Do you have a question about the ICC(ICA)-**HR-SA6-NI and is the answer not in the manual?

Questions and answers

Summary of Contents for Idea ICC(ICA)-**HR-SA6-NI

  • Page 1 Idea LCAC R-410 On-Off IDEA Indor unit: ICC(ICA)-**HR-SA6-N1 IUB-**HR-SA6-N1 Outdor unit: IOU-**HR-SA6-N1 2016 г.
  • Page 2 Idea LCAC R-410 On-Off Unit appearance Series Picture of the indoor unit Four-way Cassette 12k Btu/h 18k Btu/h 24k Btu/h 36k Btu/h 48k Btu/h 60k Btu/h Ceiling &Floor 12k Btu/h 18k Btu/h 24k Btu/h 36k Btu/h 48k Btu/h 60k Btu/h...
  • Page 3 Part 1 Indoor unit...
  • Page 4: Table Of Contents

    Four-way cassette 1.Feature ..........................8 2.Specfication ........................10 3.Capacity Amendment .....................16 4.Demension ........................18 5.Electrical wiring and connection ...................19 6.Installation ........................26 7.Explode view ........................31...
  • Page 5: Feature

    1Feature Four-way cassette type air conditioner (Cooling-only or heat pump), is installed under the ceiling, compared with Floor &Standing type A/C, it has following advantages: saving room space; Ceiling installation combining with the decoration, makes the room more elegant; Flexible installation in anywhere in the ceiling and 4-direction blowing, makes the indoor temperature is even and makes you feel more comfortable, so Cassette type A/C is a perfect replacing Product of Floor &...
  • Page 6 Function introduction Model Type Item 12/4 18/4 24/4 36/5 48/5 60/5 - - - High pressure protection ● ● ● - - - ● ● ● Low pressure protection ● ● ● ● ● ● Compressor overloading protection - - -...
  • Page 7: Specfication

    2. Specfication Indoor Model Panel Outdoor ICA-12CR-SA6-N1 ICA-12HR-SA6-N1 ICA-18CR-SA6-N1 Indoor Factory Model Panel MB13 MB13 MB13 IOU-12CR-SA6-N1 IOU-12HR-SA6-N1 IOU-18CR-SA6-N1 Outdoor V~,Hz, Power Supply 220~240,50,1 220~240,50,1 220~240,50,1 Btu/h 12000 12000 18000 Cooling Capacity Btu/h 13500 Heating Rated Cooling 1.19 1.19 1.76 Power Input Rated Heating 1.20...
  • Page 8 Liquid Side 6.35 6.35 6.35 Gas Side 12.7 12.7 12.7 Max. Refrigerant Refrigerant Pipe Pipe Length Max. Difference In Level ℃ Operation Temperature Range 16~32 16~32 16~32 Ambient Temperature ℃ -5~49 -5~49/-15~24 -5~49 Range(Cooling/Heating) Application Area 13-21 13-21 21-35 Power 3×1.5mm 3×1.5mm 3×2.5mm...
  • Page 9 Number Of Row Tube Pitch(a)x Row 20.5×12.7 20.5×12.7 20.5×12.7 Pitch(b) Fin Pitch Fin Material Hydrophilic aluminum fin Indoor Coil Tube Outside φ7,Inner grooved φ7,Inner grooved φ7,Inner grooved Dia.and Material Coil Length x Height 1160×164×25.4 2142×205×25.4 2142×205×25.4 x Width Heat Exchanging 5.76 10.02 10.02...
  • Page 10 Panel MB12 MB12 MB12 IOU-36CR-SA6-N1 IOU-36HR-SA6-N1 IOU-48CR-SA6-N1 Outdoor V~,Hz, Power Supply 380~415,50,3 380~415,50,3 380~415,50,3 Btu/h 36000 36000 48000 Cooling 10.6 10.6 14.0 Capacity Btu/h 40000 Heating 11.7 Rated Cooling 3.77 3.77 4.87 Power Input Rated Heating 3.50 Power Input Electric Data Rated Cooling 7.22 7.22...
  • Page 11 ℃ Operation Temperature Range 16~32 16~32 16~32 Ambient Temperature ℃ -5~45 -5~45/-15~24 -5~45 Range(Cooling/Heating) Application Area 42-70 42-70 56-93 Power 3×1mm 3×1mm 3×1mm Wiring( Indoor) Connection Power 5×2.5mm 5×2.5mm 5×2.5mm Wiring Wiring( Outdoor) Signal Wiring 2×1mm 2×1mm 2×1mm Wireless Remote Controller YKR-H/009E YKR-H/009E YKR-H/009E...
  • Page 12 Dia.and Material Coil Length x Height 2142×246×25.4 2142×246×25.4 2142×246×25.4 x Width Heat Exchanging 15.60 15.60 15.60 Area Indoor Air Flow 1800/1440/1260 1800/1440/1260 1800/1440/1260 (Hi/Mi/Lo) Noise dB(A) 50/47/41 50/47/41 50/47/41 Level(Hi/Mi/Lo) Net Dimension 835×835×280 835×835×280 835×835×280 Indoor Unit (W*H*D) Packing 910×910×360 910×910×360 910×910×360 Dimension (W*H*D)
  • Page 13: Capacity Amendment

    3.Capacity Amendment 3.1 Running range Cooling capacity (Btu/h) 12000 18000 24000 36000 48000 60000 Power supply 220-240V~/50Hz 380-415V 3N~/50Hz Voltage 187~242V 320~420V Cooling -5~49℃ -5~45℃ Ambient temperature Heating -15~24℃ Amendment coefficient of cooling capacity under different indoor/outdoor DB/WB temperature Indoor air inlet Outdoor air inlet DB temperature℃...
  • Page 14 Amendment coefficients of heating and cooling capacity under different height drop Different Cooling Capacity modified coefficients at different height: Equivalent pipe length EL (m) Note: H = Height of Outdoor Unit - Height of Indoor Unit Different Heating Capacity modified coefficients at different height: Equivalent pipe length EL(m) Note: H = Height of Outdoor Unit -...
  • Page 15: Demension

    4. Demension K12, K18 K24, K36 K48, K60...
  • Page 16: Electrical Wiring And Connection

    5. Electricfl wiring and connection K12, K18 (heating - cooling) K12, K18 (cooling)
  • Page 17 K24 (heating - cooling) K24 (cooling)
  • Page 18 K36, K48, K60 (heating - cooling & cooling)
  • Page 19 5. Electrical connection K12 (heating - cooling) indoor unit outdoor unit Multicore signal Wired controller Power cable Control wire Control wire Signal wire K12 (cooling) indoor unit outdoor unit Multicore signal wire Wired controller Power cable Control wire Control wire Signal wire...
  • Page 20 K18 (heating - cooling) indoor unit outdoor unit Multicore signal Wired controller Power cable Control wire Control wire Signal wire K18 (cooling) Indoor unit Outdoor unit Multicore signal wire Wired controller Power cable Control wire Control wire Signal wire...
  • Page 21 K24 (heating - cooling) Indoor unit Outdoor unit Multicore signal wire Wired controller Power cable Control wire Control wire Signal wire K24 (cooling) Indoor unit Outdoor unit Multicore signal wire Wired controller Power cable Control wire Control wire Signal wire K36, K48, K60 (heating - cooling &...
  • Page 22 Introduction of Control Board sockets QRDL-3F(2S)-SYE1 (indoor unit) (match with the outdoor unit which the Power supply is 220V-240V, 1PH) Compressor Electric Outdoor Drainage heating output 4-way pump Neutra Indoor fan output output valve output output l insert Neutral High 4-DIP switch Float switch Transformer...
  • Page 23: Installation

    6 Installation 6.1 Preparation before installation Please buy following spare parts from your local market Besides general implements, other implements are needed before installation when connecting the pipe Acetylene cylinders, oxygen cylinders (when longer pipe Hung bolts M12, 4 pcs used it should be welded) Drainage pipe PVC One set pipe cut machine.
  • Page 24 ◇ The unit should not be installed in the heat source, steam source oil mist places (such as machine room, kitchen, laundry room, mechanical workshop, etc.) in order to avoid performance degradation, electric shock, plastic parts corrosion which lead to unit broken; ◇...
  • Page 25 ◇ If this unit is installed on a sloping ceiling, a cushion block should be installed between the ceiling and the air outlet panel, in order to ensure that the unit is installed on a level surface. This is as shown in the drawing as follows: ◇...
  • Page 26 downs, it will cause water backflow or leakage etc. More than 1:100 ◇ The unit has a drain pump which will lift up to 1200mm. However after the pump stops the water still in the pipe will drain back and may overflow the drain tray causing a water leak. For this reason please install the drain pipe as shown Less than 300mm Less than 600mm...
  • Page 27 6.8 Connect duct, fresh air ventilation In order to meet different customers’ requirements and their different usage environment, 3hp and 5hp indoor unit reserves one fresh air ventilation hole and four duct connection holes. The fresh air can be introduced from outside or through duct. ◇...
  • Page 28: Explode View

    7. Explode view K12, K18 (heating - cooling & cooling) Remark 面板 MB13(英文) Panel MB13 回风格栅组件 Return-air grille assembly 空气过滤网 Air filter net 导风叶片 guide wind vane 步进电机 Step motor 24BYJ48-2 显示灯板 Display board SX-DISP-01 面板围框组件 Panel frame assembly 电控盒盖 Cover for electric components 电控盒总成...
  • Page 29 控制板 PCB board QRDL-3F(2S)-SYE1 变压器 Transformer TDB-8-B(PTC) 端子板 7 位 Terminal board 600V 2.5mm2 传感器 5K3470 XH2 0.5m(塑封) Sensor 1 传感器 5K3470 XH2 0.9m(铜壳) Sensor 2 橡胶塞 Rubber plug 接水盘组件 Water pan 蒸发器总成 Evaporator assembly 蒸发器组件 Evaporator part 蒸发器出气管组件 Evaporator outlet tube assembly 蒸发器进液管组件...
  • Page 30 K24, K36, K48, K60 (heating - cooling & cooling) Spare part list K24 (heating - cooling & cooling) 面板 MB12(英文) Panel MB12 面板边角盖板 Panel cover board 回风格栅组件 Return-air grille assembly 空气过滤网 Air filter 面板围框组件 Panel frame assembly 面板围框 1.4.1 Panel frame 导风叶片...
  • Page 31 变压器 Transformer TDB-8-B(PTC) 电容 capacitance 3μF/450V a.c 传感器 5K3470 XH2 0.5m(塑封) Sensor 1 传感器 5K3470 XH2 1.5m(铜壳) Sensor 2 底盘泡沫组件 Chassis foam assembly 底盘组件 Chassis assembly 配管盖板 Piping cover board 电机 Fan motor YDK30-6 Q 排水泵总成 Drain pump assembly 排水泵支架 10.1 Drain pump support 水泵减振橡胶...
  • Page 32 排水泵 10.3 Drain pump PLD-1200 排水软管(水泵用) 10.4 Drain flexible pipe (Drain pump) 排水接管 10.5 Drain pipe 浮子开关 GMF-31 10.6 Float switch 风轮 Wind wheel Ф462×147(3P) Spare part list K48, K60 (heating - cooling & cooling) 面板 MB12(英文) Panel MB12 面板边角盖板 Panel cover board 回风格栅组件...
  • Page 33 Idea LCAC R-410 On-Off Ceiling & floor type 1.Feature ..........................37 2.Specfication ........................39 3.Capacity amendment ......................45 4.Demension ........................47 5.Electrical wiring ......................48 6.Installation ........................56 7.Explode view ........................58...
  • Page 34: Feature

    Idea LCAC R-410 On-Off 1.Feature Ceiling& Foor type A/C (Cooling-only or Heat pump) can be installed under the ceiling and also on the floor. Compared with normal Floor &Standing type A/C, it can be hoisted under the ceiling,saving room space, it is also the updating Product for Floor & Standing type A/C.
  • Page 35 Function introduction Model Type Item 12/4 18/4 24/4 36/5 48/5 60/5 - - - High pressure protection ● ● ● - - - ● ● ● Low pressure protection ● ● ● ● ● ● Compressor overloading protection - - -...
  • Page 36: Specfication

    2.Specfication Indoor Model Outdoor IUB-18CR-SA6-N1 IUB-12CR-SA6-N1 IUB-12HR-SA6-N1 Indor IOU-18CR-SA6-N1 Outdoor IOU-12CR-SA6-N1 IOU-12HR-SA6-N1 V~,Hz,P Power Supply 220~240,50,1 220~240,50,1 220~240,50,1 Btu/h 12000 12000 18000 Cooling Capacity Btu/h 13500 Heating Rated Cooling Power Input 1.13 1.13 1.72 Rated Heating Power Input 1.15 Electric Data Rated Cooling Current 5.17 5.17...
  • Page 37 Max. Difference In Level ℃ Operation Temperature Range 16~32 16~32 16~32 ℃ Ambient Temperature Range(Cooling/Heating) -5~49 -5~49/-15~24 -5~49 Application Area 13-21 13-21 21-35 Power Wiring( Indoor) 3×1.5mm 3×1.5mm 3×2.5mm Connection Power Wiring( Outdoor) Wiring 3×1.5mm +2×1mm Signal Wiring 3×1.5mm +1mm 3×2.5mm +1mm Wireless Remote Controller...
  • Page 38 Fin Spacing Fin Material Hydrophilic aluminum fin Tube Outside Dia.and φ7,Inner grooved φ7,Inner grooved φ7,Inner grooved Material Coil Length x Height x Width 570×246×38.1 950×246×38.1 950×246×38.1 Heat Exchanging Area 6.00 10.00 10.00 Indoor Air Flow (Hi/Mi/Lo) 850/680/595 1200/960/840 1200/960/840 Noise Level(Hi/Mi/Lo) dB(A) 43/40/34 46/43/38...
  • Page 39 10.6 10.6 14.0 Btu/h 40000 Heating 11.7 Rated Cooling Power Input 3.77 3.77 4.87 Electric Rated Heating Power Input 3.50 Data Rated Cooling Current 7.22 7.22 9.32 Rated Heating Current 6.69 2.81 2.81 2.87 Performan 3.34 Model YSK-70W-4 YSK-70W-4 YSK-105W-4 Brand HUATE HUATE...
  • Page 40 Signal Wiring 2×1mm 2×1mm 2×1mm Wireless Remote Controller YKR-H/009E YKR-H/009E YKR-H/009E Qty’per 20’& 40’&40HQ(Only For Reference) 32/67/92 32/67/92 20/41/43 Note: 1. Working condition of the cooling capacity measured: Inside the room DB temperature 27℃,WB temperature19℃;Outside of the room DB temperature 35℃,WB temperature 24℃;Working condition of the heating capacity measured:Inside the room DB temperature 20℃,Outside of the room DB temperature 7℃,WB temperature 6℃。...
  • Page 41 Width Heat Exchanging Area 13.69 19.93 19.93 Indoor Air Flow (Hi/Mi/Lo) 1800/1440/1260 1800/1440/1260 1800/1440/1260 Noise Level(Hi/Mi/Lo) dB(A) 51/48/42 51/48/42 51/48/42 Net Dimension (W*H*D) 1631×660×205 1631×660×205 1631×660×205 Indoor Unit Packing Dimension 1710×720×280 1710×720×280 1710×720×280 (W*H*D) Net Weight Gross Weight Liquid Side 9.52 9.52 9.52...
  • Page 42: Capacity Amendment

    3 Capacity amendment 3.1 Running range Cooling capacity (Btu/h) 12000 18000 24000 36000 48000 60000 Power supply 220-240V~/50Hz 380-415V 3N~/50Hz Voltage 187~242V 320~420V Cooling -5~49℃ -5~45℃ Ambient temperature Heating -15~24℃ 3.2 Amendment coefficient of cooling capacity under different indoor/outdoor DB/WB temperature Indoor air inlet Outdoor air inlet DB temperature℃...
  • Page 43 3.4 Amendment coefficients of heating and cooling capacity under different height drop Different Cooling Capacity modified coefficients at different height: Equivalent pipe length EL (m) Note: H = Height of Outdoor Unit - Height of Indoor Unit 3.5 Different Heating Capacity modified coefficients at different height: Equivalent pipe length EL (m) Note: H = Height of Outdoor Unit -...
  • Page 44: Demension

    4. Demension K12, K18 K24, K36 K48, K60...
  • Page 45 5. Electricfl wiring and connection K12, K18 (heating - cooling) K12, K18 (cooling)
  • Page 46 K24 (heating - cooling) K24 (cooling)
  • Page 47 K36, K48, K60 (heating - cooling & cooling)
  • Page 48 5. Electrical connection K12 (heating - cooling) Indoor unit Outdoor unit Multicore signal wire Wired controller Power cable Control wire Control wire Signal wire K12 (cooling) Indoor unit Outdoor unit Multicore signal wire Wired controller Power cable Control wire Control wire Signal wire...
  • Page 49 K18 (heating - cooling) Indoor unit Outdoor unit Multicore signal wire Wired controller Power cable Control wire Control wire Signal wire K18 (cooling) Indoor unit Outdoor unit Multicore signal wire Wired controller Power cable Control wire Control wire Signal wire...
  • Page 50 K24 (heating - cooling) Indoor unit Outdoor unit Multicore signal wire Wired controller Power cable Control wire Control wire Signal wire K24 (cooling) Indoor unit Outdoor unit Multicore signal wire Wired controller Power cable Control wire Control wire Signal wire...
  • Page 51 K36, K48, K60 (heating - cooling & cooling)
  • Page 52 Introduction of Control Board sockets QRDL-3F(2S)-SYE1 (indoor unit) (match with the outdoor unit which the Power supply is 220V-240V, 1PH) Electric Compressor Neutra Outdoor Drainage output heating 4-way l insert pump Indoor fan output output valve output output Neutral High 4-DIP switch Float switch Transformer...
  • Page 53: Installation

    6. Installation 6.1 Preparation and equipments before installation Please buy following spare parts from your local market Besides general implements, other implements are needed before installation when connecting the pipe Acetylene cylinders, oxygen cylinders (when longer pipe used Hung bolts M12, 4 pcs it should be welded) Drainage pipe PVC One set pipe cut machine.
  • Page 54 water leakage, air leakage etc. will be resulted; ◇ Tighten the nuts and ensure that the hooks are tightly connected to the nuts and sMDms , and there is no phenomenon of virtual hanging; ◇ After the unit is installed ensure it is secure and does not shake or sway. 6.4 Drainage pipe installation ◇...
  • Page 55: Explode View

    7. Explode view K12, K18 (heating - cooling & cooling)
  • Page 56 K24, K36 (heating - cooling & cooling)
  • Page 57 K48, K60 (heating - cooling & cooling)
  • Page 58 Part 2 Universal outdoor unit...
  • Page 59 IOU-12HR-SA6-N1 Model IOU-18CR-SA6-N1 IOU-12CR-SA6-N1 V~,Hz, Power Supply 220~240,50,1 220~240,50,1 220~240,50,1 Max. Input Consumption 1750 1750 2650 Max. Current 12.0 Btu/h 12000 12000 18000 Cooling Capacity Btu/h 13500 Heating PA215X2CS-4KU Model PA150X2C-4FT PA150X2C-4FT Type ROTARY ROTARY ROTARY Brand TOSHIBA TOSHIBA TOSHIBA Capacity 3670 3670...
  • Page 60 Packing 880×350×610 880×350×610 930×410×660 Weight Gross Refrigerant Type R410A R410A R410A Type/Quantity Charged Volume 1160 1160 1360 Design Pressure 4.15 4.15 4.15 Liquid Side 6.35 6.35 6.35 Gas Side 12.7 12.7 12.7 Refrigerant Piping Max. Length Max. Height Operation Temperature Range ℃...
  • Page 61 Thermal Protection temp. UP3SE0391-T39 UP14SE5145 UP14SE5145 Capacitor Refrigerant Oil Model YDK65-6B YDK68-6A YDK68-6A code R60020207200 R60020209700 R60020209700 Brand OutdoorFan Output Power x Fan Motor 65*1 68*1 68*1 quantity Capacitor Speed r/min Number Of Row Tube Pitch(a)x Row 22×19.05 22×19.05 22×19.05 Pitch(b) Fin Pitch Fin Material...
  • Page 62 1. Nominal cooling capacities are based on the following conditions: Return air temp.: 27℃DB, 19℃WB, and outdoor temp.: 35℃DB, 24℃℃WB; 2. Nominal heating capacities are based on the following conditions: Return air temp.: 20℃DB, and outdoor temp.: 7℃DB, 6℃℃WB; 3. Parameters above are all measured when the connecting pipe is 5 meters. Model Factory Model IOU-36CR-SA6-N1...
  • Page 63 Packing 1030×410×980 1030×410×980 1090×430×1370 Weight Gross Type R410A R410A R410A Refrigerant Type/Quantity Charged Volume 2400 2400 2850 Design Pressure 4.15 4.15 4.15 Liquid Side 9.52 9.52 9.52 Gas Side 15.88 15.88 19.05 Refrigerant Piping Max. Length Max. Height ℃ Operation Temperature Range 16~32 16~32 16~32...
  • Page 64 Thermal Protection temp. 160±5℃ 160±5℃ 160±5℃ Capacitor Refrigerant Oil 1300 1300 1300 Model YDK68-6-359 YDK68-6-359 YDK68-6-359 code R60020200600 R60020200600 R60020200600 Brand WEITELI WEITELI WEITELI OutdoorFan Motor Output Power x Fan quantity 68*2 68*2 68*2 Capacitor Speed r/min Number Of Row Tube Pitch(a)x Row Pitch(b) 20.5×12.7 20.5×12.7...
  • Page 65 2 Capacity Amendment 2.1 Running range Cooling capacity (Btu/h) 12000 18000 24000 36000 48000 60000 Power supply 220-240V~/50Hz 380-415V 3N~/50Hz Voltage 187~242V 320~420V Cooling -5~45℃ A mbien temperature Heating -15~24℃ 2.2 Amendment coefficient of cooling capacity under different indoor/outdoor DB and WB temperature Indoor air inlet Outdoor air inlet DB temperature℃...
  • Page 66 Actual heating capacity calculation: Actual heating capacity=amendment coefficient of heating capacity × nominal heating capacity ——nominal heating capacity could be found from the performance parameters list ——amendment coefficient of heating capacity could be found from table above. 2.4 Amendment coefficients of heating and cooling capacity under different height drop Different Cooling Capacity modified coefficients at different height: Equivalent pipe length EL (m) Note: H = Height of Outdoor Unit -...
  • Page 67 3. Demension 4-10*19...
  • Page 68 4-10*19...
  • Page 69 K48, K60 4-10*19...
  • Page 70 4.System principle diagram Cooling circle: the Compressor inhales the low-temperature and low-pressure refrigerant vapor from the evaporator, and vapor be turned into high-temperature and high-pressure gas then enters into condenser, the high-temperature and high-pressure refrigerant gas and outdoor air make heat exchange in the condenser, the compressed vapor is then cooled by heat exchange with the outside air, so that the vapor condenses to be a high-temperature and high-pressure fluid, and then through capillary throttling to cooled, low pressure, then the liquid enters into the evaporator and two-phase of gas and liquid refrigerant...
  • Page 71 K36, K48, K60 (heating - cooling) Condenser Stopping Valve (gas) Evaporator T(Mild-Condenser) 4 Way Valve Low pressure switch High pressure indoor unit Fan switch T(Discharge) Comp. T(Evaporator) Liquid-vapor separator: T(Condenser) Capillary (Heating) Capillary (Cooling) One Way Valve (liquid) Stopping Valve Refrigerant flow direction in Cooling Refrigerant flow direction in Heating...
  • Page 72: Electrical Wiring

    5. Electrical wiring and connection K12, K18 (heating - cooling)
  • Page 73 K12, K18 (cooling) K24 (heating - cooling)
  • Page 74 K24 (cooling) K36, K48, K60 (heating - cooling & cooling)
  • Page 75 Introduction of Control Board QRD-SW3F-HCE1 (outdoor unit board) sockets (Power supply 380V-415V)
  • Page 76 6. Explode view K12 (heating - cooling & cooling) 左侧支撑板 Left-hand board 面板 Big panel 面板网罩(钢丝) Net for big panel 轴流风叶 Axial-flow wind leaves Ф400 室外风扇电机 Outdoor Motor 电机架 Motor bracket 隔风立板 Wind-defending vertical board 底盘组件 Chassis assembly 压缩机 Compressor PA150X2C-4FT 右侧板...
  • Page 77 传感器 1m 17.6 Sensor 1m 5K3470 EL2A 冷凝器总成 condenser assembly 冷凝器组件 18.1 condenser part 制冷毛细管 18.2 Cooling capillary 制热毛细管 18.3 Heating capillary...
  • Page 78 K18, K24 (heating - cooling & cooling) K18 (heating - cooling & cooling) 顶盖板 Top cover board 冷凝器总成 condenser assembly 冷凝器组件 condenser part 制冷毛细管 Cooling capillary 制热毛细管 Heating capillary 左侧板 Left-hand board 轴流风叶 Axial-flow wind leaves Ф420×150 面板 Big panel 面板网罩...
  • Page 79 电容 4μF 18.2 Capacitor for fan motor 4μF 端子板 18.3 Terminal board 电器架 18.4 Electric components box 传感器 0.5m 18.5 Sensor 0.5m 5K3470 EL2A 传感器 1m 18.6 Sensor 1m 5K3470 EL2A K24 (heating - cooling & cooling) 顶盖板 Top cover board 冷凝器总成...
  • Page 80 K36 (heating - cooling & cooling) 顶盖板 Top cover board 冷凝器总成 condenser assembly 冷凝器组件 condenser part 制冷毛细管 Cooling capillary 制热毛细管 Heating capillary 左侧板 Left-hand board 轴流风叶 Axial-flow wind leaves Ф490×130 面板 Big panel 面板网罩 Net for big panel 室外风扇电机 Outdoor Motor YDK150-6C-420 电机架组件...
  • Page 81 消音器 19.3 Muffler 高压开关 19.4 High Pressure Switch 电器架总成 Electric assembly 电容 6μF 20.1 Capacitor for fan motor 6μF 端子板 20.2 Terminal board 电器架 20.3 Electric components box 交流接触器 20.4 AC contactor 控制板 20.5 PCB board QRD-SW1C-HCE1 变压器 20.6 Transformer 传感器...
  • Page 82 隔风立板 Wind-defending vertical board 冷凝器总成 Condenser assembly 上冷凝器组件 Upside condenser part 下冷凝器组件 Underside condenser part 制冷毛细管 Cooling capillary Not including Cooling-only 制热毛细管 Heating capillary units 底盘组件 Chassis assembly 压缩机 Compressor E504DH-49D2G 回气管组件 Return air pipe assembly 低压开关 12.1 Low Pressure Switch 油温加热带...
  • Page 83 隔风立板 Wind-defending vertical board 冷凝器总成 Condenser assembly 上冷凝器组件 Upside condenser part 下冷凝器组件 Underside condenser part 节流毛细管 Throttle capillary 底盘组件 Chassis assembly 压缩机 Compressor E604DH-59D2G 回气管组件 Return air pipe assembly 低压开关 12.1 Low Pressure Switch 油温加热带 Oil heat strap 四通阀管路组件 Four-way valve assembly 高压开关...
  • Page 84 7. Installation 7.1 Preparation and equipments before installation Please buy following spare parts from your local market Besides general implements, other implements are needed before installation when connecting the pipe Acetylene cylinders, oxygen cylinders (when longer pipe Hung bolts M12, 4 pcs used it should be welded) Drainage pipe PVC One set pipe cut machine.
  • Page 85 The suitable length for bolt shall 20mm over the base level, in order to minimize vibration please do set a rubber shock absorber. ◇If the outdoor unit is mounted on the wall or on the rooftop, in order to prevent earthquake and strong wind please fasten it as tightly as possible.
  • Page 86 tighten the nut then using a wrench to tighten the nut again, the tighten torque as follows figure. ◇Take out the cover of the indoor unit gas valve and liquid valve, make the expanding right to the stop valve of outdoor unit, using hands to tighten the nut then using a wrench to tighten the nut again, the tighten torque as follows figure.
  • Page 87 pipe according to the pipe length parameter in this manual. Emptying or vacuum Before charging the refrigerant to the system, to ensure that there is no impurities, water or non-condensable gas. So, emptying and vacuum operation should be carried out. ◇Vacuum: when process this operation please be sure that the connection pipe is tightened up.
  • Page 88 Heat insulation package of piping ◇ Use heat insulation material with good insulation performanCF to wrap the pipe. Notes Drainage pipe and connection piping should be wrapped by heat insulation material respectively or there will be dew or leakage During the high temperature working environment, our air conditioner is proved my dew conditioner experiment.
  • Page 89 Additional refrigerant charge When pipe length exceeds 5m, please add refrigerant according to the table below: Connection Piping size) Additional refrigerant piping Gas pipe Liquid pipe charge amount (kg/m) φ9.52×0.75mm φ6.35×0.75mm 0.02 Piping φ12.7×1mm φ6.35×0.75mm 0.02 between φ15.88×1mm φ9.52×0.75mm 0.05 indoor and φ19.05×1mm φ9.52×0.75mm...
  • Page 90 the gas (large) pipe; When the vertical pipe height difference is more than 5 meters, then for every 5 meters an oil loop must be installed at the bottom of the gas (large) pipe, and a short loop (liquid ring) should be installed at the exit of the indoor unit liquid (small) pipe;...
  • Page 91 The earth line is neither allowed to connect to gas pipe, water pipe or circuitry of telephone or lighting rod, Notice nor to the earth line of other devices. Please fix power supply cord and connection wires of indoor and outdoor, in accordance with circuit diagram Fix the cords into terminal boards properly and safely with cable fixation tools to avoid any danger caused Others...
  • Page 92 7.5. Compressor freezing oil brand and standard oil charge Outdoor model Brand Compressor Model Compressor Lubricating Oil Model Oil charge (cm TOSHIBA PA150X2C-4FT ESTER OIL VG74 TOSHIBA PA215X2CS-4KU1 ESTER OIL VG74 TOSHIBA PA290X3CS-4MUI ESTER OIL VG74 HITACHI E404DH-38D2G FVC68D 1200 HITACHI E504DH-49D2G FVC68D...
  • Page 93: Part 4 Trouble Shooting

    Part 4 Trouble shooting 1.Main components of air conditioner ................179 2.Electrical system main components ................182 3.Poor efficiency explanation ..................184 4.Failure phenomenon ....................185 5.Electric components malfunction inspection ............186 6.Failure code display ..................... 187 7.Failure analysis ......................189...
  • Page 94: Main Components Of Air Conditioner

    1. Main components of air conditioner Appellation Figuration and inner configuration Instruction Rotary compressor function compressor: after refrigerant evaporate evaporator, compress the low temp and low pressure refrigerant gas, make the gas become high temp and high pressure gas, and then send the gas to condenser, make the refrigerant cycle, in this series products, all the compressors are complete hermetic...
  • Page 95 Elec.box Motor Function of evaporator: Evaporator Make the low pressure refrigerant liquid (heat from capillary or expansion valve happen exchanger) heat exchange with air Evap. Tray Elec. heater Function of capillary: Capillary Utilize aperture and length change bring (throttle pressure gap., control refrigerant flow components) quantity and pressure One way valve is used for heat pump...
  • Page 96 Function: Stop valve To stop or release refrigerant, only on/off, can’t adjust or throttle Function: Muffler Eliminate the system noise Function: Gas and liquid Separate liquid and gas refrigerant, separator to protect the compressor...
  • Page 97: Electrical System Main Components

    2.Electrical system main components Appellation Figuration and inner configuration Instruction Function: Via program to control the relay, make every components on/off according to temperature and pressure variety, so to realize automatic control Function: Fan motor Drive the fan, make the indoor and outdoor unit have heat exchange with air.
  • Page 98 Heat relay is normally made up of double metal sheet, when the Current setting Release link current is too large, the double button metal sheet will heat distortion and movement, and open the protection contactor ,which causes control Heat relay circuit disconnect and then the main circuit will be cut off, after it cooling, control circuit will restore...
  • Page 99: Poor Efficiency Explanation

    3. Poor efficiency explanation During the process of using air conditioner, some phenomenon seems to be malfunction but actually not. Thus when cooling effect does not to your expectation, the following factors have to be achieve ruled out Phenomenon Causing explanation When the outdoor temperature is higher, more heat penetrates into High outside temperature and too many indoor space, which increases the cooling load of AC.
  • Page 100: Failure Phenomenon

    4.Failure phenomenon Phenomenon Causing explanation Mirage comes out from indoor When the cold air from AC cools the indoor air unit 1. When air conditioner stops running, there will be some noise, and this is because the refrigerant flows contrarily. Noise 2.
  • Page 101: Electric Components Malfunction Inspection

    5.Electric components malfunction inspection Component Inspection methods name Using multi-meter ohm phase, there is correct resistance value among windings (single Compressor phase compressor refers to specification, three phase compressor resistance approximately equal), resistance of winding should be infinite. 1. 1Check if any connection part of PCB loosen or drop off, printed tinsel and components have any burn, fade, breaking off or aging phenomenon, all joints exist short circuit phenomenon etc.
  • Page 102: Failure Code Display

    6. Failure code display When air condition has failure, the timing lamp on light board of controller will display different code according to different failure case. 6.1 1Unit failure code for unit power supply is 220-240V Display mode 1 Display mode 2 Display Failure causing (indication lamp on display...
  • Page 103 Indoor temp. sensor Flash 1 times and go out - shutdown abnormal(TA) Indoor coil sensor Flash 3 times and go out - shutdown abnormal(TE) Outdoor coil sensor Flash 2 times and go out Flash 2 times non-stop abnormal(TW) and go out 2S Outdoor condensate temp.
  • Page 104: Failure Analysis

    7.Failure analysis Wired controller communication failure...
  • Page 105 Communication failure between indoor and outdoor unit...
  • Page 106 Outdoor protection(phase sequence)
  • Page 107 Cooling high pressure protection...
  • Page 108 Heating high pressure protection...
  • Page 109 Cooling low pressure protection...
  • Page 110 Heating low pressure protection...
  • Page 111 Cooling exhaust temperature protection...
  • Page 112 Heating exhaust temperature protection...
  • Page 113 Refrigerant shortage or four way valve failure protection...
  • Page 114 Sensor failure protection...
  • Page 115 No action after power-on...
  • Page 116 Poor effect...
  • Page 118 Abnormal sound or viberation...
  • Page 120 Abnormal odor...
  • Page 121 Air switch action when air conditioner starting up...
  • Page 122 Air conditioner water leakage...
  • Page 123 Remote receving:Receving signal of remote controller. Notes:Virtually all functions of the wired controller are the same as those of the remote controller and you should refer to the remote controller instructions. Wired controller: XK-02 ON/OFF button Switch the unit ON/OFF. Mode button: Select mode , push the button one time, then the operation modes will change in turn as below: Auto-Cooling-Dehumidify-Heating Temp +/- button: Press the button can adjust temperature.
  • Page 124 after 1 hour and another 1℃ auto matically after 1hour. 3. After the setting of sleeping mode,the heating operation enables the set temperature to drop 2℃ after 1 hour and another 2℃ auto matically after 1hour. 4. The air condition runs in sleeping mode for 7hours and stops automatically. Remark:Press the mode or ON/OFF button,the remote controller clears sleeping mode away.
  • Page 125 Part 6. Sensor resistance table Coil and environment temperature sensor 5K3470 resistance reference table Coil and environment temperature sensor 5K3470 Average (KΩ) Average (KΩ) Average (KΩ) Tx(℃) Tx(℃) Tx(℃) 72.99 5.854 1.421 35.16 5.626 1.376 33.43 5.408 1.334 31.80 5.199 1.293 30.26 5.000...
  • Page 126 6.877 1.563 0.489 6.603 1.724 0.476 6.342 1.466 0.464 6.092 Exhaust temperature sensor 6.339K3954 Exhaust temperature sensor R80:6.339KΩ±1% B25/80=3954K±1% Rmin [KΩ] Rmin [KΩ] Rmin [KΩ] Rmin [KΩ] T [℃] T [℃] T [℃] T [℃] 440.7 60.42 12.32 3.377 417.0 57.79 11.89 3.279...
  • Page 127 79.26 15.30 4.040 1.331 75.71 14.74 3.920 1.297 72.33 14.22 3.803 1.266 69.13 13.71 3.691 1.234 66.08 13.23 3.583 1.204 63.18 12.77 3.478 1.174...