Download Print this page

MGE UPS Systems EX RT CLA Installation And User Manual page 2

Charger module

Advertisement

EX RT CLA Module
CLA Module (Long backup time charger)
(Part number 86004)
Extended back-up time (up to 8 hours at full load) requires a high power battery cabinet connected to the EX
5/7/11RT via the CLA module.
IMPORTANT
The CLA can not be used to charge the battery module (EXB). It is designed to charge the
customer provided high power battery cabinet.
Battery backup time chart.
Battery Backup Time
2 hours
4 hours
8 hours
Total battery voltage : 240 V DC (20 x 12V DC).
The battery capacity must be set within the UPS (5 Ah increment possible, see UPS Personalization sect
STEP 1 EX RT CLA Module Unpacking and Parts Check
EX RT CLA Module Box Contents
2
Recommended Batteries
EX 5 RT
50 Ah
65 Ah
100 Ah
130 Ah
200 Ah
200 Ah
EX RT CLA Module
Installation and
User Manual
Stabilizer Bracket
(4 screws included)
EX RT CLA Module Installation
EX 7 RT
EX 11 RT
100 Ah
200 Ah
400 Ah
Tower Stand Expanders
Power Cable
Battery Detection Cable
86-86000-04 AO

Advertisement

loading