9-4. Troubleshooting check table
NOTE : Before taking measures, make sure that the symptom reappears for accurate troubleshooting.
Self check table
Abnormal
No.
Operation indicator lamp
point
Left lamp flashes.
0.5-second ON
Mis-Wiring
or serial
1
signal
0.5-second OFF
Indoor coil
Left lamp flashes.
thermistor
2-time flash
2
Room
tempera-
2.5-second OFF
ture
thermistor
Left lamp flashes.
3-time flash
Indoor fan
3
motor
2.5-second OFF
Left lamp flashes.
Indoor
4-time flash
control
4
system
2.5-second OFF
Left lamp flashes.
5-time flash
Outdoor
power
5
system
Left lamp flashes.
6-time flash
Outdoor
6
thermistors
Left lamp flashes.
7-time flash
Outdoor
control
7
system
Left lamp flashes.
14-time flash
Other
8
abnormality
2.5-second OFF
NOTE : When the indoor unit has started operation and the above detection method has detected an abnormality (the first
detection after the power ON), the indoor electronic control P.C. board turns OFF the indoor fan motor with
OPERATION INDICATOR lamp flashing.
· Flashing of OPERATION INDICATOR lamp (left-hand side lamp)
Lighted
indicates abnormalities.
Blinking
Not Lighted
Symptom
Indoor unit
and outdoor
unit do not
operate.
Indoor unit
and outdoor
unit do not
operate.
Indoor unit
and outdoor
unit do not
operate.
Indoor unit
and outdoor
unit do not
operate.
Indoor unit
and outdoor
unit do not
operate.
2.5-second OFF
Indoor unit
and outdoor
unit do not
operate.
2.5-second OFF
Indoor unit
and outdoor
unit do not
operate.
2.5-second OFF
Indoor unit
and outdoor
unit do not
operate.
Detection method
When serial signal from outdoor unit is not
received for a maximum of 6 minutes.
When the indoor coil or room temperature
thermistor is short or open circuit.
When rotational frequency feedback signal is
not emit during indoor fan operation.
When it cannot properly read data in the
nonvolatile memory of indoor electronic
control P.C. board.
When it consecutively occurs 3 times that the
compressor stops for overcurrent protection or
start-up failure protection witth in 1 minute
after start-up.
Outdoor thermistors short or open circuit
during compressor operation.
When it cannot properly read data in the
nonvolatile memory of the inverter P.C. board
or the outdoor electronic control P.C. board.
An abnormality other than above mentioned is
detected.
16
Check point
• Refer to 9-6.D "How to check
mis-wiring and serial signal
error".
• Refer to 9-7.the
characteristics of indoor coil
thermistor, and the room
temperature thermistor.
• Refer to 9-6.A "Check of
indoor fan motor".
• Replace the indoor electronic
control P.C. board.
• Refer to "Check of inverter/
compressor".
Refer to service manual
OB389 or OB377.
Check the stop valve.
• Refer to "Check of outdoor
thermistor".
Refer to service manual
OB389 or OB377.
• Replace the inverter P.C.
board or the outdoor
electronic control P.C. board.
Refer to service manual
OB389 or OB377.
• Confirm the abnormality in
detail using the failure mode
recall function.