Summary of Contents for Neoenerji 4KVA

  • Page 1 User Manual 4KVA/ 5KVA INVERTER / CHARGER...
  • Page 2: Table Of Contents

    CONTENTS ABOUT THIS MANUAL ............................. 1 Purpose ................................1 Scope ................................1 SAFETY INSTRUCTIONS ..........................1 INTRODUCTION ............................... 2 Features ................................2 Basic System Architecture ..........................2 Product Overview ............................. 3 Operation Diagrams and work conditions ......................4 INSTALLATION ..............................7 Unpacking and Inspection..........................
  • Page 3: About This Manual

    Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Please refer to INSTALLATION section of this manual for the details. 10. Fuses (4 pieces of 30A, 150VDC for 4KVA and 5pcs of that for 5KVA) are provided as over-current protection for the battery supply.
  • Page 4: Introduction

    INTRODUCTION This is a multi-function inverter/charger, combining functions of inverter, solar charger and battery charger to offer uninterruptible power support with portable size. Its comprehensive LCD display offers user-configurable and easy-accessible button operation such as battery charging current, AC/solar charger priority, and acceptable input voltage based on different applications.
  • Page 5: Product Overview

    Note: Appliances such as air conditioner are required at least 2~3 minutes to restart because it’s required to have enough time to balance refrigerant gas inside of circuits. If a power shortage occurs and recovers in a short time, it will cause damage to your connected appliances. To prevent this kind of damage, please check manufacturer of air conditioner if it’s equipped with time-delay function before installation.
  • Page 6: Operation Diagrams And Work Conditions

    Operation Diagrams and Working Conditions Abbreviation: charging current from AC charger charger current from solar charger total charging current of battery discharging current from battery DISC output current of AC load LOAD CSF, Solar Charge First CUF, Utility Charge First CS+UF, Solar &...
  • Page 7 The load is powered by battery power and solar power. Solar charger works when solar power is OK. The maximum I will go up to 50Amp. Then, the status of solar power and connected load will determine if battery is charge or discharge. 2) SOLAR CHARGE WITHOUT OUTPUT Utility Source Solar Source...
  • Page 8 5) AC & SOLAR CHARGE Utility Source LOAD Solar Source Solar Charger DC/AC Inverter AC Load Battery Bank The battery is charged by the utility and solar power at the same time. I and the maximum I is 50Amp. When the power ON/OFF switch is turned “ON’, the device will generate output to the load. If the power ON/OFF switch is turned “OFF”, the device won’t generate output to the load.
  • Page 9: Installation

    INSTALLATION Unpacking and Inspection Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should have received the following items inside of package:  The unit x 1  User manual x 1  Communication cable x 1 Preparation Before connecting all wirings, please take off bottom cover by removing two screws as shown below.
  • Page 10: Battery Connection

    Recommended battery cable and terminal size: Typical Battery Ring Type for Cable Model 1~3 m one-way Torque value Amperage capacity Terminal 1*4AWG KST: RNBS22-6 4KVA 200AH 2~ 3 Nm 2*8AWG KST: RNBS14-6 1*4AWG KST: RNBS22-6 5KVA 200AH 2~ 3 Nm 2*8AWG KST: RNBS14-6 Please follow below steps to implement battery connection: 1.
  • Page 11: Ac Input/Output Connection

    AC input. The recommended spec of AC breaker is 40A for 4KVA and 50A for 5KVA. CAUTION!! There are two terminal blocks with “IN” and “OUT” markings. Please do NOT mis-connect input and output connectors.
  • Page 12: Pv Connection (Only Apply For The Model With Solar Charger)

    To reduce risk of injury, please use the proper recommended cable size as below. Model Typical Amperage Cable Size Torque 4KVA/5KVA 8 AWG 1.4~1.6 Nm Please follow below steps to implement PV module connection: 1. Remove insulation sleeve 10 mm for positive and negative conductors.
  • Page 13: Final Assembly

    3. Make sure the wires are securely connected. Final Assembly After connecting all wirings, please put bottom cover back by screwing two screws as shown below. Communication Connection This inverter/charger is equipped with a communication port to communicate with a PC with corresponding software.
  • Page 14: Operation

    OPERATION Power ON/OFF Once the unit has been properly installed and the batteries are connected well, simply press On/Off switch (located on the button of the case) to turn on the unit. Operation and Display Panel The operation and display panel, shown in below chart, is on the front panel of the inverter. It includes three indicators, four function keys and a LCD display, indicating the operating status and input/output power information.
  • Page 15: Lcd Display Icons

    LCD Display Icons Icon Function description Input Source Information Indicates the AC input. Indicates the PV input Indicate input voltage, input frequency, PV voltage, battery voltage and charger current. Configuration Program and Fault Information Indicates the setting programs. Indicates the warning and fault codes. Warning: flashing with warning code.
  • Page 16 In battery mode, it will present battery capacity. Load Percentage Battery Voltage LCD Display < 1.717V/cell 1.717V/cell ~ 1.8V/cell Load >50% 1.8 ~ 1.883V/cell > 1.883 V/cell < 1.817V/cell 1.817V/cell ~ 1.9V/cell 50%> Load > 20% 1.9 ~ 1.983V/cell > 1.983 <...
  • Page 17: Lcd Setting

    LCD Setting After pressing and holding ENTER button for 3 seconds, the unit will enter setting mode. Press “UP” or “DOWN” button to select setting programs. And then, press “ENTER” button to confirm the selection or ESC button to exit. Setting Programs: Program Description...
  • Page 18: Display Setting

    Alarm on(default): Alarm off: Alarm control Backlight on(default): Backlight off: Backlight control Alarm on(default): Alarm off: Beeps while primary source is interrupted Record enable: Record disable(default): Record Fault code Display Setting The LCD display information will be switched in turns by pressing “UP” or “DOWN” key. The selectable input voltage, input frequency, battery voltage, charging current, information is switched as below order: PV voltage, output voltage, output frequency, load percentage, load in Watt, load in VA, CPU1 Version and...
  • Page 19 Current ≧ 10A Charging current/Output voltage Current < 10A When load is lower than 1kVA, load in VA will presents 350V as below. Input voltage/Load in VA When load is larger than 1kVA (≧1KVA), load in VA will presents 1.5kVA as below: When load is lower than 1kW, load in W will present 270W as below: Input voltage/Load in Watt...
  • Page 20: Operating Mode Description

    Main CPU version 00014.04 Main CPU version checking Secondary CPU version 00003.03 Secondary CPU version checking Operating Mode Description Operation mode Description LCD display Charging by utility and PV Charging by utility No output is supplied by the Standby mode/ Fault mode/ unit but it still can charge Power saving mode batteries.
  • Page 21: Fault Reference Code

    Power from battery and PV power. The unit will provide output Battery Mode power from battery and PV power. Power from battery only. Fault Reference Code Fault Code Fault Event Icon on Fan is locked Over temperature Battery voltage is too high Battery voltage is too low Output short circuited or Over temperature Output voltage is too high...
  • Page 22: Warning Indicator

    Warning Indicator Warning Warning Event Audible Alarm Icon flashing Code Beep three times every Fan is locked second Battery is over charged Beep once every 1second Beep once every 1 Low battery second Beep once every 0.5 Overload second Beep twice every 3 Power limitation seconds...
  • Page 23: Specifications

    SPECIFICATIONS Table 1 Line Mode Specifications INVERTER MODEL 4KVA 5KVA Input Voltage Waveform Sinusoidal (utility or generator) Nominal Input Voltage 230Vac 170Vac± 7V (UPS); Low Loss Voltage 90Vac± 7V (Appliances) 180Vac± 7V (UPS); Low Loss Return Voltage 100Vac± 7V (Appliances) High Loss Voltage 280Vac±...
  • Page 24: Table 2 Invert Mode Specifications

    Table 2 Invert Mode Specifications INVERTER MODEL 4KVA 5KVA 4KVA/3.2KW 5KVA/4KW Rated Output Power Pure Sine Wave Output Voltage Waveform 230Vac± 5% Output Voltage Regulation 50Hz Output Frequency Peak Efficiency Overload Protection 5s@≥150% load; 10s@110%~150% load 2* rated power for 5 seconds...
  • Page 25: Charging Controls

    Max. PV Array Open Circuit Voltage 125Vdc Standby Power Consumption DC Voltage Accuracy +/-0.3% Table 4 General Specifications INVERTER MODEL 4KVA/5KVA Safety Certification Operating Temperature Range 0°C to 55°C Storage temperature -15°C~ 60°C Dimension (D*W*H), mm 468 * 295 * 120...
  • Page 26: Trouble Shooting

    TROUBLE SHOOTING Problem LCD/LED/Buzzer Explanation / Possible cause What to do Unit shuts down LCD/LEDs and buzzer automatically will be active for 3 The battery voltage is too low 1. Re-charge battery. during startup seconds and then (<1.91V/Cell) 2. Replace battery. process.
  • Page 27: Appendix: Approximate Back-Up Time Table

    Appendix: Approximate Back-up Time Table Model Load (VA) Backup Time @ 12Vdc 100Ah (min) Backup Time @ 12Vdc 200Ah (min) 1610 1200 1600 2000 4KVA 2400 2800 3200 3600 4000 Model Load (VA) Backup Time @ 12Vdc 100Ah (min) Backup Time @ 12Vdc 200Ah (min)