When installing the appliance as a rear
vent unit, the 90° or 45° transition elbow
attached directly to the rear of the unit is
NOT INCLUDED in the following criteria
and calculations and, unless specifi cally
mentioned, should be ignored when
calculating venting layouts.
HORIZONTAL WITH VERTICAL RISE
(THROUGH-THE-WALL)
TERMINATION CONFIGURATIONS
Since it is very important that the venting system
maintain its balance between the combustion air
intake and the fl ue gas exhaust, certain limitations
as to vent confi gurations apply and must be strictly
adhered to.
The Vent Graph, showing the relationship between vertical
and horizontal side wall venting, will help to determine the
various dimensions allowable. Figure 18
Minimum clearance between vent pipes and combustible
materials is 3" on top and 1" from bottom and sides unless
otherwise noted (Exception: Outside wall with fi restop: 1"
all around pipes are allowed). If the vertical run is 7.5 feet
or more, from the fl oor of the fi replace, the clearance is 1"
on all sides of the horizontal run.
When vent termination exits through foundations less than
20" below siding outcrop, the vent pipe must be fl ush with
the siding.
It is best to locate the fi replace in such a way that minimizes
the number of offsets and horizontal vent length.
The horizontal vent run refers to the total length of vent
pipe from the fl ue collar of the fi replace (or the top of the
Transition Elbow) to the face of the fi nished outside wall
or the mounting fl ange of the termination.
The maximum number of 90° elbows per side wall
installation is three (3). Figure 25
If a 90° elbow is fi tted directly on the top of the fi replace,
the maximum horizontal vent run before the termination
or a vertical rise is 36" (914 mm). Figure 26
If a 90° elbow is used in the horizontal vent run (level
height maintained) the horizontal vent length is reduced
by 36". Figure 23. This does not apply if the 90° elbows
are used to increase or redirect a vertical rise. Figure
27
Example: According to the vent graph (Page 19) the
maximum horizontal vent length in a system with a 7.5'
vertical rise is 20' (6 m) and if a 90° elbow is required in the
horizontal vent it must be reduced to 17' (5.2 m).
In Figures 27 and 28 dimension A plus B must not be
greater than 17' (5.2 m).
22
3 x 90°
Elbows
Figure 25 -
Maximum Three (3) 90°
Elbows Per Installation
Figure 26 -
Maximum Horizontal Run
with No Rise
A
Figure 27 -
Horizontal Run Reduction
VENTING INSTALLATION
3 x 90°
Elbows
36"
(914 mm)
Max.
FP1177
90°
B
7'6"
20306750
FP1176
FP2837