Sro series commercial reverse osmosis system (5 pages)
Summary of Contents for Sterling IFS10
Page 1
Installation Instructions and Owner’s Manual IFS Series Iron Filter / Softener System Sterling Water Treatment 12630 US Highway 33 N Churubusco, IN 46723 Phone (260) 693-1972 Fax (260) 693-0602 www.sterlingwatertreatment.com IFS Instruction Manual 140326.docx...
7.0, lower values indicate acidic water. The IFS performs best when the pH is 7.0, or higher. The IFS10 uses Iron Pro media blend in the filter in order to elevate low pH for proper iron oxidation.
Page 4
Water Supply Unlike other iron filters that do not use chemicals to oxidize the iron, the IFS iron filter portion does not require additional plumbing such as solenoid valves, pressure switches or pressure tanks. This filter will function properly when the water supply is furnished by a jet pump, submersible pump, variable speed (constant pressure) pump or community water supply.
Page 5
The manufacturer has set the water treatment unit’s sequence of cycles, cycle times, salt dose, exchange capacity and gallon capacity. The salt dose refill time has been preset. The dealer should read this page and guide the installer regarding hardness, day override, and time of regeneration, before installation: For the installer, the following sections should be read: ...
Bypass Valve The bypass valve is used to isolate the control valve from the plumbing system's water pressure in order to perform control valve repairs or maintenance. The 1" full flow bypass valve incorporates four positions including a diagnostic position that allows a service technician to have pressure to test a system while providing untreated bypass water to the building.
General Installation GENERAL INSTALLATION & SERVICE WARNINGS The control valve, fittings and/or bypass are designed to accommodate minor plumbing misalignments. There is a small amount of “give” to properly connect the piping but the water softener is not designed to support the weight of plumbing.
HAND TIGHTEN UNION NUTS ONLY. DO NOT OVERTIGHTEN. Outlet to service Inlet from water supply Brine Refill Elbow and BLFC Retainer Clip Brine Line Flow Control Assembly Drain Line Flow Control Assembly DLFC Retainer Clip (DLFC Elbow Fitting not shown) FIGURE 3: Top View of IFS10...
Page 9
STEP 6: Shut off water at main supply. Relieve pressure by opening nearest faucet. On private well systems, turn off power to pump and drain pressure tank. SHUT OFF POWER OR FUEL SUPPLY TO WATER HEATER. STEP 7: Cut main supply line as required to fit plumbing to inlet and outlet of bypass valve. DO NOT PLUMB INLET AND OUTLET BACKWARDS.
Page 10
Programming Procedures for the IFS 1. Set Time of Day: Time of day should only need to be set after extended power outages or when daylight saving time begins or ends. If an extended power outage occurs, the time of day will flash on and off indicating that the time should be reset.
Page 11
2. Programming cont’d: STEP 4 -- Regeneration Hour: The manufacturer has factory set 2:00 am as the default. This is the buttons. “AM/PM” toggles hour of day for regeneration and can be reset by using after 12. The default time is 2:00 a.m. (recommended for a normal household). Press next to go to step 5.
Operating Displays for the IFS 1. General Operation: When the system is operating, one of the three displays may be shown. Pressing next will alternate between displays. One of the displays is always the current time of day. The second display shows the current treated water flow rate through the system in Gallons Per Minute (gpm).
Page 13
TROUBLESHOOTING PROBLEM CAUSES SOLUTIONS A) Loose nut at either end of the brine line B) Brine line inserted into the brine tank 1) Tighten nuts at either end of brine line overflow fitting 2) Verify brine line is installed correctly rather than 3) Verify softener drain line is not connected connected to the...
1) See “Brine tank overfills” section (Page 12) “E” in Brine Tank 2) Resolve drain line issues Overfill section) 3) Contact Sterling technical support for C) Rinse cycle is short Salty Water assistance in verifying \ adjusting Rinse D) Salt setting too high...
Page 15
TROUBLESHOOTING (continued) PROBLEM CAUSES SOLUTIONS A) Outlet is on a switch Display shows B) Power outage 1) Use an un-switched outlet incorrect time-of-day C) Control valve was 2) Reset time-of-day or time-of-day flashes reset 3) Replace circuit board if needed D) Defective circuit board ERROR CODE:...
SPECIFICATIONS: UNIT MODEL NUMBER IFS10 MEDIA VOLUME (ft CAPACITY (grains) @Minimum Salt Setting (6#/ft 18,000 @Factory Salt Setting (9#/ft 21,000 @Maximum Salt Setting (15#/ft 32,000 SERVICE FLOW RATES (gpm) Continuous Peak PRESSURE LOSS (psi) @ Continuous Flow Rate @ Peak Flow Rate...
Control Valve Parts List REF # Part Number Description CV3002CC Drive Assembly, IM Series CV3186 Power Cord with Transformer CV3003 Meter and Cable Assembly CV3006 Bypass Valve, Less Fittings CV3175CC-01GR Front Cover, Gray CV3107-01 Drive Motor CV3108CC Circuit Board CV3004 Drive Cap Assembly CV3135 O-ring, -228...
Page 24
Installation Fitting Assemblies Continued 3/4" QUICK CONNECT Description Part # 3/4" QUICK CONNECT QFNCR4 (*2 required) SERVICE WRENCH - CV3193 Although no tools are necessary to assemble or disassemble the valve, the Service Wrench, (shown in various positions on the valve) is available to aid in assembly or disassembly.
Need help?
Do you have a question about the IFS10 and is the answer not in the manual?
Questions and answers