EXAMPLE WIRING DIAGRAM
Figure 4 shows an example wiring diagram for a system using
two SEC-H-INT-KP SmartKeys. Note in this example,
SmartKey #1 is installed at the end of the RS-485 buss, on
which the security controller is daisy-chain connected on its
NPB-2X-485 option connector. From there, this SmartKey
buss continues on one pair of a 2-pair cable run to the SEC-H-
R2R module (the other pair is used for RS-485
communications between the security controller and its
expansion modules).
JUMPER 1
ON
SEC-H-INT-KP
SMARTKEY 1
J5
3
2
1
J1
3
2
1
BELDEN
9501 OR
EQUIVALENT
+ -
+ -
S
S
NPB-2X-485
OPTION CARD IN
PS–
OPTION SLOT 2
PS+
BB
SECURITY CONTROLLER
-
+
S
Fig. 4. Example wiring diagram for system with two SEC-H-INT-KP SmartKey units.
When done wiring, insert the SEC-H-INT-KP SmartKey onto
its backplate and secure with the screw in the bottom of its
case.
Wiring Checkout
After completing wiring terminations and restoring power to
the security controller, the LCD display on the SEC-H-INT-KP
SmartKey should display time, and keys should be backlit in
blue. This verifies power to the SmartKey.
To verify RS-485 communications, refer to the WEBs AX
Security User's Guide for setup procedures.
EOL RESISTOR JUMPER 1
SHOULD BE IN THE ON POSITION
ON AN END UNIT ONLY
CUT AND TAPE BACK SHIELD
BELDEN
9501 OR
EQUIVALENT
NPB-2X-485 OPTION
CONNECTOR PLUG
-
(SHOWN SCREW
S
SIDE UP)
BELDEN
9502 OR
EQUIVALENT
PS–
PS+
BB
-
+
S
From the SEC-H-R2R module, another 2-pair cable is run to
the SmartKey #2 unit, which allows for RS-485 "multidrop"
wiring (using one pair to return back to the SEC-H-R2R
module). Wiring can continue in this fashion to other SEC-H-
R2R modules and SmartKey units, if needed.
JUMPER 1
OFF
SEC-H-INT-KP
SMARTKEY 2
J5
3
2
1
J1
3
2
1
BELDEN
9502 OR
EQUIVALENT
BELDEN 9154
OR EQUIVALENT
PS–
PS+
BB
SEC-H-R2R
-
+
S
RELATED DOCUMENTATION
For more information on mounting and wiring a WEBs
Security system, refer to the following documents:
• SEC-H-201 Security Controller Installation Guide, 95-7750
• SEC-H-600 Security Controller Installation Guide, 95-7759
• SEC-H-R2R Remote Reader Module Installation Guide,
95-7749
• SEC-H-RIO Remote I/O Installation Guide, 74-4060
• SEC-ENC-H-1 and SEC-ENC-H-2 Medium and Large
Enclosure Installation Guide, 95-7747
• SEC-ENC-H-3 Small Enclosure Installation Guide,
95-7748
For details on software configuration for a fully functioning
security system, refer to the following document:
• WEBs AX Security Controller User's Guide, 74-4062
3
SEC-H-INT-KP SMARTKEY
PAIR 2
PAIR 1
CUT AND TAPE
BACK SHIELD
TO OTHER
UNITS
PS–
PS+
BB
-
+
S
M27322
62-0272—01

Advertisement