Download Print this page

Specifications - Fujitsu ARG36TLC3 Service Manual

Advertisement

MODELS
COOLING CAPACITY
HEATING CAPACITY
ELECTRICAL DATA
POWER SOURCE
RUNNING CURRENT
(A)
INPUT WATTS
(kW)
E.E.R.
(kW/kW)
MOISTURE REMOVAL
AIR CIRCULATION-Hi
Note : The above list shows values at the external static pressure of 98 Pa. (10 mm Aq.).
COMPRESSOR
TYPE
CODE
FAN MOTOR
TYPE
HI-SPEED
INDOOR UNIT
MED-SPEED (r.p.m.)
LO-SPEED
TYPE
OUTDOOR UNIT
HI-SPEED
Note : The above list shows values at the external static pressure of 0 Pa, 415V.
DIMENSIONS
INDOOR UNIT
H x W x D
OUTDOOR UNIT
WEIGHT
INDOOR UNIT
NET / GROSS (kg)
OUTDOOR UNIT
ADDITIONAL REFRIGERANT CHARGE (R407C)
PIPE LENGTH
MODELS
ARG36TLC3
FULL CHARGE
ARY36TLC3
AMOUNT
ARG45TLC3
(R407C)
ARY45TLC3
Note : In the case that 20 m are exceeded, when using a connection pipe other than that in the table,
charge additional refrigerant with 30 g (1.06 oz) / 1 m (3.3 ft) as the criteria.
S P E C I F I C A T I O N S
ARG36TLC3
ARY36TLC3
AOG36TPB3L
AOY36TPB3L
(kW)
10.3 - 10.5
(kW)
10.8 - 11.0
COOL
7.1 - 6.9
HEAT
5.9 - 5.9
COOL
4.15 - 4.17
HEAT
3.34 - 3.37
COOL
2.48 - 2.52
HEAT
3.23 - 3.26
( /hr)
4.0
(m
3
/hr)
2,000
Hermetic type, 2 pole, 3-phase, Induction motor, Scroll
ZR49KCE-TFD
(r.p.m.)
1,280
1,200
(r.p.m.)
1,130
(r.p.m.)
(mm)
100 / 114
10 m
20 m
(33 ft)
(66 ft)
2,600 g
(91.9 oz)
3,500 g
(123.7 oz)
ARG45TLC3
AOG45TPB3L
AOY45TPB3L
12.4 - 12.7
14.0 - 14.3
3N 380 - 415V 50Hz
8.3 - 8.5
8.4 - 8.5
4.73 - 4.79
4.73 - 4.80
2.62 - 2.65
2.96 - 2.98
5.5
2,200
ZR61KCE-TFD
MFA-45BTT
1,320
1,270
1,200
MFB-362FT
770
270 x 1,210 x 700
1,152 x 940 x 370
45 / 60
110 / 124
30 m
40 m
(99 ft)
(132 ft)
2,900 g
3,200 g
(102.5 oz)
(113.1 oz)
3,800 g
4,100 g
(134.3 oz)
(144.9 oz)
- 1 -
ARY45TLC3
50 m
Additional
(164 ft)
refrigerant
3,500 g
(123.7 oz)
30 g / m
4,400 g
(1.06 oz / 3.3 ft)
(155.5 oz)
2003.08.28

Hide quick links:

Advertisement

loading