Photoelectronic Smoke Detector with Built-in Wireless Transmitter INSTALLATION AND OPERATION MANUAL ETLus Listed Model # SD4-SS Patents Pending. All Rights Reserved.
Page 2
What smoke detectors can do: Smoke detectors are designed to provide early warning of developing fires at a reasonable cost. They monitor the air and can sense smoke and can provide precious minutes for you and your family to escape before a fire spreads.
Page 3
Smoke detectors may not sense fires that start where smoke cannot reach the detectors such as in chimneys, in walls, on roofs, or on the other side of closed doors. If bedroom doors are usually closed at night, detectors should be placed in each bedroom as well as in the common hallway between them.
Page 4
can sense every kind of fire every time. In general, detectors may not always warn you about fired caused by carelessness and safety hazards like smoking in bed, violent explosions, escaping gas, improper storage of flammable materials, overloaded electrical circuits, children playing with matches or arson.
Page 5
minimum recommendations is one detector on each level of a building and one in every sleeping area. See how this recommendation applies in the figures below. • Put a smoke detector in the hallway outside of every separate bedroom area. See figure 1. Two detectors are required in homes with two bedroom areas.
Page 6
Figure 1: recommended smoke detector protection for single- floor residence with only one sleeping area. Family Kitchen Bedroom Dining Room Room Living Room Bedroom Bedroom Smoke detectors for minimum protection Smoke detectors for more protection Figure 2: recommended smoke detector protection for single- floor residence with more than one sleeping area.
Page 7
Bedroom Bedroom Bedroom Kitchen Living Garage Room Basement Smoke detectors for minimum protection Smoke detectors for more protection Figure 3: recommended smoke detector protection for a multi-level residence. • put a smoke detector inside bedrooms where a smoker sleeps. • put a smoke detector inside every bedroom where electrical appliances (such as portable heaters or humidifiers) are operated where someone sleeps.
Page 8
• Put a smoke detector inside every bedroom where someone sleeps with the door closed. Smoke could be blocked by the closed door, or the alarm may not wake the sleeper if the door is closed. • Put detectors as close to the center of the ceiling as possible. If this is not practical, put the detector on the ceiling, but no closer than 4 inches (10 cm) from any wall or corner.
Page 9
No closer than 4 inch Best in Dead (10 cm) from side wall center of ceiling Space Mount on wall at least 4 inch (10 cm) from ceiling No more than 6 inches (15 cm) from ceiling Best location Acceptable location Figure 4: recommended smoke detector mounting locations.
Page 10
as long as no other door or other obstructions block the path of smoke to the detector. • In rooms with sloped, peaked, or gabled ceilings, mount detectors within 3 feet (0.9 meters) measured horizontally from the highest point of the ceiling. See figure 5.
Page 11
This detector will provide maximum protection when installed in compliance with the National Fire Protection Association (NFPA). Standard NFPA 72, household fire warning equipment, defines the NFPA requirements for fire protection in private residence. This standard states that smoke detectors must be mounted in the following locations: “Smoke detectors shall be installed outside of each separate sleeping area in the immediate vicinity of the bedrooms and on each additional story of the family living unit including basements and excluding crawl spaces...
Page 12
as kitchens, in garages where there are particles of combustion from vehicle exhausts, near furnaces, hot water heaters, or gas space heaters. Install detectors at least 20 feet (6 meters) away from kitchens and any other areas where combustion particles are normally present. •...
Page 13
• In damp or very humid areas, or next to bathrooms with showers. The moisture in humid air can enter the sensing chamber as water vapor, and will cool and condense into droplets that cause a nuisance alarm. Install detectors at least 5 feet (1.5 meters) away from bathrooms. •...
Page 14
The transmitter will send alarm condition messages to the system’s receiver. Refer to the wireless system’s instructions for the maximum number of transmitters that can be supported. The Model #SD4-SS incorporates a state of the art optical sensing chamber and an advanced microprocessor. The microprocessor allows...
Page 15
This includes cleaning, maintenance or screen replacement. The Model #SD4-SS contains a piezoelectric horn which generates the ANSI S3.41 temporal pattern in an alarm condition. During an alarm condition, pressing the detector’s test switch will silence the piezoelectric horn for 5 minutes.
Page 16
Two LEDs and a sounder on the detector provide local visual and audible indication of the detector’s status: Table 1: Detector LED Modes Green LED Red LED Piezoelectric Horn Power-up Blinks every 5 Blinks every 5 seconds seconds Normal (standby) Blinks every 10 seconds Out of sensitivity Blinks every 5...
Page 17
DL123A Lithium battery (included). The detector checks for a low battery at least every 65 minutes. In addition, the red LED of the Model #SD4-SS will blink every 45 seconds and the test switch will be disabled. This condition will exist for a minimum of 7 days, and then the detector’s horn will “chirp”...
Page 18
batteries maybe purchased from a local hardware store. Battery Installation and Replacement To replace the battery: 1. Remove the detector from its mounting base by twisting the detector counterclockwise. Remove the battery and dispose of it properly. 2. To ensure proper power-down sequence, wait a minimum of 20 seconds before installing new battery.
Page 19
Test Switch Figure 7: Silent Call Model #SD4-SS Wireless Smoke Detector Green LED Red LED Programming The smoke detector is pre-programmed at the factory. Address Switch Settings The Silent Call system is digitally encoded. All Silent Call receivers and transmitters are tested and leave the factory programmed to a factory default address.
Page 20
that you MUST remove the batteries first or the switch setting will not take effect. 3. Locate the address switch on the transmitter circuit board that has 5 small dip switches. Set the switches to any combination that you want. For Example: 1, 2 ON 3, 4, 5 OFF. This gives your transmitter an “address.”...
Page 21
Figure 8: Detector Mounting Base Figure 9: Mount Detector Across Ceiling Panel Support. the following steps: 1. Once a suitable location has been determined, install the mounting base on the ceiling or on the wall (if local ordinances permit). Use the two screws and anchors provided.
Page 22
Testing the Sensor Detectors must be tested after installation and following periodic maintenance. The Model #SD4-SS may be tested as follows: A. Test Switch 1. A recessed test switch is located on the detector housing (see Figure 10).
Page 23
Test Switch Green LED Red LED PUSH RECESSED SWITCH WITH A 0.18’ MAX DIAMETER TOOL Recessed Test Switch Opening diameter of 0.18 inch (the detector will trigger and then the smoke detector will go into alarm thus sending a transmitting signal to the receiver.
Page 24
If the detector is within the listed sensitivity limits, the LED on the detector should blink once per second and the horn should sound within 3 seconds. B. Smoke Entry Test Hold a smoldering punk stick or cotton wick at the side of the detector and gently blow smoke through the detector until the unit alarms.
Page 25
NOTE: Power must be removed from the detector before performing maintenance of any kind by removing the detector’s battery. 1. To ensure proper power-down sequence, battery must be removed from detector for a minimum of 20 seconds before removing chamber top. 2.
Page 26
chamber and turning it clockwise until it snaps into place. 8. Reinstall the battery into the battery compartment noting proper orientation. 9. Reinstall the detector and test. (see the Testing section). Figure 11: Removing Screen/Sensing Chamber...
Page 27
What to do in case of fire • Don’t panic; stay calm. Follow your family escape plan. • Get of the house as quickly as possible. Don’t stop to get dressed or collect anything. • Feel doors with the back of your hand prior to opening them. If a door is cool, open it slowly.
Page 28
Operating Humidity Range: 0% to 95% Relative Humidity Agency Listings: Tested by ETL to comply with UL 217 Manufactured by: Silent Call Communications 5095 Williams Lake Rd Waterford, MI 48329 USA For warranty Silent Call Communications claims and service 5095 Williams Lake Rd...