (e.g., DAA2, DAX). Refer to the DAL Earth Fault Detection appendix in the DVC Digital Voice Command manual for examples of how to mix devices with different earth fault detection.
DVC. Clears local signal silences and reinitializes the After causes of DAA trouble amplifier if it turned off due to overcurrent messages have been protection. cleared. Table C.5 Pushbutton Controls DAA2 & DAX — P/N 53265:A1 8/24/2011...
NOTE: Battery Sharing - When batteries are shared by two or more DAAs, Table C.6 must be completed for each DAA. The totals for Columns A and Columns B must be summed and entered into Table C.7 where indicated. DAA2 & DAX — P/N 53265:A1 8/24/2011...
Page 127
Manufacturer's Return Material Authorization form. The replacement part shall come from Manufacturer's stock and may be new or refurbished. THE FOREGOING IS DISTRIBUTOR'S SOLE AND EXCLUSIVE REMEDY IN THE EVENT OF A WARRANTY CLAIM. Warn-HL-08-2009.fm DAA2 & DAX — P/N 53265:A1 8/24/2011...
Page 128
World Headquarters 12 Clintonville Road Northford, CT 06472-1610 USA 203-484-7161 fax 203-484-7118 www.notifier.com...