Specification The HRX 5000 is a Proximity card reading terminal with TCP/IP connection, Fire Alarm printout, Access Control for 2 doors and optional internal Modem. HRX5000 Technical Manual V1.2 Page 2 of 18...
Page 4
Dimensions: 280mm (W) X 170mm (H) X 60mm (D) Display: 16 X 2 Large character LCD with LED Backlight Display area: 100mm X 25mm Clockings: 15,000 in circular buffer Employees: 25 to 1,000, remotely upgradeable Firmware: Flash memory upgradeable over TCP/IP Configuration: 1 Master, up to 15 Slaves Reader:...
Page 5
Connections: Power 9-12v DC 350mA to 500mA TCP/IP 10/100 Base-T RS/232 Second, alternative, PC connection RS485 Slave clocks. 2 connectors for buss RS232 Fire Alarm printer Digital IN Fire Alarm Panel Remote Reader A 8 core up to 50 metres Relay A SPCO up to 250V 0.5A Door Ajar A...
Connectors RS-485 Network Connectors (J6 and J7) Pin Signal Direction J6, J7 In/Out In/Out Screen A Master HRX5000 is able to communicate with up to 15 Slave HRX5000s (or HRX3000s) over a twisted pair RS-485 bus. 2 connectors are fitted in each clock to make wiring easier in the field.
RS-232 to Printer (J19) Pin Signal Direction Printer DB-25 Notes Power 5-9 volts available to power an external line driver. Current limited to approx 50mA RXD pin 3 Transmit data. 9600 baud, 8 data, 1 stop, no parity RTS pin 20 Hardware handshake from printer.
RS-232 to PC (J8) Pin Signal Direction Notes Power 5-9 volts available to power an external line driver. Current limited to approx 50mA Transmit data. 19,200 baud, 8 data, 1 stop, no parity Receive data. 19,200 baud, 8 data, 1 stop, no parity Signal Ground The terminal can communicate with the PC either by TCP/IP, RS-232 or Modem.
TCP/IP TCP/IP The TCP/IP connection supports Ethernet 10/100 Base-T. The IP address of the unit is set up via the Focus software using the System | Clock Utilities | TCP/IP Tab. A password is required to modify the TCP/IP address of the unit as inadvertent changes will cause loss of communication. You would normally modify the IP Address by communicating over the RS232 cable from the PC.
Power (J21) Pin Signal Direction Notes Signal Ground connected to pin 2 9-12 volts DC at up to 500mA Connected to Pin 3 The unit requires 9 to 12 volts DC at up to 500mA depending on configuration. The unit is protected internally against reverse polarity connection. HRX5000 Technical Manual V1.2 Page 9 of 18...
Fire Alarm Input (J20) Pin Signal Direction Notes Fire Alarm Input Signal Ground Connected internally to Pin 1 Connected internally to Pin 2 The Fire Alarm Input triggers the Fire Evacuation Report to be printed via the RS-232 printer port. A voltage free pair of contacts triggers the report on contact closure.
Relays (J12, J15) J12, J15 Pin Signal Direction Notes In/Out Normally Closed Contact In/Out Common Contact In/Out Normally Open Contact The two relays each provide one set of changeover contacts for operating a door release mechanism or a sounder. The contacts are rated at up to 240 volts AC 100mA , or 12V DC 2 Amps. The contacts are protected internally by transient suppressing Varistors.
Remote Readers (J13, J16) J13, J16 Signal Colour Direction Required 9 Volts Card Load Signal Violet Signal Ground Black Data Green Clock White Green LED Orange Red LED Brown Sounder Yellow NB: Pin 1 located at the TOP of the connector Recommended cable for extending the reader distance: Belden 9538 which is 8 core 24 awg (7X32) with overall screen.
Remote Door Inputs (J14, J17) J14, J17 Pin Signal Direction Notes AJAR Door Ajar EXIT Exit Pushbutton Pin 1 and 2 connect to a normally closed door sensor such as a magnetic reed contact. The contacts open when the door opens. With the contacts open there is a 5 volt signal present on Pin 1.
Modem (J3) Modem The unit can accept a plug in Modem which sits underneath the LCD. The footprint is compatible with a PSTN landline modem or a GSM radio modem. The PSTN Modem connects to the phone line via J3 which is a standard modem line socket.
Access Control The HRX5000 supports Access Control for 2 Doors. Two independent groups of connectors allow for connection to: 1. Proximity reader; 2. Door release device (latch or magnet) driven by a built in changeover relay; 3. Door open sensor; 4.
Master/Slave systems In a Master/Slave configuration, the master holds all the Door Rules and the Access Rules as well as the Access Clocking Records. The Access Clocking records are downloaded at the same time as the Time and Attendance Records. The Master holds: 20 Door Rules 100 Access Rules...
Page 18
Recommended Printer: OKI B4250 Mono Laser plus optional serial RS-232 interface. Source www.printerland.co.uk. If the printer does not have a serial interface it is possible, though less convenient, to use an external Serial-to-Parallel converter. This must be capable of converting serial data in the format 9600 Baud, 8 data bits , 1 Stop bit to Parallel data.
Issue History Issue Date Firmware Focus Changes V1.0 July 2006 Original Issue V1.1 11/9/2006 2.002 2.07 Access Control and Bells Descriptions Added V1.2 29/9/2006 Fire Alarm printer details added. HRX5000 Technical Manual V1.2 Page 18 of 18...