Ambirad SmartCom2 Installation And User Manual

Factory set to operate on warm air systems
Hide thumbs Also See for SmartCom2:

Advertisement

SmartCom
Installation and User Manual
for Lite, Standard, Advanced and Network versions
The SmartCom
settings for radiant products please refer to Section 4, Engineer Functions.
Increase a value
PLUS
Decrease a value
MINUS
Accept a newly entered value
OK
Press once to cancel overtime, vent,
exam, off and holiday modes or a
newly entered value not yet OK'd
UNDO
12
Change the settings (see diagram
9
3
below)
6
SETTINGS
SET
TEMPERATURES
12
9
6
SETTINGS
12
SET
9
3
PROGRAM
6
TIMES
SETTINGS
SET
12
VENT
9
ONLY
6
MODE
SETTINGS
2
control is factory set to operate on warm air systems. To change

Quick Guide

3
Initialise Programming
Press repeatedly to
access required setting
3
Press to return
to main display
12
9
3
6
SETTINGS
SET
HEAT ONLY
MODE
FROST ONLY
Initiate a period of forced
vent operation
VENT ONLY
Initiate or quickly extend a
period of heating
OVERTIME
Set the control to holiday
mode
HOLIDAY
Toggle the display to show
the temperatures
CHECK TEMP
Clear a fl ame failure lockout
LOCKOUT
12
9
3
6
SETTINGS
UNDO
12
9
6
12
SETTINGS
9
3
SET
6
AUTO
SETTINGS
MODE
SET
MODE
2
SET
OFF
12
9
3
6
SETTINGS
12
SET
9
3
CLOCK
6
SETTINGS
SET
EXAM
MODE
Optional
3

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SmartCom2 and is the answer not in the manual?

Questions and answers

Summary of Contents for Ambirad SmartCom2

  • Page 1: Quick Guide

    SmartCom Installation and User Manual for Lite, Standard, Advanced and Network versions The SmartCom control is factory set to operate on warm air systems. To change settings for radiant products please refer to Section 4, Engineer Functions. Quick Guide Initiate a period of forced Increase a value vent operation PLUS...
  • Page 2: Table Of Contents

    SmartCom Control Installation and User Manual CONTENTS Introduction ........................... 3 Technical Specifi cations ....................3 Operating Environment ................... 3 Performance Specifi cations ................3 Lite Version Electrical Specifi cations ............... 4 Standard Version Electrical Specifi cations ............. 4 Advanced and Network Version Electrical Specifi cations ......4 Installation Instructions ....................
  • Page 3: Introduction

    SmartCom Control Installation and User Manual INTRODUCTION This manual describes the Installation and Operation of the ‘SmartCom ’ control unit. NB This control must be installed according to the current IEE Wiring Regulations and should include full disconnection means and fusing appropriate to the connected loads.
  • Page 4: Lite Version Electrical Specifi Cations

    SmartCom Control Installation and User Manual 1.3 Lite Version Electrical Burner reset, Heat and 7A/240Vac resistive Specifi cations Vent 1 relay rating: 2A/240Vac inductive Control power consumption: 1.4 Standard Burner reset, Heat and 7A/240Vac resistive Version Electrical Std Vent 1 relay rating: 2A/240Vac inductive Specifi...
  • Page 5: Installation Instructions

    SmartCom Control Installation and User Manual 2 INSTALLATION INSTRUCTIONS ● Remove the screws. 2.1 Mounting the Control Assembly ● Carefully lift the lid and unplug the The housing consists of a two ribbon cable from the power PCB part plastic moulding held assembly situated in the bottom of together by four screws.
  • Page 6 SmartCom Control Installation and User Manual Figure - Controller mounting holes ● A drilling template is provided to enable the controller assembly to be securely fi xed to a solid surface. Figure - Minimum height above fl oor level. ● Ensure that the controller is installed no less than 1.5m above the fl...
  • Page 7: General Wiring Specifi Cations

    SmartCom Control Installation and User Manual 2.2 General Wiring Specifi cations Connect as shown below. All wiring connections must be made by a suitably qualifi ed person. Please refer to the following wiring connection drawings (2.3 to 2.6) and observe the note at the bottom of each page referring to cable type and length.
  • Page 8: Standard Version Wiring Connections

    SmartCom Control Installation and User Manual 2.4 STANDARD VERSION WIRING CONNECTIONS S/R0 S/R1 NEUT LIVE 5 6 40 41 1 2 10 Figure - Standard version PCB connections Terminal No: Connection Capacity mm Burner Reset output Time relay output Heat 1 relay output Vent 1 relay output Vent 1 relay input (550W relay version only)
  • Page 9: Advanced Version Wiring Connections

    SmartCom Control Installation and User Manual 2.5 ADVANCED VERSION WIRING CONNECTIONS S/R1 S/R0 FUSE LIVE NEUT 41 40 14 5 1/L 2/N 10 Figure - Advanced version PCB connections Terminal No: Connection Capacity mm Vent 1 relay input (550W/low fan) Vent 1 relay output (550W/low fan) Heat 2 relay input (2 stage) Heat 2 relay output (2 stage)
  • Page 10: Network Version Wiring Connections

    SmartCom Control Installation and User Manual 2.6 NETWORK VERSION WIRING CONNECTIONS S/R1 S/R0 FUSE LIVE NEUT 41 40 14 5 1/L 2/N 10 Figure - Network version PCB connections Terminal No: Connection Capacity mm Vent 1 relay input (550W/low fan) Vent 1 relay output (550W/low fan) Heat 2 relay input (2 stage) Heat 2 relay output (2 stage)
  • Page 11: Operating Instructions

    SmartCom Control Installation and User Manual 3 OPERATING INSTRUCTIONS 3.1 The Buttons PLUS VENT ONLY OVERTIME LOCKOUT MINUS UNDO SETTINGS HOLIDAY CHECK TEMP The ten buttons have the following functions: Initiate a period of forced Increase a value vent operation PLUS VENT ONLY Initiate or quickly extend a...
  • Page 12: Setting The Clock

    SmartCom Control Installation and User Manual 3.3 Setting the Clock Press the SETTINGS button up to CLOCK 3 times until the set clock display SETTINGS appears. The icons [SET], [CLOCK] and [OK?] will be displayed with the [CLOCK] icon fl ashing. (Enter your PIN code if prompted.) Figure –...
  • Page 13: Setting The Program (On/Off Times)

    SmartCom Control Installation and User Manual Auto mode: Heating and ventilation operate automatically depending on the room temperature, time/set temperature program and the control method AUTO selected. Ventilation is disabled during off periods of the time program. Frost Only mode: Heating operates automatically depending on the room temperature and control method selected.
  • Page 14 SmartCom Control Installation and User Manual Press the SETTINGS button SETPROGRAM repeatedly until the set program SETTINGS display appears. The icons [SET], [PROGRAM] and [OK?] will be displayed with the [PROGRAM] icon fl ashing. Figure - Set Program (Enter your PIN code if prompted.) Press the OK button to accept the Set Program function.
  • Page 15: Setting The Day And Night Temperatures

    SmartCom Control Installation and User Manual 3.6 Setting the Day & Night Temperatures Press the SETTINGS button repeatedly until the icons [SET], [TEMP] and [OK?] are displayed with the [TEMP] icon fl ashing (enter your PIN code if SETTINGS prompted). Press the OK button to accept the Set Temperatures function.
  • Page 16: Networked Controllers (Sc-Net Only)

    SmartCom Control Installation and User Manual ● If you forget the PIN code there is a master PIN code that is factory set by the manufacturer. This master PIN code over-rides the unique PIN code and will enable you to change the PIN code again. Please call the manufacturer for this master PIN code.
  • Page 17: Operating The Master Controller

    SmartCom Control Installation and User Manual 3.8.2 Operating the master controller ● Pressing the CHECK TEMP button on the master controller will display the sensor temperature and set temperature for the master zone (Zone 1) as well as the slave zones (Zone 2, 3, etc.) The fi rst and second press of the CHECK TEMP button will display the sensor temperature and set temperature for Zone 1.
  • Page 18: Setting A Temporary Overtime Extension Period

    SmartCom Control Installation and User Manual 3.11 Setting a temporary overtime extension period Pressing the OVERTIME button will initiate or extend the day-time operation of the controller. Overtime is activated as follows: ● Press the OVERTIME button. The [OVERTIME] icon will be displayed. The hours and minutes digits will fl...
  • Page 19: Error Message:- Lockout

    SmartCom Control Installation and User Manual 3.13 Error Message:- Lockout When the controller detects a fl ame failure signal, the display will clear and show only the [LOCKOUT] icon. The lockout state continues even when the fl ame failure signal clears. In order to reset the lockout state, press the LOCKOUT button.
  • Page 20: Engineer Functions

    SmartCom Control Installation and User Manual 4 ENGINEER FUNCTIONS ● The engineer functions allow you to program various advanced parameters. ● Depending on the version of the controller (i.e. Lite, Standard, Advanced or Network), some options may not be available although displayed. ●...
  • Page 21: Programming The Engineer Functions

    SmartCom Control Installation and User Manual 4.2 Programming The Engineer Functions All engineer functions are displayed as a code in the fi rst two digits of the display, e.g. C1, t1, t2, and a variable in the second two digits. Figure - Engineer variable Press the SETTINGS button until the desired variable code is displayed.
  • Page 22 SmartCom Control Installation and User Manual Radiant / NorRayVac / Herringbone fan Temperature measurement method. delay time (in 10 second steps). Space temperature from F1: Range: 00 to 24 internal sensor only. Default value = 03 (30 secs) Space temperature from remote sensor only.
  • Page 23: External Inputs

    SmartCom Control Installation and User Manual Heating hours saved since the last PIN protection activation. service reset. (Savings hours are the 0 PIN protection off times when the heating is on, but the 1 PIN protection on Heat Stage 1 relay is not on.) Default value = 0 H3: Range: 0 to 9999 Settings menu PIN number.
  • Page 24 SmartCom Due to continuous product innovation, we reserve the right to change product specifi cation without due notice. Document reference number GB/SCOM/120/1206...