Preparations Before Installation - Panasonic CS-25DM1HPK Installation Manual

Packaged air conditioner
Table of Contents

Advertisement

(2) Ceiling height
This unit can be installed in ceilings up to 3.8 meters high. If the ceiling height exceeds 2.7 meters, how-
ever, the connector of terminal board (A2P) must be replaced and an air outlet blocking pad must be
installed. See HIGH CEILING INSTALLATION (P .13).
(3) If you feel there is danger as a result of investigating whether the place you want to install the unit can hold
its weight, reinforce with a board or beam, etc., before installing. (Because installation pitch is recorded on
the paper pattern for installation, check wheter reinforcement will be required or not along with referring to
the paper pattern.)

4. PREPARATIONS BEFORE INSTALLATION

(1) Relation of ceiling opening to suspension bolt position
Model
CS-25 · 32 · 40DM1HPK
CS-63DM1HPK
(2) Open a hole in the ceiling for installation. (Case of existing ceiling)
• Use the paper pattern for installation which has been adjusted to the dimensions of the ceiling opening.
• Open a hole in the ceiling for installation at the place the unit is to be installed, and run refrigerant and
drain piping, remote controller cord, and outdoor/indoor transmission wiring to the unit's piping and wir-
ing hole. (For wiring procedure, refer to "WIRING EXAMPLE AND HOW TO SET THE REMOTE CON-
TROLLER." For piping procedure, refer to the attached installation manual of the outdoor unit.)
• After opening a hole in the ceiling, reinforcement of the ceiling frame, etc., may be required to maintain
the levelness of the ceiling and to prevent vibration of the ceiling. For details, consult with your builder
and interior contractor.
5
150 cm
or more
(Discharge side)
A
B
C
1110
1150
1200
1310
1350
1400
〈Set-up example〉
Note) All parts shown in the figure above are field supplied parts.
2 cm or more
(Suction side)
D
1240
1440
Ceiling slab
Anchor
Wing nut or turnbuckle
Suspension bolt
Ceiling surface
Decoration
panel
Ceiling
opening
Indoor unit
Suspension
bolt
4
A
B
C
D
English

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cs-32dm1hpkCs-63dm1hpkCs-40dm1hpk

Table of Contents