Optional Features Explained
THE FOLLOWING SETTINGS ARE OPTIONAL AND IN MOST CASES
NEED NOT BE ADJUSTED
Feature 01 - Temperature Format: This function allows you to select between °C and °F.
Feature 02 – Switching Differential: This function allows you to increase the switching
differential of the thermostat. The default is 1°C which means that with a set temperature
of 20°C, the thermostat will switch the heating on at 19°C and off at 20°C.
With a 2°C differential, the heating will switch on at 18°C and off at 20°C.
Feature 03 – Frost Protect: You can set whether the thermostat will maintain the frost
temperature when the thermostat display is turned off. As a default, this is enabled.
Feature 04 – Frost Protect Temperature: This is the temperature maintained when the
thermostat is in frost mode. The range is 07 - 17°C. The default is 12°C and is suitable for
most applications.
Feature 05 – Output Delay: To prevent rapid switching, an output delay can be entered.
This can be set from 00 - 15 minutes. The default is 00 which means there is no delay.
Feature 06 – Communication Address: This setting is used when you have connected
your thermostat to a network system. Each thermostat on your network must have a
unique communication address. This can be set from 01-32.