General Installation Guidelines; Location Selection - LG LMCN077HV Installation Manual

Multi f; multi f max
Hide thumbs Also See for LMCN077HV:
Table of Contents

Advertisement

GENERAL INSTALLATION GUIDELINES

Location Selection

DANGER
To avoid the possibility of fire, do not install the unit in an area where combustible gas may generate, flow, stagnate, or leak. Installing the unit in
an area containing combustible gas will cause serious bodily injury or death.
Note:
Before beginning installation, read the safety summary at the beginning of this manual.
Select a location for installing the ceiling cassette indoor unit (IDU) that meets the following conditions:
• Place the unit where air circulation will not be blocked.
• Place the unit where drainage can be obtained easily.
• Place the unit where noise prevention is taken into consideration.
• Ensure there is sufficient strength to bear the load of the indoor unit.
• Ensure there is sufficient maintenance space.
• Locate the indoor unit in a location that is level, and where it can be easily connected to the outdoor unit / branch distribution unit.
The unit may be damaged, may malfunction, and / or will not operate as designed if installed in any of the conditions listed.
The unit should not be installed near a heat or steam source, or where considerable amounts of oil, iron powder, or flour are used.
Do not install the unit in an area where combustible gas may generate, flow, vent into, stagnate, leak, or be stored.
Do not install the unit in a location where acidic solution and spray (sulfur) are often used.
Do not use the unit in environments where oil, steam, or sulfuric gas are present.
Avoid installing the unit near high-frequency generators or near any equipment that generates an electromagnetic field (minimum
3-1/3 feet away)
Do not install the unit near a doorway.
Note:
If the unit is installed near a body of water, certain components are at risk of being corroded. Appropriate anti-corrosion methods should be taken for
the unit and all components.
Installing in a High or Dropped Ceiling
High or dropped ceilings, often found in commercial buildings and
offices, may cause a wide temperature differentiation. To counter-
measure:
• Change the indoor unit mode selection to allow for higher
ceilings (see table).
• Install an air circulator.
• Set the air discharge outlet so that heated air flows in a down-
ward direction.
• Use a dual door system to protect the building gate or exit.
Installing in an Area Exposed to Unconditioned Air
In some installation applications, areas (floors, walls) in some rooms may be exposed to unconditioned air (room may be above or next to an
unheated garage or storeroom). To countermeasure:
• Verify that carpet is or will be installed (carpet may increase the temperature by three (3) degrees).
• Add insulation between the floor joists.
• Install radiant heat or another type of heating system to the floor.
18
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Table 11: Ceiling Cassette Indoor Unit High Ceiling Mode Selection
Options.
Ceiling Height
≤7-1/2 feet
7-1/2 feet to 8-7/8 feet
8-7/8 feet to 10-3/16 feet
10-3/16 feet to 11-13/16 feet
F
MULTI
F
MULTI
MAX
Mode Selection
Low Ceiling
Standard
High Ceiling
Very High Ceiling

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lmcn185hvLmcn125hvLmcn097hv

Table of Contents