Heating Capacity Table - Philips WH-UD16CE5-A-1 Service Manual

Air-to-water hweatpump
Table of Contents

Advertisement

19.2 Heating Capacity Table

19.2.1 WH-SDC07C3E5 WH-UD07CE5-A (WH-SDC07C3E5-1 WH-UD07CE5-A-1)
LWC
Tamb
-15
-7
2
7
25
HC: Heating Capacity (kW)
IP: Power Input (kW)
LWC: Leaving Water Condenser Temperature (°C)
Tamb: Ambient Temperature (°C)
19.2.2 WH-SDC09C3E5 WH-UD09CE5-A (WH-SDC09C3E5-1 WH-UD09CE5-A-1)
LWC
Tamb
-15
-7
2
7
25
HC: Heating Capacity (kW)
IP: Power Input (kW)
LWC: Leaving Water Condenser Temperature (°C)
Tamb: Ambient Temperature (°C)
19.2.3 WH-SDC12C6E5 WH-UD12CE5-A (WH-SDC12C6E5-1 WH-UD12CE5-A-1)
LWC
Tamb
-15
-7
2
7
25
HC: Heating Capacity (kW)
IP: Power Input (kW)
LWC: Leaving Water Condenser Temperature (°C)
Tamb: Ambient Temperature (°C)
30
35
HC
IP
HC
IP
4.60
1.87
4.60
2.00
5.15
1.80
5.15
1.94
6.70
1.83
6.55
1.98
7.00
1.43
7.00
1.59
7.00
0.79
7.00
0.93
30
35
HC
IP
HC
IP
6.00
2.55
5.90
2.68
6.10
2.16
5.90
2.36
6.80
1.87
6.70
2.16
9.00
1.93
9.00
2.20
9.00
1.07
9.00
1.27
30
35
HC
IP
HC
IP
9.30
3.50
8.90
3.66
10.40
3.41
10.00
3.70
11.80
3.14
11.40
3.35
12.00
2.14
12.00
2.57
12.00
1.42
12.00
1.70
40
45
HC
IP
HC
IP
4.60
2.19
4.60
2.42
5.08
2.14
5.00
2.38
6.58
2.29
6.60
2.64
7.00
1.77
7.00
2.12
6.40
1.03
6.10
1.17
40
45
HC
IP
HC
IP
5.50
2.82
5.40
3.00
5.85
2.63
5.80
2.90
6.70
2.38
6.60
2.64
9.00
2.45
9.00
2.81
8.40
1.40
8.00
1.59
40
45
HC
IP
HC
IP
8.50
3.83
8.10
3.99
9.60
3.99
9.20
4.28
11.00
3.57
10.60
3.78
12.00
3.00
12.00
3.43
11.80
1.98
11.70
2.27
164
50
55
HC
IP
HC
IP
4.55
2.68
4.50
3.00
4.90
2.47
4.80
2.67
6.30
2.90
6.00
3.16
6.90
2.30
6.80
2.72
5.90
1.33
5.70
1.49
50
55
HC
IP
HC
IP
5.20
3.14
5.00
3.33
5.80
3.06
5.80
3.22
6.30
2.90
6.00
3.16
8.95
3.23
8.90
3.87
7.80
1.81
7.50
2.03
50
55
HC
IP
HC
IP
7.50
4.09
7.00
4.20
8.70
4.30
8.20
4.31
9.80
3.98
9.10
4.18
12.00
3.82
12.00
4.20
11.50
2.53
11.40
2.78

Advertisement

Table of Contents
loading

Table of Contents