1Feature Four-way cassette type air conditioner (Cooling-only or heat pump), is installed under the ceiling, compared with Floor &Standing type A/C, it has following advantages: saving room space; Ceiling installation combining with the decoration, makes the room more elegant; Flexible installation in anywhere in the ceiling and 4-direction blowing, makes the indoor temperature is even and makes you feel more comfortable, so Cassette type A/C is a perfect replacing Product of Floor &...
Page 8
Liquid Side 6.35 6.35 6.35 Gas Side 12.7 12.7 12.7 Max. Refrigerant Refrigerant Pipe Pipe Length Max. Difference In Level ℃ Operation Temperature Range 16~32 16~32 16~32 Ambient Temperature ℃ -5~49 -5~49/-15~24 -5~49 Range(Cooling/Heating) Application Area 13-21 13-21 21-35 Power 3×1.5mm 3×1.5mm 3×2.5mm...
Page 9
Number Of Row Tube Pitch(a)x Row 20.5×12.7 20.5×12.7 20.5×12.7 Pitch(b) Fin Pitch Fin Material Hydrophilic aluminum fin Indoor Coil Tube Outside φ7,Inner grooved φ7,Inner grooved φ7,Inner grooved Dia.and Material Coil Length x Height 1160×164×25.4 2142×205×25.4 2142×205×25.4 x Width Heat Exchanging 5.76 10.02 10.02...
Page 10
Panel MB12 MB12 MB12 IOU-36CR-SA6-N1 IOU-36HR-SA6-N1 IOU-48CR-SA6-N1 Outdoor V~,Hz, Power Supply 380~415,50,3 380~415,50,3 380~415,50,3 Btu/h 36000 36000 48000 Cooling 10.6 10.6 14.0 Capacity Btu/h 40000 Heating 11.7 Rated Cooling 3.77 3.77 4.87 Power Input Rated Heating 3.50 Power Input Electric Data Rated Cooling 7.22 7.22...
Page 11
℃ Operation Temperature Range 16~32 16~32 16~32 Ambient Temperature ℃ -5~45 -5~45/-15~24 -5~45 Range(Cooling/Heating) Application Area 42-70 42-70 56-93 Power 3×1mm 3×1mm 3×1mm Wiring( Indoor) Connection Power 5×2.5mm 5×2.5mm 5×2.5mm Wiring Wiring( Outdoor) Signal Wiring 2×1mm 2×1mm 2×1mm Wireless Remote Controller YKR-H/009E YKR-H/009E YKR-H/009E...
Page 12
Dia.and Material Coil Length x Height 2142×246×25.4 2142×246×25.4 2142×246×25.4 x Width Heat Exchanging 15.60 15.60 15.60 Area Indoor Air Flow 1800/1440/1260 1800/1440/1260 1800/1440/1260 (Hi/Mi/Lo) Noise dB(A) 50/47/41 50/47/41 50/47/41 Level(Hi/Mi/Lo) Net Dimension 835×835×280 835×835×280 835×835×280 Indoor Unit (W*H*D) Packing 910×910×360 910×910×360 910×910×360 Dimension (W*H*D)
3.Capacity Amendment 3.1 Running range Cooling capacity (Btu/h) 12000 18000 24000 36000 48000 60000 Power supply 220-240V~/50Hz 380-415V 3N~/50Hz Voltage 187~242V 320~420V Cooling -5~49℃ -5~45℃ Ambient temperature Heating -15~24℃ Amendment coefficient of cooling capacity under different indoor/outdoor DB/WB temperature Indoor air inlet Outdoor air inlet DB temperature℃...
Page 14
Amendment coefficients of heating and cooling capacity under different height drop Different Cooling Capacity modified coefficients at different height: Equivalent pipe length EL (m) Note: H = Height of Outdoor Unit - Height of Indoor Unit Different Heating Capacity modified coefficients at different height: Equivalent pipe length EL(m) Note: H = Height of Outdoor Unit -...
Page 19
5. Electrical connection K12 (heating - cooling) indoor unit outdoor unit Multicore signal Wired controller Power cable Control wire Control wire Signal wire K12 (cooling) indoor unit outdoor unit Multicore signal wire Wired controller Power cable Control wire Control wire Signal wire...
Page 20
K18 (heating - cooling) indoor unit outdoor unit Multicore signal Wired controller Power cable Control wire Control wire Signal wire K18 (cooling) Indoor unit Outdoor unit Multicore signal wire Wired controller Power cable Control wire Control wire Signal wire...
Page 21
K24 (heating - cooling) Indoor unit Outdoor unit Multicore signal wire Wired controller Power cable Control wire Control wire Signal wire K24 (cooling) Indoor unit Outdoor unit Multicore signal wire Wired controller Power cable Control wire Control wire Signal wire K36, K48, K60 (heating - cooling &...
Page 22
Introduction of Control Board sockets QRDL-3F(2S)-SYE1 (indoor unit) (match with the outdoor unit which the Power supply is 220V-240V, 1PH) Compressor Electric Outdoor Drainage heating output 4-way pump Neutra Indoor fan output output valve output output l insert Neutral High 4-DIP switch Float switch Transformer...
6 Installation 6.1 Preparation before installation Please buy following spare parts from your local market Besides general implements, other implements are needed before installation when connecting the pipe Acetylene cylinders, oxygen cylinders (when longer pipe Hung bolts M12, 4 pcs used it should be welded) Drainage pipe PVC One set pipe cut machine.
Page 24
◇ The unit should not be installed in the heat source, steam source oil mist places (such as machine room, kitchen, laundry room, mechanical workshop, etc.) in order to avoid performance degradation, electric shock, plastic parts corrosion which lead to unit broken; ◇...
Page 25
◇ If this unit is installed on a sloping ceiling, a cushion block should be installed between the ceiling and the air outlet panel, in order to ensure that the unit is installed on a level surface. This is as shown in the drawing as follows: ◇...
Page 26
downs, it will cause water backflow or leakage etc. More than 1:100 ◇ The unit has a drain pump which will lift up to 1200mm. However after the pump stops the water still in the pipe will drain back and may overflow the drain tray causing a water leak. For this reason please install the drain pipe as shown Less than 300mm Less than 600mm...
Page 27
6.8 Connect duct, fresh air ventilation In order to meet different customers’ requirements and their different usage environment, 3hp and 5hp indoor unit reserves one fresh air ventilation hole and four duct connection holes. The fresh air can be introduced from outside or through duct. ◇...
Idea LCAC R-410 On-Off 1.Feature Ceiling& Foor type A/C (Cooling-only or Heat pump) can be installed under the ceiling and also on the floor. Compared with normal Floor &Standing type A/C, it can be hoisted under the ceiling,saving room space, it is also the updating Product for Floor & Standing type A/C.
2.Specfication Indoor Model Outdoor IUB-18CR-SA6-N1 IUB-12CR-SA6-N1 IUB-12HR-SA6-N1 Indor IOU-18CR-SA6-N1 Outdoor IOU-12CR-SA6-N1 IOU-12HR-SA6-N1 V~,Hz,P Power Supply 220~240,50,1 220~240,50,1 220~240,50,1 Btu/h 12000 12000 18000 Cooling Capacity Btu/h 13500 Heating Rated Cooling Power Input 1.13 1.13 1.72 Rated Heating Power Input 1.15 Electric Data Rated Cooling Current 5.17 5.17...
Page 37
Max. Difference In Level ℃ Operation Temperature Range 16~32 16~32 16~32 ℃ Ambient Temperature Range(Cooling/Heating) -5~49 -5~49/-15~24 -5~49 Application Area 13-21 13-21 21-35 Power Wiring( Indoor) 3×1.5mm 3×1.5mm 3×2.5mm Connection Power Wiring( Outdoor) Wiring 3×1.5mm +2×1mm Signal Wiring 3×1.5mm +1mm 3×2.5mm +1mm Wireless Remote Controller...
Page 38
Fin Spacing Fin Material Hydrophilic aluminum fin Tube Outside Dia.and φ7,Inner grooved φ7,Inner grooved φ7,Inner grooved Material Coil Length x Height x Width 570×246×38.1 950×246×38.1 950×246×38.1 Heat Exchanging Area 6.00 10.00 10.00 Indoor Air Flow (Hi/Mi/Lo) 850/680/595 1200/960/840 1200/960/840 Noise Level(Hi/Mi/Lo) dB(A) 43/40/34 46/43/38...
Page 39
10.6 10.6 14.0 Btu/h 40000 Heating 11.7 Rated Cooling Power Input 3.77 3.77 4.87 Electric Rated Heating Power Input 3.50 Data Rated Cooling Current 7.22 7.22 9.32 Rated Heating Current 6.69 2.81 2.81 2.87 Performan 3.34 Model YSK-70W-4 YSK-70W-4 YSK-105W-4 Brand HUATE HUATE...
Page 40
Signal Wiring 2×1mm 2×1mm 2×1mm Wireless Remote Controller YKR-H/009E YKR-H/009E YKR-H/009E Qty’per 20’& 40’&40HQ(Only For Reference) 32/67/92 32/67/92 20/41/43 Note: 1. Working condition of the cooling capacity measured: Inside the room DB temperature 27℃,WB temperature19℃;Outside of the room DB temperature 35℃,WB temperature 24℃;Working condition of the heating capacity measured:Inside the room DB temperature 20℃,Outside of the room DB temperature 7℃,WB temperature 6℃。...
Page 41
Width Heat Exchanging Area 13.69 19.93 19.93 Indoor Air Flow (Hi/Mi/Lo) 1800/1440/1260 1800/1440/1260 1800/1440/1260 Noise Level(Hi/Mi/Lo) dB(A) 51/48/42 51/48/42 51/48/42 Net Dimension (W*H*D) 1631×660×205 1631×660×205 1631×660×205 Indoor Unit Packing Dimension 1710×720×280 1710×720×280 1710×720×280 (W*H*D) Net Weight Gross Weight Liquid Side 9.52 9.52 9.52...
3 Capacity amendment 3.1 Running range Cooling capacity (Btu/h) 12000 18000 24000 36000 48000 60000 Power supply 220-240V~/50Hz 380-415V 3N~/50Hz Voltage 187~242V 320~420V Cooling -5~49℃ -5~45℃ Ambient temperature Heating -15~24℃ 3.2 Amendment coefficient of cooling capacity under different indoor/outdoor DB/WB temperature Indoor air inlet Outdoor air inlet DB temperature℃...
Page 43
3.4 Amendment coefficients of heating and cooling capacity under different height drop Different Cooling Capacity modified coefficients at different height: Equivalent pipe length EL (m) Note: H = Height of Outdoor Unit - Height of Indoor Unit 3.5 Different Heating Capacity modified coefficients at different height: Equivalent pipe length EL (m) Note: H = Height of Outdoor Unit -...
Page 48
5. Electrical connection K12 (heating - cooling) Indoor unit Outdoor unit Multicore signal wire Wired controller Power cable Control wire Control wire Signal wire K12 (cooling) Indoor unit Outdoor unit Multicore signal wire Wired controller Power cable Control wire Control wire Signal wire...
Page 49
K18 (heating - cooling) Indoor unit Outdoor unit Multicore signal wire Wired controller Power cable Control wire Control wire Signal wire K18 (cooling) Indoor unit Outdoor unit Multicore signal wire Wired controller Power cable Control wire Control wire Signal wire...
Page 50
K24 (heating - cooling) Indoor unit Outdoor unit Multicore signal wire Wired controller Power cable Control wire Control wire Signal wire K24 (cooling) Indoor unit Outdoor unit Multicore signal wire Wired controller Power cable Control wire Control wire Signal wire...
Page 52
Introduction of Control Board sockets QRDL-3F(2S)-SYE1 (indoor unit) (match with the outdoor unit which the Power supply is 220V-240V, 1PH) Electric Compressor Neutra Outdoor Drainage output heating 4-way l insert pump Indoor fan output output valve output output Neutral High 4-DIP switch Float switch Transformer...
6. Installation 6.1 Preparation and equipments before installation Please buy following spare parts from your local market Besides general implements, other implements are needed before installation when connecting the pipe Acetylene cylinders, oxygen cylinders (when longer pipe used Hung bolts M12, 4 pcs it should be welded) Drainage pipe PVC One set pipe cut machine.
Page 54
water leakage, air leakage etc. will be resulted; ◇ Tighten the nuts and ensure that the hooks are tightly connected to the nuts and sMDms , and there is no phenomenon of virtual hanging; ◇ After the unit is installed ensure it is secure and does not shake or sway. 6.4 Drainage pipe installation ◇...
Page 59
IOU-12HR-SA6-N1 Model IOU-18CR-SA6-N1 IOU-12CR-SA6-N1 V~,Hz, Power Supply 220~240,50,1 220~240,50,1 220~240,50,1 Max. Input Consumption 1750 1750 2650 Max. Current 12.0 Btu/h 12000 12000 18000 Cooling Capacity Btu/h 13500 Heating PA215X2CS-4KU Model PA150X2C-4FT PA150X2C-4FT Type ROTARY ROTARY ROTARY Brand TOSHIBA TOSHIBA TOSHIBA Capacity 3670 3670...
Page 60
Packing 880×350×610 880×350×610 930×410×660 Weight Gross Refrigerant Type R410A R410A R410A Type/Quantity Charged Volume 1160 1160 1360 Design Pressure 4.15 4.15 4.15 Liquid Side 6.35 6.35 6.35 Gas Side 12.7 12.7 12.7 Refrigerant Piping Max. Length Max. Height Operation Temperature Range ℃...
Page 61
Thermal Protection temp. UP3SE0391-T39 UP14SE5145 UP14SE5145 Capacitor Refrigerant Oil Model YDK65-6B YDK68-6A YDK68-6A code R60020207200 R60020209700 R60020209700 Brand OutdoorFan Output Power x Fan Motor 65*1 68*1 68*1 quantity Capacitor Speed r/min Number Of Row Tube Pitch(a)x Row 22×19.05 22×19.05 22×19.05 Pitch(b) Fin Pitch Fin Material...
Page 62
1. Nominal cooling capacities are based on the following conditions: Return air temp.: 27℃DB, 19℃WB, and outdoor temp.: 35℃DB, 24℃℃WB; 2. Nominal heating capacities are based on the following conditions: Return air temp.: 20℃DB, and outdoor temp.: 7℃DB, 6℃℃WB; 3. Parameters above are all measured when the connecting pipe is 5 meters. Model Factory Model IOU-36CR-SA6-N1...
Page 63
Packing 1030×410×980 1030×410×980 1090×430×1370 Weight Gross Type R410A R410A R410A Refrigerant Type/Quantity Charged Volume 2400 2400 2850 Design Pressure 4.15 4.15 4.15 Liquid Side 9.52 9.52 9.52 Gas Side 15.88 15.88 19.05 Refrigerant Piping Max. Length Max. Height ℃ Operation Temperature Range 16~32 16~32 16~32...
Page 64
Thermal Protection temp. 160±5℃ 160±5℃ 160±5℃ Capacitor Refrigerant Oil 1300 1300 1300 Model YDK68-6-359 YDK68-6-359 YDK68-6-359 code R60020200600 R60020200600 R60020200600 Brand WEITELI WEITELI WEITELI OutdoorFan Motor Output Power x Fan quantity 68*2 68*2 68*2 Capacitor Speed r/min Number Of Row Tube Pitch(a)x Row Pitch(b) 20.5×12.7 20.5×12.7...
Page 65
2 Capacity Amendment 2.1 Running range Cooling capacity (Btu/h) 12000 18000 24000 36000 48000 60000 Power supply 220-240V~/50Hz 380-415V 3N~/50Hz Voltage 187~242V 320~420V Cooling -5~45℃ A mbien temperature Heating -15~24℃ 2.2 Amendment coefficient of cooling capacity under different indoor/outdoor DB and WB temperature Indoor air inlet Outdoor air inlet DB temperature℃...
Page 66
Actual heating capacity calculation: Actual heating capacity=amendment coefficient of heating capacity × nominal heating capacity ——nominal heating capacity could be found from the performance parameters list ——amendment coefficient of heating capacity could be found from table above. 2.4 Amendment coefficients of heating and cooling capacity under different height drop Different Cooling Capacity modified coefficients at different height: Equivalent pipe length EL (m) Note: H = Height of Outdoor Unit -...
Page 70
4.System principle diagram Cooling circle: the Compressor inhales the low-temperature and low-pressure refrigerant vapor from the evaporator, and vapor be turned into high-temperature and high-pressure gas then enters into condenser, the high-temperature and high-pressure refrigerant gas and outdoor air make heat exchange in the condenser, the compressed vapor is then cooled by heat exchange with the outside air, so that the vapor condenses to be a high-temperature and high-pressure fluid, and then through capillary throttling to cooled, low pressure, then the liquid enters into the evaporator and two-phase of gas and liquid refrigerant...
Page 71
K36, K48, K60 (heating - cooling) Condenser Stopping Valve (gas) Evaporator T(Mild-Condenser) 4 Way Valve Low pressure switch High pressure indoor unit Fan switch T(Discharge) Comp. T(Evaporator) Liquid-vapor separator: T(Condenser) Capillary (Heating) Capillary (Cooling) One Way Valve (liquid) Stopping Valve Refrigerant flow direction in Cooling Refrigerant flow direction in Heating...
Page 84
7. Installation 7.1 Preparation and equipments before installation Please buy following spare parts from your local market Besides general implements, other implements are needed before installation when connecting the pipe Acetylene cylinders, oxygen cylinders (when longer pipe Hung bolts M12, 4 pcs used it should be welded) Drainage pipe PVC One set pipe cut machine.
Page 85
The suitable length for bolt shall 20mm over the base level, in order to minimize vibration please do set a rubber shock absorber. ◇If the outdoor unit is mounted on the wall or on the rooftop, in order to prevent earthquake and strong wind please fasten it as tightly as possible.
Page 86
tighten the nut then using a wrench to tighten the nut again, the tighten torque as follows figure. ◇Take out the cover of the indoor unit gas valve and liquid valve, make the expanding right to the stop valve of outdoor unit, using hands to tighten the nut then using a wrench to tighten the nut again, the tighten torque as follows figure.
Page 87
pipe according to the pipe length parameter in this manual. Emptying or vacuum Before charging the refrigerant to the system, to ensure that there is no impurities, water or non-condensable gas. So, emptying and vacuum operation should be carried out. ◇Vacuum: when process this operation please be sure that the connection pipe is tightened up.
Page 88
Heat insulation package of piping ◇ Use heat insulation material with good insulation performanCF to wrap the pipe. Notes Drainage pipe and connection piping should be wrapped by heat insulation material respectively or there will be dew or leakage During the high temperature working environment, our air conditioner is proved my dew conditioner experiment.
Page 89
Additional refrigerant charge When pipe length exceeds 5m, please add refrigerant according to the table below: Connection Piping size) Additional refrigerant piping Gas pipe Liquid pipe charge amount (kg/m) φ9.52×0.75mm φ6.35×0.75mm 0.02 Piping φ12.7×1mm φ6.35×0.75mm 0.02 between φ15.88×1mm φ9.52×0.75mm 0.05 indoor and φ19.05×1mm φ9.52×0.75mm...
Page 90
the gas (large) pipe; When the vertical pipe height difference is more than 5 meters, then for every 5 meters an oil loop must be installed at the bottom of the gas (large) pipe, and a short loop (liquid ring) should be installed at the exit of the indoor unit liquid (small) pipe;...
Page 91
The earth line is neither allowed to connect to gas pipe, water pipe or circuitry of telephone or lighting rod, Notice nor to the earth line of other devices. Please fix power supply cord and connection wires of indoor and outdoor, in accordance with circuit diagram Fix the cords into terminal boards properly and safely with cable fixation tools to avoid any danger caused Others...
Page 92
7.5. Compressor freezing oil brand and standard oil charge Outdoor model Brand Compressor Model Compressor Lubricating Oil Model Oil charge (cm TOSHIBA PA150X2C-4FT ESTER OIL VG74 TOSHIBA PA215X2CS-4KU1 ESTER OIL VG74 TOSHIBA PA290X3CS-4MUI ESTER OIL VG74 HITACHI E404DH-38D2G FVC68D 1200 HITACHI E504DH-49D2G FVC68D...
1. Main components of air conditioner Appellation Figuration and inner configuration Instruction Rotary compressor function compressor: after refrigerant evaporate evaporator, compress the low temp and low pressure refrigerant gas, make the gas become high temp and high pressure gas, and then send the gas to condenser, make the refrigerant cycle, in this series products, all the compressors are complete hermetic...
Page 95
Elec.box Motor Function of evaporator: Evaporator Make the low pressure refrigerant liquid (heat from capillary or expansion valve happen exchanger) heat exchange with air Evap. Tray Elec. heater Function of capillary: Capillary Utilize aperture and length change bring (throttle pressure gap., control refrigerant flow components) quantity and pressure One way valve is used for heat pump...
Page 96
Function: Stop valve To stop or release refrigerant, only on/off, can’t adjust or throttle Function: Muffler Eliminate the system noise Function: Gas and liquid Separate liquid and gas refrigerant, separator to protect the compressor...
2.Electrical system main components Appellation Figuration and inner configuration Instruction Function: Via program to control the relay, make every components on/off according to temperature and pressure variety, so to realize automatic control Function: Fan motor Drive the fan, make the indoor and outdoor unit have heat exchange with air.
Page 98
Heat relay is normally made up of double metal sheet, when the Current setting Release link current is too large, the double button metal sheet will heat distortion and movement, and open the protection contactor ,which causes control Heat relay circuit disconnect and then the main circuit will be cut off, after it cooling, control circuit will restore...
3. Poor efficiency explanation During the process of using air conditioner, some phenomenon seems to be malfunction but actually not. Thus when cooling effect does not to your expectation, the following factors have to be achieve ruled out Phenomenon Causing explanation When the outdoor temperature is higher, more heat penetrates into High outside temperature and too many indoor space, which increases the cooling load of AC.
4.Failure phenomenon Phenomenon Causing explanation Mirage comes out from indoor When the cold air from AC cools the indoor air unit 1. When air conditioner stops running, there will be some noise, and this is because the refrigerant flows contrarily. Noise 2.
5.Electric components malfunction inspection Component Inspection methods name Using multi-meter ohm phase, there is correct resistance value among windings (single Compressor phase compressor refers to specification, three phase compressor resistance approximately equal), resistance of winding should be infinite. 1. 1Check if any connection part of PCB loosen or drop off, printed tinsel and components have any burn, fade, breaking off or aging phenomenon, all joints exist short circuit phenomenon etc.
6. Failure code display When air condition has failure, the timing lamp on light board of controller will display different code according to different failure case. 6.1 1Unit failure code for unit power supply is 220-240V Display mode 1 Display mode 2 Display Failure causing (indication lamp on display...
Page 103
Indoor temp. sensor Flash 1 times and go out - shutdown abnormal(TA) Indoor coil sensor Flash 3 times and go out - shutdown abnormal(TE) Outdoor coil sensor Flash 2 times and go out Flash 2 times non-stop abnormal(TW) and go out 2S Outdoor condensate temp.
Page 123
Remote receving:Receving signal of remote controller. Notes:Virtually all functions of the wired controller are the same as those of the remote controller and you should refer to the remote controller instructions. Wired controller: XK-02 ON/OFF button Switch the unit ON/OFF. Mode button: Select mode , push the button one time, then the operation modes will change in turn as below: Auto-Cooling-Dehumidify-Heating Temp +/- button: Press the button can adjust temperature.
Page 124
after 1 hour and another 1℃ auto matically after 1hour. 3. After the setting of sleeping mode,the heating operation enables the set temperature to drop 2℃ after 1 hour and another 2℃ auto matically after 1hour. 4. The air condition runs in sleeping mode for 7hours and stops automatically. Remark:Press the mode or ON/OFF button,the remote controller clears sleeping mode away.
Page 125
Part 6. Sensor resistance table Coil and environment temperature sensor 5K3470 resistance reference table Coil and environment temperature sensor 5K3470 Average (KΩ) Average (KΩ) Average (KΩ) Tx(℃) Tx(℃) Tx(℃) 72.99 5.854 1.421 35.16 5.626 1.376 33.43 5.408 1.334 31.80 5.199 1.293 30.26 5.000...
Page 126
6.877 1.563 0.489 6.603 1.724 0.476 6.342 1.466 0.464 6.092 Exhaust temperature sensor 6.339K3954 Exhaust temperature sensor R80:6.339KΩ±1% B25/80=3954K±1% Rmin [KΩ] Rmin [KΩ] Rmin [KΩ] Rmin [KΩ] T [℃] T [℃] T [℃] T [℃] 440.7 60.42 12.32 3.377 417.0 57.79 11.89 3.279...