Bacchus BCS2000 Installation Manual

Advertisement

Quick Links

Supplies Needed for Installation
1. 3/8" and 5/8" copper tubing.
2. 1/4" copper water supply
3. 1/4" condensate vinyl drain tube/tube clamps
4. Provide 120v 15A circuit for indoor evaporator, and 120v/230v 30A, single or three
(dependent upon your condensing unit) for outdoor condensing unit.
Check local codes.
5. 18-2 stat wire; to be used to extend temperature sensor, humidity sensor cable,
and master to slave control jumper.
6. Condensing unit pad
Condensing Unit Set Up
1. Place a (suggested model) on a firm level location (pad) for outdoor applications, or
anti-vibration pads to each corner of the condensing unit for indoor use. Place
in an area with adequate air flow.
2. Braze in suction and liquid lines to condensing unit.
3. Bring 3/8" copper tubing from the liquid line of the condensing unit to a spot
equidistant to both evaporators and solder that line into the run side of a 3/8" x 3/8" x
4. Braze both the 3/8" line to the liquid line of each evaporator from the run and branch
tee.
Installation Manual
BCS2000/3000
1
phase
keyboard,
add 4
3/8" tee.
of the

Advertisement

loading

Summary of Contents for Bacchus BCS2000

  • Page 1 Installation Manual BCS2000/3000 Supplies Needed for Installation 1. 3/8” and 5/8” copper tubing. 2. 1/4” copper water supply 3. 1/4” condensate vinyl drain tube/tube clamps 4. Provide 120v 15A circuit for indoor evaporator, and 120v/230v 30A, single or three phase (dependent upon your condensing unit) for outdoor condensing unit.
  • Page 2 Use moly bolts for all other mounting locations. Attach base securely to the ceiling. (diagram 1) Minimum 7 mounts. 4. Below is the BCS electronic control package used in both the BCS2000 and BCS3000 System. The main control module below must be mounted equidistantly between both evaporators in a serviceable location.
  • Page 3 5. The first port on the left includes two pieces of 18-2 that should be connected to each slave module in both evaporators at #1 and #2 terminals. These connections will shut down the system if there is ever a high water condition in either evaporator. They are connected parallel to each safety float.
  • Page 4 Controller Display Set Up 1. Install double gang box and cut out the blank plate to accept the Bacchus Temp/Humidity Keyboard (VH620). The keyboard can be mounted inside or outside of the room. Run 18-2 stat wire from the monitor back to the evaporator above the ceiling opening, and...
  • Page 5 Low humidity alarm outputs unchanged In the instance of any of these alarms, call Bacchus Tech Services, or your installation contractor Power to the Evaporator 1. Bring in 14-2 conductor wire with ground to the evaporator, and connect to the 14-2 with ground wire harness exiting the evaporator.
  • Page 6: Charging The System

    Charging the System 1. Evacuate and pressure test the system. This can be accomplished by charging with nitrogen to 75 lbs and checking your gauges for any sign of a leak. Evacuate the system to 500 microns. 2. Charge the system with R134A until the sight glass goes clear.
  • Page 7: Troubleshooting

    “HLA” Low humidity alarm outputs unchanged In the instance of any of these alarms, call Bacchus Tech Services, or your local service contractor Dimensional /Electrical BCS1000 BCS1000 BCS1500 BCS1500 BCS2000 BCS3000 Cond. Unit Evap. Con. Unit Evaporator Con. Unit Con. Unit Dims.
  • Page 8 Compressor 1/2 hp 115v .65 hp 115v 1 hp 115v 1 HP/voltage 208/230-1v Electrical compressor rla 12.1A compressor lra cond. Unit MFS 17.6A cond. Unit mca 13.4A 13.4A 11.3A 12.1A BTU capacity 40F 4857 6250 10200 (100 amb) 12,185 suc, 110 amb. Phone: 937-665-0424 Fax: 937-890-6664...