IMPORTANT SAFETY INSTRUCTION SAVE THESE INSTRUCTIONS — This manual contains important instructions for all inverters that must be followed during installation, operation and maintenance of the equipment. To reduce the risk of fire or electric shock, install in a temperature and humidity controlled indoor area free of conductive contaminants.
Page 3
Owner’s Manual WARNING As standards, specifications, and designs are subject to change, please ask for confirmation of the information given in this publication. ATTENTION Comme les normes, spécifications et produits peuvent changer, veuillez demander confirmation des informations contenues dans cette publication. WARNUNG! Normen, Spezifizierungen und Plaene unterliegen Aenderungen.
Page 6
MGE UPS Systems warranty: warranties to distributors and other commercial customers: MGE UPS Systems warrants equipment manufactured by MGE UPS Systems to be free from defects in materials and workmanship for a period of one year from date of installation, but no longer than eighteen months from purchase by end user. No warranty shall extend more than three years beyond date of manufacture, except for Ultra-Isolator®...
Page 11
How To Use This Manual: A WARNING notebox indi- cates vided to protect the user and service personnel against safety hazards and/or possible equip- ment damage. An IMPORTANT notebox indicates provided as an operating instruction, or as an oper- ating tip. 86-153061-00 This manual is designed for ease of use and easy location of information.
Please retain this manual for future reference. The manual is divided into four sections: Section I — Introduction This section introduces the Topaz S3 family of single phase inverters, including a general description of the system and its internal components, a description of available options, and system specifications.
Page 14
Specifications 1 — 2 Section IV — Maintenance and Service This section describes maintenance of the Topaz S3 inverter, including safety instructions, preventive maintenance, and information about replacement parts, and customer service. A Glossary in the rear of this manual provides definitions of terms used within the text.
Characteristics of Model Ta bl e : C h a r a c t e r i s t i c s o f I nv e r t e r 1- 1 Model Number 63204* 63104* 63054* *Model number is followed by a two-digit dash number: -92 = Inverter with Status indicators.
Indicators and Controls 1.6.1 Digital LCD (Liquid Crystal Display) F i g u r e : S y s t e m S t a t u s R e a d o u t 1- 1 Upper Scroll Switch Lower Scroll Switch 86-153061-00 See Figure 2-1 on page 2-2 for the location of indicators and...
Topaz S3 Inverters 0.5 kVA, 1 kVA, & 2 kVA Ta bl e : L C D R e a d o u t D e f i n i t i o n s 1- 2 Column 1 Column 2 Column 3...
Page 19
The LCD can display a total of 10 different measurements, with two measurement values per line. The following is a list of measurements displayed: Load Volts (Vrms) Utility Volts (Vrms) DC Input Volts (VDC) Load Watts Inverter internal temperature (deg. C) To display a measurement, press and hold the UPPER or LOWER scroll switch until the LCD read-out changes to the desired measurement.
Topaz S3 Inverters 0.5 kVA, 1 kVA, & 2 kVA 1.6.3.1 Utility Failure (Only Available on Model With Static Transfer Switch) 1.6.3.2 Minor Alarm (Only Available on Model With Static Transfer Switch) 1.6.3.3 Major Alarm 1.6.4 Front Panel Controls 1 — 10 Alarm if Utility voltage is not within proper limits.
1.6.4.1 Input DC Circuit Breaker 1.6.4.2 Scroll Switch 1.6.5 Inverter Module Switches and Controls 86-153061-00 A circuit breaker is located on the front panel and identified as "DC INPUT". Turning the breaker to the ON position will apply the input D.C. voltage to a capacitor bank through a resistor network to limit the inrush current.
Page 24
Topaz S3 Inverters 0.5 kVA, 1 kVA, & 2 kVA F i g u r e : I nv e r t e r M o d u l e C o n f i g u r a t i o n fo r . 5 k VA a n d 1 k VA 1- 3A 1 —...
Page 25
Owner’s Manual F i g u r e : I nv e r t e r M o d u l e C o n f i g u r a t i o n fo r 2 k VA 1- 3B 86-153061-00 Introduction...
Topaz S3 Inverters 0.5 kVA, 1 kVA, & 2 kVA 1.6.5.1 Output Voltage Selection Modules with "BYPASS" option installed may be damaged when utility voltage and inverter output voltage settings are not the same. Un module avec l'option "BYPASS" risque d'être endommagé si les réglages de tension du réseau et de sortie onduleur ne sont pas les...
1.7.1 Dimensions 1.7.2 Weight Environmental Specifications 1.8.1 Operating Temperature 1.8.2 Non-Operating Temperature 1.8.3 Operating Humidity 1.8.4 Operating Altitude 1.8.5 Audible Noise 1.8.6 Cooling 86-153061-00 These dimensions include both the receiver cabinet and the inverter module. Depth is inclusive of the inverter module thumb screws.
Storage Prerequisites to Installation Installation This section describes the installation of the Topaz S3 0.5 kVA, 1 kVA, & 2 kVA including receiving, handling, storage, and installation procedures. Before accepting the shipment from the freight carrier, inspect the exterior surfaces of all shipping containers or packaging used, and the equipment, for damage that may have occurred during transit.
F i g u r e : O u t l i n e a n d M o u n t i n g fo r 2 k VA 2- 1B 2.5.2 Mounting And Wiring Access Input and output conductors must be sized for the maximum current as shown in Table 2-1 and otherwise be in compliance with applica- ble electrical codes.
2.5.3 Grounding 2.5.4 Inverter Connection 86-153061-00 For safety and proper operation of the unit, including maximum attenuation of electrical noise, suitable grounding is required. A separate grounding electrode conductor should be connected from the ground (GND) terminal to a nearby grounding electrode, and should be sized per National Electrical Code Article 250-94.
Page 34
Topaz S3 Inverters 0.5 kVA, 1 kVA, & 2 kVA F i g u r e : W i r i n g A c c e s s a n d C o n n e c t i o n fo r . 5 k VA & 1 k VA 2- 2A 2 —...
Page 35
Owner’s Manual F i g u r e : W i r i n g A c c e s s a n d C o n n e c t i o n fo r 2 k VA 2- 2B 86-153061-00 Installation and Operation 2 —...
Topaz S3 Inverters 0.5 kVA, 1 kVA, & 2 kVA 2.5.4.1 Hard Wire Access 2.5.4.2 Knockout Access 2.5.4.3 DC Hard Wire Connection This inverter was designed with the intent that the user will terminate the positive polarity terminal of the DC source to earth or chassis ground.
AC output will be present at the output terminals immediately when AC input is energized even without the inverter module installed in the receiver cabinet. La tension alternative de sortie appara ît dès la mise sous tension de le'entrée, même si le module onduleur n'est pas installé. Die Netzausgangsspannung ist unmittelbar an den Ausgangsklemmen, sowie der Netzeingang angeschlossen wird-slebst wenn der Einschub nicht im Gestell ist.
Topaz S3 Inverters 0.5 kVA, 1 kVA, & 2 kVA 2.6.1 Voltage Selection 2.6.2 Frequency Selection 2.6.3 Bypass 2.6.4 On-Line, Off-Line Operation 2.6.5 Automatic Restart 2 — 10 Viewed from the left side of the Inverter module, access holes can be seen for selecting the AC output voltage via a 120VAC/240VAC hard wired connector plug, and setting of the MICRO CONTROL "DIP"...
Page 39
Operation 86-153061-00 When all selections have been made, perform the following steps to operate the inverter: A) Be sure that all loads are disconnected or turned OFF and AC input power to models with a Static Transfer Switch is OFF. B) Refer to the installation checklist in Table 2-1 (page 4-3)and be sure that all control settings and terminal block screws are tight.
Page 40
Topaz S3 Inverters 0.5 kVA, 1 kVA, & 2 kVA Module may be damaged if removed with the DC breaker closed. Le module risque d'être endommagé s'il est retiré avec le disjoncteur DC fermé. Entfernung des Moduls mit geschlossenem Gleichstromunterbrecher koennte zu Schaden fuehren.
Inverter Theory of Operation This section describes the theory of operation of the Topaz S3 Inverter systems. The inverter utilizes a "Fly-back" converter to boost the input voltage to two regulated +/- 200 volt outputs. Two identical inverters are contained in the unit, both inverters controlled by a single PWM to generate sinusoidal AC outputs.
S3 Static Inverters 1kVA F i g u r e : I nv e r t e r B l o ck D i a g r a m 3- 1 3 — 2 Theory of Operation 86-153061-00...
Page 43
3.1.1 Battery Booster 3.1.1.1 Hysteretic Booster Operation 86-153061-00 The battery booster is a "continuous" mode Fly-back converter which takes the DC input voltage and boost it to four separate outputs of 200 volts. Two of these outputs are connected in series to produce -200 VDC and +200 VDC and used by one of the Inverters.
Page 44
S3 Static Inverters 1kVA F i g u r e : H y s t e r t i c B o o s t e r D i a g r a m 3- 2 3 — 4 Theory of Operation...
S3 Static Inverters 1kVA 3.1.2 Dual Inverters F i g u r e : D u a l I nv e r t e r a n d Wav e fo r m D i a g r a m...
Page 46
Topaz S3 Inverters 0.5 kVA, 1 kVA, & 2 kVA 3.1.2.1 Average Current Mode 3.1.2.2 Reference Sine Wave and Control 3 — 6 A microprocessor is used in the Inverter system to generate a reference sine wave via one of its three PWM outputs. The PWM signal is filtered to make a clean sine wave.
3.1.3 Static Transfer Switch and Maintenance Bypass Relay 3.1.3.1 On-Line, Off-Line Mode, and Static Transfer Switch 3.1.3.1.1Static Transfer Switch 86-153061-00 This is an optional feature that is described below. The ON LINE mode is defined as allowing the load to operate from the Inverter instead of the Utility power.
Topaz S3 Inverters 0.5 kVA, 1 kVA, & 2 kVA 3.1.3.1.2 Start Up Sequence 3.1.3.2 Off-Line Mode 3.1.4 Digital LCD Display 3.1.5 Status Indicators (LEDs) 3 — 8 When the inverter is enabled (by turning ON the front panel DC circuit breaker) the microprocessor goes through its start up sequence, including phase locking the reference sine wave to the Utility AC input.
Inverter can not operate properly. LED not illuminated indicates the inverter is not ON. An internal power supply is used within the inverter module which makes several 15 VDC outputs from the -48 VDC battery input and/or utility AC power through a transformer and bridge rectifier.
Topaz S3 Inverters 0.5 kVA, 1 kVA, & 2 kVA 3.1.6.2 Supply Operation The duty cycle of the UC3842ANs oscillator is set up to be about 45%. The output of the chip drives the gate of an IRF840 FET. The "Drain" of the FET is connected to a "Flyback"...
The following preventive maintenance routines should be considered the minimum requirements; your installation and site may require additional preventive maintenance to assure optimal performance from your installed Topaz S3 series Inverter System and associated equipment. recommend contracting MGE Customer Support Services for preventive and remedial maintenance.
Topaz S3 Inverters 0.5 kVA, 1 kVA, & 2 kVA Replacement Parts Troubleshooting and MGE Servicing 4 — 2 a. Ensure that all equipment is clean and free of loose dust, dirt, and debris. The exterior of all enclosures may be cleaned with a mild solution of soap and water, lightly applied with a lint-free cloth.
4.4.1 Installation Checks Ta bl e : I n s t a l l a t i o n C h e ck l i s t 4- 1 Installation Item To Be Verified DC Input Terminals Voltage Polarity AC Input Terminals Voltage Connections AC Output Terminals...
Topaz S3 Inverters 0.5 kVA, 1 kVA, & 2 kVA 4.4.2 Basic Inverter System (List 11, -B2 Models) 4 — 4 Before the inverter system can be turned on with the DC circuit breaker on the front panel, the DC power source must be energized.
4.4.3 Inverter With Static Transfer Switch (-94 Models) There will be AC on the output immediately when the AC input is ener- gized, even without turning the system ON with the DC circuit breaker. The digital LCD can display AC voltages, but not current when the DC circuit breaker is OFF since the Maintenance Bypass relay is closed.
Topaz S3 Inverters 0.5 kVA, 1 kVA, & 2 kVA 4.4.4 ON-LINE Mode 4.4.5 OFF-LINE Mode 4.4.6 Troubleshooting Guide 4 — 6 If AC has been applied to the Inverter and is within proper limits (120VAC or 230VAC, +/- 10% maximum) the Inverter...
Page 57
Ta bl e : Tro u b l e s h o o t i n g C h e ck l i s t 4- 2 SYMPTOM No response when DC circuit breaker is turned ON. Inverter STATUS indicator remains non-illuminated Inverter start up but STATUS indicator goes to RED after lamp...
Page 58
Topaz S3 Inverters 0.5 kVA, 1 kVA, & 2 kVA SYMPTOM Inverter will not start. Inverter starts and stops. Inverter STATUS indicator illuminated RED. Inverter starts and Inverter STATUS indicator is YELLOW. Bypass STATUS indicator is YELLOW or RED. 4 — 8...
Page 59
Symbols ¶ Used to reference paragraph headings that are listed in the table of contents. Used to represent “and/or.” Percent; of each hundred. ° F. Degrees Fahrenheit. ° C Degrees Celsius. ± Plus or minus. Number. Ø Phase. Ω Ohms. Second.
Page 60
Topaz S3 Inverters 0.5 kVA, 1 kVA, & 2 kVA Common. Circuit breaker. Conduit A flexible or rigid tube surrounding electrical conductors. C.S.S. Customer Support Services. Current rating The maximum current that a piece of electrical equipment is designed to carry.
Page 61
Input branch circuit Inverter Mains or mains 1 Main AC input source. Mains 2 module NFPA NO. or No. On-line mode Off-line mode OSHA 86-153061-00 The input circuit from the building power panel to the equipment. An electrical circuit that generates an AC sinewave output from a DC input. Kilovolt-Ampere;...
Page 62
Topaz S3 Inverters 0.5 kVA, 1 kVA, & 2 kVA Silicon-controlled rectifier. Shipping damage Any damage done to an article while it is in transit. SPDT Single Pole Double Throw. Static Transfer Switch An electronic or solid state switching mechanism electronically controlled to pass AC power directly from the utility to an output load.
__________________ STATE ______________ ZIP _____________ I would like to order _______ (quantity @ $50.00 each) additional copies of the: Topaz S3 Inverters 0.5 kVA,1 kVA, & 2 kVA Owner’s Manual 86-153061-00 B03 3/99 I would like to report the following problems with this document:...
Page 64