Conrad MFT1816-12 V Operating Instructions Manual
Conrad MFT1816-12 V Operating Instructions Manual

Conrad MFT1816-12 V Operating Instructions Manual

Multifunction timer

Advertisement

Quick Links

 OPERATING INSTRUCTIONS
Version 03/13
Multifunction Timer
Item no. 39 39 03: „MFT1816-12 V"
Item no. 39 39 04: „MFT1816-24 V"

Advertisement

Table of Contents
loading

Summary of Contents for Conrad MFT1816-12 V

  • Page 1  OPERATING INSTRUCTIONS Version 03/13  Multifunction Timer Item no. 39 39 03: „MFT1816-12 V“ Item no. 39 39 04: „MFT1816-24 V“...
  • Page 2: Table Of Contents

    Table of Contents  Page 1. Introduction ........................................ 3 2. General Information ....................................4 3. Overview of the Available Operating Modes............................... 5 4. Installation of the PC Software ................................... 5 5. Operation of the PC Software ..................................6 6. Available Functions ....................................7 a) Staircase Lighting Timer ..................................
  • Page 3: Introduction

    All company names and product names are trademarks of their respective owners. All rights reserved. If there are any technical questions, contact: Germany: Tel. no.: +49 9604 / 40 88 80 Fax. no.: +49 9604 / 40 88 48 E-mail: tkb@conrad.de Mon. to Thur. 8.00am to 4.30pm, Fri. 8.00am to 2.00pm...
  • Page 4: General Information

    • The data interface serves only parameter transmission. It must not be connected to a computer during operation. The PC software is available free of charge at www.conrad.com in the download area for the „MFT1816“ (supported operating systems: Windows XP and higher)
  • Page 5: Overview Of The Available Operating Modes

    3. Overview of the Available Operating Modes Operating modes that can be set via the PC-software: Settable time (HH : MM : SS) Staircase Light Machine Options: • Activation time extension • Early shut-down 00:00:01 - 01:30:00 • Short push of the button: Time Extension Long push of a button (>3 s): Immediate shut-down •...
  • Page 6: Operation Of The Pc Software

    5. Operation of the PC Software After the first programme start of the PC-software, a dialogue window appears in which the language and communications port (COM port) are determined. The settings in this window are saved with „OK“ and can later be changed via „Setup“.
  • Page 7: Available Functions

    6. Available Functions a) Staircase Lighting Timer General: • The maximum time that can be set for the staircase lighting timer by the PC software is 90 minutes. • The service function or pre-warning function can be added optionally. • If the button at the input „SET“ is pushed for a short time, a positive level is pending. The relay is activated at once. When the button at the input „SET“...
  • Page 8: Options For The Staircase Lighting Timer

     Options for the Staircase Light ing Timer 1. „Activation Time Extension“ If the relay is already activated, another push of the button at the input „SET“ resets the activation duration to the set value. RESET RELAIS <------------------------T1------------------------> <------------------------T1------------------------> 2. „Early Shut-Down“ If the relay is already activated, another push of the button at the input „SET“...
  • Page 9: Additional Functions

         Additional functions 1. Prewarning function Pre-warning structure: After the end of the selected function with the set activation time T1, a 30-second pre-warning time T2 is attached. The relay swtiches off for a short time three times at reducing intervals within a pre-warning period T2. This deactivates the relay output. If the button at the input „SET“...
  • Page 10: B) Delay Functions

    b) Delay Functions 1. „Switch-Off Delay“ If the button at the input „SET“ is pushed for a short time, a positive level is pending. The relay is activated at once. When the button at the input „SET“ is released again, the relay remains activated for the set deactivation delay T1. If the button at the input „SET“ is pushed again during this time, this does not affect the set deactivation delay (timer time T1).
  • Page 11: Switch-On/Switch-Off Delay

    4. „Switch-On/Switch-Off Delay“ If the button at the input „SET“ is pushed, a positive level is pending and the set switch-on delay T1 will start at once. After the end of T1, the relay is activated for the duration of switch-off delay T2. If the button at the input „SET“...
  • Page 12: C) Sequence Functions

    c) Sequence Functions 1. „Alternating Button (REL<->SEQ)“ Operation of the button at the input „SET“ toggles the relay output and the sequence output („OFF“ <-> „ON“).  The function is NOT started with the input „SET“ but is activated by transferring the function on the multifunction transmitter! The function starts with activated relay output and deactivated sequence output.
  • Page 13: Step Button (Rel->Rel+Seq->Off)

    3. „Step Button (REL->REL+SEQ->OFF)“ Operation of the button at the input „SET“ toggles the relay output on, its sequence output on and then both outputs off in sequence. First operation of the button at the input „SET“ => relay output activated, sequence output deactivated. Second operation of the button at the input „SET“...
  • Page 14: D) Logical Operations (And, Or, Xor) Of The Inputs „Set" And „Reset

    d) Logical Operations (AND, OR, XOR) of the Inputs „SET“ and „RESET“ Logical operation Input 1 („SET“) Input 2 („RESET“) Relay The inputs „SET“ and „RESET“ can be used as logical inputs for the operation functions „AND“, „OR“ or „XOR“. ...
  • Page 15: E) Other Functions

    e) Other Functions 1. „Power Surge Switch“ (On/Off Switch) If the button at the input „SET“ is pushed, this causes the relay to toggle („ON“ <-> „OFF“). The push of a button at the input „RESET“ deactivates the relay output immediately. RESET RELAIS 2.
  • Page 16: On-Off Toggle" Switch (Activation And Break Time Can Be Set Independently)

    4. „On-Off Toggle“ Switch (Activation and Break Time can be set independently) While the button at the input „SET“ is kept pushed, the relay is activated or deactivated according to the respective switch-on time (T1) and break time (T2) set, starting with the activation time T1. Releasing the button at the input „SET“...
  • Page 17 Legal Notice  These operating instructions are a publication by Conrad Electronic SE, Klaus-Conrad-Str. 1, D-92240 Hirschau (www.conrad.com). All rights including translation reserved. Reproduction by any method, e.g. photocopy, microfilming, or the capture in electronic data processing systems require the prior written approval by the editor. Reprinting, also in part, is prohibited.