D LC Ser i es USER MANUAL D LC 6 0 0 w w w . m i n a r i k d r i v e s . c o m...
Page 2
No part of this document may be reproduced or transmitted in any form without written permission from Minarik Drives. The information and technical data in this document are subject to change without notice. Minarik Drives makes no warranty of any kind with respect to this material, including, but not limited to, the implied warranties of its merchantability and fitness for a given purpose.
Follow sound maintenance procedures. It is possible for a drive to run at full speed as a result of a component failure. Minarik Drives strongly recommends the installation of a master switch in the main power input to stop WARNING! the drive in an emergency.
Page 5
Save the Program Settings and Exit the Programming Mode ...23 Set the Speed ................24 Programming Examples ..............25 Section 8. Leader-Follower Applications ......31 Leader-Follower Example Using A Leader Encoder ......33 Leader-Follower Example Using Two DLC600’s .......35 Section 9. Troubleshooting ..........39 Unconditional Warranty ............. 41...
Page 6
List of Figures Figure 1 DLC600 Dimensions ............3 Figure 2 Panel Cutout ..............5 Figure 3 Inserting the DLC600 ............5 Figure 4 Inserting the Brackets ............6 Figure 5 Secure the DLC600 ............6 Figure 6 DLC600 Connections ............11 Figure 7 SW501 - Line Voltage Switch ..........13...
The user may enter and display the motor speed in RPM or other units, such as feet per minute or inches per second. The DLC600 offers the advantage of repeatable speed settings and speed stability.
DLC Series Section 2. Specifications AC Line Voltage 115/230 VAC ± 10%, 50/60 Hz, 1Ø AC Power 5.5 watts nominally Acceptable Feedback Sources 5 VDC or 12 VDC NPN-type encoder 5 VDC or 12 VDC NPN-type proximity switch Hall effect sensor Magnetic pickup Feedback Frequency Range External Reference Frequency*...
Precautions on page i before attempting to install this product. WARNING! Variable speed drives manufactured by other companies may require hookup procedures that differ from those given in this manual. Contact your local Minarik Drives distributor for assistance. Mounting •...
Step 1. Cut a rectangular hole in the panel 1.78 inches (45 mm) and 3.38 inches (86 mm) wide. PANEL 3.38 [86] CUTOUT AREA 1.78 BOUNDED BY [45] DASHED LINES Figure 2. Panel Cutout Step 2. Slide the DLC600 into the panel opening. Figure 3. Inserting the DLC600...
DLC Series Step 3. Insert the two mounting brackets into each side of the DLC600 case. Figure 4. Inserting the Brackets Step 4. Secure the DLC600 to the panel using the bracket screws. Figure 5. Secure the DLC600...
DLC Series Wiring Do not install, rewire, or remove this control with input power applied. Failure to heed this warning may result in fire, explosion, or serious injury. WARNING! Circuit potentials are at 115 or 230 VAC above ground. To prevent the risk of injury or fatality, avoid direct contact with the printed circuit board or with circuit elements.
WARNING! As a general rule, Minarik Drives recommends shielding of all conductors. If it is not practical to shield power conductors, it is recommended to shield all logic-level leads. If shielding of all logic-level leads is not practical, the user should twist all logic leads with themselves to minimize induced noise.
If using a regenerative drive, connect the DLC600 S1 to drive S0 and the DLC600 S2 to drive S2. Refer to Figure 6 on page 11. If using a XP-AC series drive, connect the DLC600 S1 to drive S2 and the DLC600 S2 to drive S1. Refer to Figure 6 on page 11.
Refer to Figure 6 on page 11. Frequency Terminal (Fin) The DLC600 can be used as a signal source to control another DLC600 via SO502 terminals FO+ and FO-. SO502 is a two-terminal, cage-clamp terminal block onthe printed circuit board. The frequency output available from these terminals is equal to 50% fo the commanded speed.
DLC Series MODEL DLC600 INPUT 115/230V AC, 50/60 Hz, 50 mA MINARIK DRIVES, SOUTH BELOIT, IL 61080 www.minarikdrives.com S2 Fin INHIBIT SWITCH OPEN TO RUN CLOSE TO INHIBIT 115 VAC 230 VAC EARTH GND MAGNETIC PICKUP AC VOLTAGE (NON-POLARIZED) NON-REGENERATIVE DRIVE...
RPM maximum 4000 The selected feedback device must produce 30 or fewer PPR. The DLC600 can control armature shaft speeds within a 30:1 speed range. Under no circumstances can the DLC600 be expected to control motor speed beyond this speed range.
The switches are visible when the nameplate is removed. Line Voltage Switch (SW501) The slide switch on the left rear of the DLC600 (Figure 7) is the voltage switch. Set this switch to the left position for 115 VAC input or to the right for 230 VAC input.
8). Set to OFF for +5 VDC source or to ON for a +12 VDC source. If using a device that does not need to be powered by the DLC600, set to OFF. The power supply voltage has a maximum current of 10 mA.
DLC Series Feedback Device Selection (SW502, DIP Switches 2 & 3) DIP switches 2 and 3 are for feedback device selection (Figure 9). If using an optical pickup, hall sensor, proximity switch, or an open-collector transducer, set DIP switch 2 to ON and 3 to OFF. If a magnetic pickup is used, set DIP switch 2 to OFF and 3 to ON.
DLC Series Reference Signal Selection (SW502, DIP Switches 4 & 5) DIP switches 4 and 5 are for reference signal selection (Figure 10). If an internal reference signal is used (normal operation), set DIP switch 4 to OFF and 5 to ON. If an external reference signal is used, set DIP switch 4 to ON and 5 to OFF.
Use a non-metallic screwdriver for calibration. Each trim pot is identified on the printed circuit board. Calibrate the drive for use with the DLC600. The purpose is to optimize the response on the drive to the DLC600 signal and to minimize any tendency by the drive to independently attempt to regulate motor speed.
3. Adjust the MIN trim pot CW until the motor shaft starts to rotate. Slowly adjust the MIN trim pot CCW until the motor just stops. 4. Set the DLC600 speed to 200% of maximum desired motor speed as outlined in step 2 above.
DLC600 except for the gate time. Speed Scaling Factor The speed scaling factor (SSF) correlates the digital speed set at the DLC600 with the speed (in RPM) desired at the feedback shaft. The SSF equation is (Speed Entry)(3000)
The load response number range is 0 through 99. The factory setting is Display Scaling Factor The display scaling factor (SSF) correlates the speed displayed by the DLC600 with the speed at the feedback shaft. The DSF equation is (Speed Display)(3000) SSF =...
Decimal Point Location The decimal point location number fixes the decimal point within the DLC600 display. The DLC600 may be set for no decimal point, or for a decimal point in the tenths, hundredths, or thousandths position. The factory setting is for no decimal point.
Entering the Programming Mode 1. Press and hold the ENTER pushbutton (labeled E) while applying AC power to the DLC600 only. Do not apply power to the drive. 2. Release the ENTER pushbutton after AC power is applied. You have entered the programming mode when the decimal point appears on the display in the lower right-hand corner.
DLC Series Entering the Calculated Program Parameters 1. Press ENTER until the decimal point is displayed in the lower right corner (e.g. 1 2 3 4.). 2. Press the UP and DOWN pushbuttons until you reach the desired speed scaling factor. 3.
9. Press ENTER once to return to the operating mode. 10. Remove power to the DLC600. 11. Reconnect the drive and apply power to the DLC600 and drive simultaneously. 12. The motor will accelerate to the set speed. 13. To change the set speed, repeat steps 1 - 9.
DLC Series Programming Examples Example 1 An application uses a 30 tooth magnetic pickup mounted on a motor shaft. The application requires that the motor speed and display be equal to the speed entry. Calculate the program parameters. Solution: PPR = 30 (given in example) Shaft RPM = 100 (arbitrarily chosen) Speed Entry = 100 (same as Shaft RPM) Speed Display = 100 (same as Shaft RPM)
Page 32
DLC Series Example 2 An application uses a 60 tooth magnetic pickup mounted on a motor shaft. The application requires that the motor speed and display be equal to the speed entry. Calculate the program parameters. Solution: PPR = 60 (given in example) Shaft RPM = 100 (arbitrarily chosen) Speed Entry = 100 (same as Shaft RPM) Speed Display = 100 (same as Shaft RPM)
Page 33
DLC Series Example 3 An application uses a 30 tooth magnetic pickup mounted on a motor shaft that is part of an exercise treadmill. The pulley is driving a belt that has a radius of 4 inches. The applications requires the user to enter the speed in miles per hour, and the display to read in miles per hour.
Page 34
Adding a decimal point widens the input range (the range of settings from 0 to maximum), increases the gate time, and decreases the rounding error to the nearest digit in the first calculation of the SSF and DSF. The DLC600 has a gate time range of 0.5 - 3 seconds.
Page 35
Gate Time = = 0.05 seconds The gate time is not within the DLC600’s range of 0.5 - 3 seconds. There is alos a significant error (20%) in rounding 2.5 to 3. Introduce a decimal point and recalculate the program parameters. Since the user will enter 10.0 for 10 RPM, the speed entry is now 100.
Page 36
DLC Series Recalculating the program parameters: (Speed Entry)(3000) (100)(3000) SSF = = 25 (Shaft RPM)(PPR) (400)(30) (Speed Display)(3000) (100)(3000) DSF = = 25 (Shaft RPM)(PPR) (400)(30) Gate Time = = 0.5 seconds This is much more acceptable. Note that there is no error due to rounding here because the SSF and DSF came out to be whole numbers.
The product of the external frequency and the set speed on the DLC600 must not exceed 500 kHz. This will limit the speed set value to to 5000 or less (500,000 / 10 = 50,000; however, the DLC600 only uses 4 digits. Thus, the maximum is 5000).
DLC Series Leader-Follower Example Using A Leader Encoder In this example, the DLC600 recieves a signal from an encoder on a lead motor. The DLC600 then controls a follower motor at 100% of the lead motor’s speed. Assume the following conditions exist: - The lead motor’s maximum speed is 1800 RPM.
Page 39
DLC Series Step 3. Calculate the SSF Program the speed scale factor (SSF) per the following formula: FR * Set Speed SSF = where, FR calculated in step 1. FM calculated in step 2. Desired leader/follower speed ratio, expressed as a Set Speed percentage.
DLC Series MODEL DLC600 INPUT 115/230V AC, 50/60 Hz, 50 mA MINARIK DRIVES, SOUTH BELOIT, IL 61080 www.minarikdrives.com S1 S2 Fin C INH RUN-STOP SWITCH OPEN TO RUN CLOSE TO STOP 115 VAC 230 VAC MAGNETIC PICKUP EARTH GND (NON-POLARIZED)
Leader-Follower Connections Use 14 - 28 AWG wire to connect the leader and follower DLC600’s. Connect SO502 terminal FO- on the leader DLC600 to the C terminal on the follower DLC600. Connect SO502 terminal FO+ on the leader DLC600 to the Fin terminal on the follower DLC600.
Page 42
DLC Series Programming the Follower Program the follower DLC600 as follows; 1. Calculate the follower reference frequency (FR) using the following formula: 25 * Lead Motor Speed in RPM FR = SSF of Lead DLC600 In this example, assume the lead motor speed is 1800 RPM. The leader SSF in this example is 100.
Page 43
The speed scale factor is 50. Enter this value as the SSF on the follower DLC600. 4. It is recommended that you set the DSF of the follower DLC600 to 100. Although any you can set whatever DSF value you’d like, setting it to 100 removes the need to correlate the DSF value with system speed.
DLC Series MOTOR DRIVE NO. 1 MOTOR DRIVE NO. 2 MOTOR MOTOR LINE INPUT PICK-UP PICK-UP STOP STOP LEADER FOLLOWER NO. 1 (RPM) SET IN PERCENT/DISPLAY IN RPM 1800 SET SPEED = 1800 RPM 100 SET SPEED = 1800 RPM SSF = 100 SSF = 50 DSF = 100...
Section 9. Troubleshooting The motor will not run. 1. The connections from the DLC600 ot the drive, or the drive to the motor, may not be wired correctly. Check the connections from the DLC600 to the drive and from the drive to the motor.
Page 46
For long paths, these leads must be shielded, and properly grounded at the DLC600 end. The motor is running at a fixed difference below set speed.
(12) months or 3000 hours, whichever comes first, from date of manufacture thereof. Within this warranty period, Minarik Drives will repair or replace, at its sole discretion, such products that are returned to Minarik Drives, 14300 De La Tour Drive, South Beloit, Illinois 61080 USA.
Page 48
w w w.m i n ar i kd r ive s. co m 1 430 0 D E L A TOU R D R IV E SO U TH B ELO IT, IL 6 1080 ( 800) MI NA R IK 25 0 -031 6 Rev 5...
Need help?
Do you have a question about the DLC600 and is the answer not in the manual?
Questions and answers