To Gain General Access; To Remove; Room Sealed Chamber - Vocera Linea Plus AG Installation & Servicing Instructions Manual

Table of Contents

Advertisement

8.4
To Gain General Access/Assembly
To remove components access to the interior
is essential. Refer to figs. 10 & 11.
Ensure electricity supply is isolated before
carrying out any servicing.
8.4.1
To remove front casing.
Push to release front door panel and lower to
reveal controls. Loosen the 2 captive screws
securing the front control panel to the lower
part of the casing and lower to reveal inside of
boiler (fig. 10).
Remove two screws at base of casing, slightly
lift the casing and slide it gently towards the
top of the appliance to disengage the case
from the top suspension hooks (fig. 11).
Ensure the casing and screws are put to one
side in a safe place.
8.4.2
Reassembly is always carried out in reverse
order to dismantling, unless otherwise stated.
Electrical connections must be remade in
accordance with the wiring diagram (figs.39-
40).
8.4.3
Where gas control components are replaced,
check the burner pressures and adjust if nec-
essary. See 8.23.
8.5
Room Sealed Chamber Front Cover
Refer to fig. 26.
8.5.1
Gain general access as 8.4.
8.5.2
Remove room sealed cover plate by releasing
two lower retaining clips and easing cover off
the top locating hooks. Inspect gasket for
damage. If damaged, replace.
NOTE: when refitting the combustion cham-
ber front cover it is essential to correctly seat
and secure the cover in place ensuring both
clips are secured in place.
Fig. 27 b
22
Supplied By www.heating spares.co Tel. 0161 620 6677
Flue gas analysis
Fig. 28 a
Fig. 26
test point
Fig. 27 a
Linea Plus AG