SmartCom Installation and User Manual for Lite, Standard, Advanced and Network versions The SmartCom control is factory set to operate on warm air systems. To change settings for radiant products please refer to Section 4, Engineer Functions. Quick Guide Initiate a period of forced Increase a value vent operation PLUS...
SmartCom Control Installation and User Manual INTRODUCTION This manual describes the Installation and Operation of the ‘SmartCom ’ control unit. NB This control must be installed according to the current IEE Wiring Regulations and should include full disconnection means and fusing appropriate to the connected loads.
SmartCom Control Installation and User Manual 1.3 Lite Version Electrical Burner reset, Heat and 7A/240Vac resistive Specifi cations Vent 1 relay rating: 2A/240Vac inductive Control power consumption: 1.4 Standard Burner reset, Heat and 7A/240Vac resistive Version Electrical Std Vent 1 relay rating: 2A/240Vac inductive Specifi...
SmartCom Control Installation and User Manual 2 INSTALLATION INSTRUCTIONS ● Remove the screws. 2.1 Mounting the Control Assembly ● Carefully lift the lid and unplug the The housing consists of a two ribbon cable from the power PCB part plastic moulding held assembly situated in the bottom of together by four screws.
Page 6
SmartCom Control Installation and User Manual Figure - Controller mounting holes ● A drilling template is provided to enable the controller assembly to be securely fi xed to a solid surface. Figure - Minimum height above fl oor level. ● Ensure that the controller is installed no less than 1.5m above the fl...
SmartCom Control Installation and User Manual 2.2 General Wiring Specifi cations Connect as shown below. All wiring connections must be made by a suitably qualifi ed person. Please refer to the following wiring connection drawings (2.3 to 2.6) and observe the note at the bottom of each page referring to cable type and length.
SmartCom Control Installation and User Manual 2.4 STANDARD VERSION WIRING CONNECTIONS S/R0 S/R1 NEUT LIVE 5 6 40 41 1 2 10 Figure - Standard version PCB connections Terminal No: Connection Capacity mm Burner Reset output Time relay output Heat 1 relay output Vent 1 relay output Vent 1 relay input (550W relay version only)
SmartCom Control Installation and User Manual 3 OPERATING INSTRUCTIONS 3.1 The Buttons PLUS VENT ONLY OVERTIME LOCKOUT MINUS UNDO SETTINGS HOLIDAY CHECK TEMP The ten buttons have the following functions: Initiate a period of forced Increase a value vent operation PLUS VENT ONLY Initiate or quickly extend a...
SmartCom Control Installation and User Manual 3.3 Setting the Clock Press the SETTINGS button up to CLOCK 3 times until the set clock display SETTINGS appears. The icons [SET], [CLOCK] and [OK?] will be displayed with the [CLOCK] icon fl ashing. (Enter your PIN code if prompted.) Figure –...
SmartCom Control Installation and User Manual Auto mode: Heating and ventilation operate automatically depending on the room temperature, time/set temperature program and the control method AUTO selected. Ventilation is disabled during off periods of the time program. Frost Only mode: Heating operates automatically depending on the room temperature and control method selected.
Page 14
SmartCom Control Installation and User Manual Press the SETTINGS button SETPROGRAM repeatedly until the set program SETTINGS display appears. The icons [SET], [PROGRAM] and [OK?] will be displayed with the [PROGRAM] icon fl ashing. Figure - Set Program (Enter your PIN code if prompted.) Press the OK button to accept the Set Program function.
SmartCom Control Installation and User Manual 3.6 Setting the Day & Night Temperatures Press the SETTINGS button repeatedly until the icons [SET], [TEMP] and [OK?] are displayed with the [TEMP] icon fl ashing (enter your PIN code if SETTINGS prompted). Press the OK button to accept the Set Temperatures function.
SmartCom Control Installation and User Manual ● If you forget the PIN code there is a master PIN code that is factory set by the manufacturer. This master PIN code over-rides the unique PIN code and will enable you to change the PIN code again. Please call the manufacturer for this master PIN code.
SmartCom Control Installation and User Manual 3.8.2 Operating the master controller ● Pressing the CHECK TEMP button on the master controller will display the sensor temperature and set temperature for the master zone (Zone 1) as well as the slave zones (Zone 2, 3, etc.) The fi rst and second press of the CHECK TEMP button will display the sensor temperature and set temperature for Zone 1.
SmartCom Control Installation and User Manual 3.11 Setting a temporary overtime extension period Pressing the OVERTIME button will initiate or extend the day-time operation of the controller. Overtime is activated as follows: ● Press the OVERTIME button. The [OVERTIME] icon will be displayed. The hours and minutes digits will fl...
SmartCom Control Installation and User Manual 3.13 Error Message:- Lockout When the controller detects a fl ame failure signal, the display will clear and show only the [LOCKOUT] icon. The lockout state continues even when the fl ame failure signal clears. In order to reset the lockout state, press the LOCKOUT button.
SmartCom Control Installation and User Manual 4 ENGINEER FUNCTIONS ● The engineer functions allow you to program various advanced parameters. ● Depending on the version of the controller (i.e. Lite, Standard, Advanced or Network), some options may not be available although displayed. ●...
SmartCom Control Installation and User Manual 4.2 Programming The Engineer Functions All engineer functions are displayed as a code in the fi rst two digits of the display, e.g. C1, t1, t2, and a variable in the second two digits. Figure - Engineer variable Press the SETTINGS button until the desired variable code is displayed.
Page 22
SmartCom Control Installation and User Manual Radiant / NorRayVac / Herringbone fan Temperature measurement method. delay time (in 10 second steps). Space temperature from F1: Range: 00 to 24 internal sensor only. Default value = 03 (30 secs) Space temperature from remote sensor only.
SmartCom Control Installation and User Manual Heating hours saved since the last PIN protection activation. service reset. (Savings hours are the 0 PIN protection off times when the heating is on, but the 1 PIN protection on Heat Stage 1 relay is not on.) Default value = 0 H3: Range: 0 to 9999 Settings menu PIN number.
Page 24