Air Flow, Weights And Filter Sizes; General Operation; Table 1 Cooling Performance And Air Flow; Table 2 Return Air Filter Sizes - Ice ECUA90 Installation & Operation Manual

Vertical air conditioners
Table of Contents

Advertisement

1.4
Weights and Filter Sizes
Complete electrical and performance specifications and dimensional drawings are in the Product Data
Sheet.
Model Number
Cooling BTUH
1
Rated Air Flow (CFM
)
2
ESP
@ Rated Conditions
3
Cooling rated at 95°F (35°C) outdoor and 80°F DB/67° WB (26.5°C DB/19.5°C WB) return air
1
CFM=Cubic Feet per Minute
2
ESP=External Static Pressure
3
Ratings are with no outside air. Performance will be affected by altitude.
Ratings are at 230 volts for 208/230 volt units ("C" models), 460 volts for "D" models, 380 volts for "E" models, 575 volts for "Z"
models. Derate performance by 17% for ACE (380v. 3ø, 50 Hz) models
Operation of units at a different voltage from that of the rating point will affect performance and air flow.
MODEL
Description
Exterior Access Return Air Filter 25" x 16" x 2" 635 x 406 x 51
ECUA90/120/150
Interior Access Return Air Filter 15" x 20" x 2" 381 x 508 x 51
ECUA90/120/150
ECUA180/240
Exterior Access Return Air Filter 25" x 16" x 2" 635 x 406 x 51
ECUA180/240
Interior Access Return Air Filter 24" x 18" x 2" 610 x 457 x 51
MODEL
ECUA90
ECUA120
ECUA150
ECUA180
ECUA240
1.5

General Operation

Refrigerant Cycle (Cooling Mode)
The air conditioners use R-410A refrigerant in a conventional vapor-compression refrigeration cycle to
transfer heat from air in an enclosed space to the outside. A motorized impeller assembly blows indoor
air across the evaporator. Cold liquid refrigerant passing through the evaporator is boiled into gas by
heat removed from the air. The warmed refrigerant gas enters the compressor where its temperature
and pressure are increased. The hot refrigerant gas condenses to liquid as heat is transferred to outdoor
air drawn across the condenser by the condenser fan. Liquid refrigerant is metered with a thermal
expansion valve (TXV) into the evaporator to repeat the cycle.
Heating Mode
A wall-mounted thermostat controls the heating cycle of models which incorporate resistance heating
elements. On a call for heat, the thermostat closes the heat relay to energize the indoor fan and the
resistance elements.
ECUA90
ECUA120
94,000
3,500
0.25
Table 1. Cooling Performance and Air Flow Ratings
INCHES
Table 2. Return Air Filter Sizes
Unit Weight
LBS
KG
1,053
478.6
1,160
527.3
1,166
530
2,307
1,046
2,523
1,144
Table 3. Shipping Weights & Dimensions
ECUA150
125,000
150,000
4,000
5,000
0.30
0.35
MILLIMETERS
PART NO.
Shipping
Weight
Height
LBS
KG
Inches
1,178
535.5
98
1,285
584.1
98
1,291
586.8
98
2,420
1,098
98
2,636
1,196
98
6
ECUA180
170,000
6,000
0.35
FILTERS PER UNIT
80137
3
92365
3
80137
4
81257
4
Shipping Dimensions
Width
MM
Inches
MM
2,489
56
1,422
2,489
56
1,422
2,489
56
1,422
2,489
76
1,930
2,489
76
1,930
ECU 04/2015 rev.3
ECUA240
235,000
8,000
0.40
MERV RATING
8
8
8
8
Depth
Inches
MM
42
1,067
48
1,219
48
1,219
51
1,295
51
1,295