AQ-C
NOTE
When used for the load less than rated
In the case of the load current less than
rated, malfunction may result from the
residual voltage across the both ends of
the load even if the solid state relay is
turned off.
Use a dummy resistor as a
countermeasure.
The total of the current through the
resistor and the load current must exceed
the min. rated load current.
R
(Dummy resistor)
0
( + )
Load
Load power source
( – )
Input power source
For Cautions for Use.
In case the dummy resistor is not used,
keep in mind that the residual voltage
becomes as follows:
Example:
For the inductive load by the 5 mA load
current and the 200 V AC load voltage,
the load impedance becomes 40 kW and
Ve/V = 16% is estimated from the below
graph.
Accordingly, the 32 V voltage remains
across the both ends of the load when
the solid state relay is turned off.
8
5
1
16
+
All Rights Reserved © COPYRIGHT Panasonic Electric Works Co., Ltd.
• Characteristics of residual voltage
vs. load impedance
100
f = 60 Hz
Ve: Residual voltage
V: Power voltage
80
1
Load
V
SSR
Ve
60
Ve
×
2
100 , %
V
40
20
0
20
40
60
Load impedance, kΩ
Power factor: 1
(resistive load)
Power factor: 0.4
(inductive load)
80