Fault input 1...2
Note
Siemens
Building Technologies
Path: Home > 0.5 OZS164... > Settings > Inputs > Fault input 1...2
Digital inputs D1, D2 help connect potential-free status contacts. They work as fault
inputs.
The following settings show how to configure fault inputs.
Select "Settings > Faults > Local > Fault input 1...2" to define behavior during
faults.
Data point
F ault input 1...2*
Default val.:
(Blank)
Setting val:
Max. 20 characters
N ormal position
Default val.:
Open
Setting val:
Open,
Closed
T ext for: Logic 0*
Default val.:
0
Setting val:
Max. 20 characters
T ext for: Logic 1*
Default val.:
1
Setting val:
Max. 20 characters
* Notes:
• Note Section 2.4, Section "Update device web pages".
• Delete the entry to reset to default text.
Web server
Commissioning
Explanation, example
Customizable text for fault input. The
designation is displayed in the menu and
transmitted as part of the message.
Identical to data point in "Settings > Faults >
L
ocal > Fault input 1...2".
Normal position specifies the contact position
deemed "No fault".
Logic 0: No fault.
Customizable text for fault input status, e.g.
W
ater press normal.
Logic 1: Fault.
Customizable text for fault input status, e.g.
W
ater press too low.