Monowave system
indirect heat pump cylinder range (25 pages)
Summary of Contents for Grant DuoWave Plus System
Page 1
Storage Cylinder Grant DuoWave Plus System Triple Coil Solar Cylinder Range Installation & User Instructions Part No. IRL 21. Rev 00. June 2011 Do not fit on a well or borehole supply...
Excessive Hot Water from Taps Discharge Pipe Arrangement Discharge Pipe Sizing User Instructions Worked Example User Instructions DuoWave Plus 300 Cold Water Storage Cistern (CWSC) 10 Warranty Cold Feed Pipe 10.1 The Grant Cylinder Warranty Open Vent Pipe Notes Primary Connections...
1.1 Installation Requirements 1.4 About Your New Cylinder 1.6 Pipework Connections All Pipework connections to the cylinder Thank you for purchasing a Grant The DuoWave Plus cylinder has three must be made in accordance with vented hot water storage cylinder from coils for connection to Primary heat Figure 2-2.
3 Primary Circuit Installation 3.1 Grant DuoWave Plus Solar 3.3 Auxiliary Primary Cylinders Connections Grant DuoWave Plus Solar cylinders are Solar Heating suitable for connecting to most fully The Solar flow and return connections pumped domestic gas or oil fired...
4 Secondary Circuit Installation 4.1 Discharge Pipe Arrangement 4.3 Worked Example The example below is for a ”diameter temperature relief valve with a Safety device ( e.g. temperature relief valve) discharge pipe (D2) having 4 elbows and a length of 7 m from the tundish to Metal the point of discharge.
4.4 DuoWave Plus 300 Cold water Breather with filter storage cistern Vent pipe The Grant DuoWave Plus 300 Open Purpose made Vented Indirect Solar cylinder is Insulating jacket fully fitted lid designed to be used as part of a static Open Vented hot water system.
5 Electrical Installation The unit must be permanently d) The BEAB approval certification on WARNING connected to the electrical supply this immersion heater only applies if through a double-pole isolator. A safety a Cotherm TSE rod type thermostats cut-out is also incorporated within the is used.
5.3 ‘Y’ Plan System Schematic and Wiring Diagram Grant DuoWave Plus Indirect water cylinder 3 port mid-position valve (not supplied) Radiator Not supplied Pump Boiler Figure 5-2: ‘Y’ Plan system schematic Blue Blue Green/Yellow Brown White Green/Yellow Grey 2 port...
5 Electrical Installation 5.4 ‘S’ Plan System Schematic and Wiring Diagram Grant DuoWave Plus Indirect water cylinder Radiator Not supplied 2 port diverter valve (not supplied) Pump Boiler Figure 5-4: ‘S’ Plan system schematic Blue Grey Blue Grey Brown Brown...
Collector Twin-coil Cylinder Grant GSD1 Controller Pump Station Electrical Junction Box (not supplied) Figure 5-6: Solar thermal schematic Grant GSD1 Mk2 Controller N E L Solar pump 230V Sensor N E L Solenoid valve Cylinder Collector bottom sensor 230V 3A...
6 Commissioning, Draining Down & Safety 6.1 Filling the Cylinder 6.3 Safety Cut-Out 6.4 Hot Water Discharge from Tundish IMPORTANT 1. The safety cut-out operates if: Before filling the cylinder check that the There are three reasons why hot water a.
8 Fault Finding Guide 8.1 Intermittent Water Discharge Intermittent Water Discharge from T & P Valve Thermostat Failure Immersion Thermostat Primary Cylinder Faulty T & P Failure Thermostat Valve Repair or Replace Repair or Replace Replace T & P Immersion Thermostat Thermostat Valve Test for correct operation.
8.2 Constant Water Discharge Constant Water Discharge from T & P Valve Faulty T & P Faulty Pressure Valve Reducing Valve Replace T & P Replace Pressure Valve Reducing Valve Test for correct operation. If water is still discharging, contact a competent Engineer...
8 Fault Finding Guide 8.3 No Flow from Hot Water Taps No Flow from Hot Water Taps Mains Supply Mains Supply Disconnected? Disconnected? Open supply valve or Repair or Replace wait for supply to be Thermostat reconnected Test for correct operation. If water is still not flowing, contact a competent Engineer...
8.4 Cold Water Flow from Hot Water Taps Cold Water from Hot Water Taps Is Motorised Valve Is Programmer calling Is Boiler working? for Hot Water? working? Check and Set Hot Is Cylinder Stat Water setting Calling for Heat? Check and Replace Cylinder Thermostat Test for correct operation.
8 Fault Finding Guide 8.5 Excessive Hot Water from Taps Excessive Hot Water from Taps Is System Wiring Correct Wiring as Is Cylinder Thermostat set too high? correct? per instructions Reduce Thermostat Is Cylinder Thermostat Replace Cylinder Setting Operating? Thermostat Fault.
9 User Instructions 9.1 User Instructions WARNING 1. Your Grant DuoWave Plus Solar vented hot water cylinder has been designed to give many years of If water is seen to flow from the trouble-free service and is made Temperature & Pressure Relief (T&P...
Proof of ‘purchase’ date must be guarantee. operation. provided upon request. 9. The Grant Cylinder must not be Grant Engineering (IRL) Ltd guarantees Chargeable Repairs: sited in a location where it may be all electrical and mechanical A charge will be made if the cause of subjected to frost.