American Standard 2A7A3018-060A Installer's Manual
American Standard 2A7A3018-060A Installer's Manual

American Standard 2A7A3018-060A Installer's Manual

Condensing units

Advertisement

ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
IMPORTANT — This Document is customer property and is to remain with this unit. Please return to service information pack
upon completion of work.
These instructions do not cover all variations in systems
nor provide for every possible contingency to be met in
connection with installation. All phases of this installa-
tion must comply with NATIONAL, STATE AND LOCAL
CODES. Should further information be desired or should
particular problems arise which are not covered sufficiently for
the purchaser's purposes, the matter should be referred to your
installing dealer or local distributor.
A. GENERAL
WARNING:
for use by individuals possessing adequate backgrounds
of electrical and mechanical experience. Any attempt to
repair a central air conditioning product may result in
personal injury and or property damage. The manufac-
turer or seller cannot be responsible for the interpreta-
tion of this information, nor can it assume any liability in
connection with its use.
NOTE: AMERICAN STANDARD HEATING & AIR CONDI-
TIONING HAS ALWAYS RECOMMENDED INSTALLING
MANUFACTURER APPROVED MATCHED INDOOR AND
OUTDOOR SYSTEMS.
THE BENEFITS OF INSTALLING APPROVED MATCHED
SYSTEMS ARE MAXIMUM EFFICIENCY, OPTIMUM PER-
FORMANCE AND BEST OVERALL SYSTEM RELIABILITY.
Check for transportation damage after unit is uncrated. Report
promptly, to the carrier, any damage found to the unit.
To determine the electrical power requirements of the unit,
refer to the nameplate of the unit. The electrical power avail-
able must agree with that listed on the nameplate.
B. LOCATION AND PREPARATION OF THE UNIT
1. When removing unit from the pallet, notice the tabs on the
basepan. Remove tabs by cutting with a sharp tool as shown in
Figure 2 (see page 2).
2. The unit should be set on a level support pad at least as large
as the unit base pan, such as a concrete slab. If this is not the
application used please reference ALG-APG0*-EN (*latest revi-
sion number).
3. The support pad must NOT be in direct contact with any
structure. Unit must be positioned a minimum of 12" from any
wall or surrounding shrubbery to insure adequate airflow.
© 2009 American Standard Heating & Air Conditioning
INSTALLER'S GUIDE

Condensing Units

2A7A3018-060A
Models:
This information is intended
1
5 FT. ABOVE UNIT — UNRESTRICTED
Clearance must be provided in front of control box (access panels)
& any other side requiring service access to meet National
Electrical Code. Also, the unit location must be far enough away
from any structure to prevent excess roof run-off water from
pouring directly on the unit. When choosing the location of the
unit(s), sound transmission through air and refrigerant lineset
should be taken into consideration. It is recommended to locate
unit(s) away from areas (bedrooms, etc.) where such sound could
be objectionable.
4. The top discharge area must be unrestricted for at least
five (5) feet above the unit.
5. When the outdoor unit is mounted on a roof, be sure the roof
will support the unit's weight. Properly selected isolation is
recommended to prevent transmission to the building structure.
6. The maximum length of refrigerant lines from outdoor to
indoor unit should NOT exceed sixty (60) feet.
Since the manufacturer has a policy of continuous product
and product data improvement, it reserves the right to
change design and specifications without notice.
11-AC18D1-4

Advertisement

Table of Contents
loading

Summary of Contents for American Standard 2A7A3018-060A

  • Page 1: Condensing Units

    Since the manufacturer has a policy of continuous product and product data improvement, it reserves the right to © 2009 American Standard Heating & Air Conditioning change design and specifications without notice.
  • Page 2: Installer's Guide

    INSTALLER'S GUIDE Final refrigerant charge adjustment is necessary. Use BASEPAN TAB REMOVAL the Charging Information on page 6 or in the outdoor unit Service Facts. 1. Determine the most practical way to run the lines. 2. Consider types of bends to be made and space limitations. NOTE: Large diameter tubing will be very difficult to rebend once it has been shaped.
  • Page 3 INSTALLER'S GUIDE GAS LINE BALL SERVICE VALVE GAS LINE SERVICE VALVE 1/4 TURN ONLY COUNTERCLOCKWISE FOR FULL OPEN POSITION VALVE STEM UNIT SIDE OF VALVE PRESSURE TAP PORT GAS LINE CONNECTION SYSTEM EVACUATION NOTE: Since the outdoor unit has a refrigerant charge, the gas and liquid line valves must remain closed.
  • Page 4 INSTALLER'S GUIDE 11. The gas valve can now be opened. For a ball type gas valve, open the gas valve by removing the shut-off valve cap and PIN IDENTIFICATION turning the valve stem 1/4 turn counterclockwise, using 1/4" Open End or Adjustable wrench. See Figure 4. For brass gas line service valve opening, follow 9 and 10 above.
  • Page 5 INSTALLER'S GUIDE TYPICAL FIELD WIRING DIAGRAMS Notes: 1. Be sure power supply agrees with equipment nameplate. 2. Power wiring and grounding of equipment must comply with local codes. 3. Low voltage wiring to be No. 18 AWG minimum conductor. 4. ODT-B must be set lower than ODT-A. 5.
  • Page 6 INSTALLER'S GUIDE SUBCOOLING CHARGING IN COOLING ABOVE 55°F OD AMBIENT American Standard Heating & Air Conditioning has always R-22 SUBCOOLING CHARGING TABLE recommended installing manufacturer approved matched indoor and outdoor systems. DESIGN SUBCOOLING VALUES (°F) LIQUID All 13 SEER split systems are ARI rated with only TXV indoor TEMP .
  • Page 7 INSTALLER'S GUIDE 2A7A3 OUTLINE DRAWING NOTE: ALL DIMENSIONS ARE IN MM (INCHES). MODELS BASE FIG. 2A7A3018A 651 (25-5/8) 724 (28-1/2) 651 (25-5/8) 127 (5) 57 (2-1/4) 180 (7-1/8) 44 (1-3/4) 457 (18) 2A7A3024A 832 (32-3/4) 724 (28-1/2) 651 (25-5/8) 5/16 137 (5-3/8) 65 (2-5/8) 210 (8-1/4)
  • Page 8: Mounting Hole Location

    ........[ ] 7. Indoor coil drain line drains freely. Pour water into drain pan ..........[ ] Technical Literature - Printed in U.S.A. American Standard Heating & Air Conditioning Pub. No. 11-AC18D1-4 Troup Highway Tyler, TX 75707...