PRECAUTIONS We strongly recommend installing supplementary natural ventilation, a failure alarm system as well as a back-up ther- mostat on at least one cooling stage (refer to the wiring diagram enclosed with this user's manual to connect the ther- mostat). Although fuses at the input and outputs of the controller protect its circuits in case of an overload or overvoltage, we recommend installing an additional protection device on the...
FEATURES The ST 5110 is an electronic device used for environmental control in live- stock buildings. It allows the user to maintain a specified target tempera- ture by controlling the operation of ventilation and heating equipment. One stage of variable speed cooling fans can be connected to the controller, as well as one stage of either constant-speed fans or heating units.
Page 5
CONTROL OF AIR INLET MOVEMENT If the ST 5110 is used in combination with a SB 2000 controller, the move- ment of the air inlets can be coordinated with the operation of the fans using a potentiometer located on the curtain machine or baffle actuator.
ST 5110 CONTROLLER STATUS LEDS INTERNAL SWITCHES The internal switches are located on the inside of the front cover. When the controller is shipped from the factory, all the switches are set to OFF. QM 1329.rev.00...
INSTALLATION OUNTING INSTRUCTIONS Open the latch and lift the cover. Remove the black caps located on each of the four mounting holes. Mount the enclosure on the wall using four screws. Be sure the electrical knockouts are at the bottom of the enclosure in order to prevent water from entering the controller.
ST 5110 OTOR TYPES The relationship between the voltage supplied to a motor and its operating speed is described by a motor curve. This curve varies with the make and capacity of the motor. The various motors available in the industry have been divided into five categories and the controller has been programmed with a different motor curve for each of these categories.
ST 5110 EATING / COOLING OPTION Stage 2 can operate as a heating or cooling stage. Set switch # 3 to OFF to use stage 2 for cooling. Set switch # 3 to ON to use Stage 2 for heating.
Page 12
ST 5110 It is preferable to solder the cable joint to ensure a proper contact between the two cables. CAUTION: Do not run probe cables next to other power cables. When crossing over other cables, cross at 90°. Defective Probes If a defective probe is detected, the Defective Probe Pilot Light turns on.
CHANGING THE PARAMETER SETTINGS HE MEANING OF A FLASHING DISPLAY The display will flash in cer- tain cases and not in others. The flashing indicates that the value shown can be adjusted. A value that is not flashing cannot be adjusted. OCKING THE PARAMETER SETTINGS The parameter settings can be locked to prevent accidentally modifying them.
TEMPERATURE SETTINGS EMPERATURE UNITS Temperatures can be displayed in either Celsius or Fahrenheit units Set internal switch # 2 to the desired position: • ON to display temperatures in Celsius units. • OFF to display temperatures in Fahrenheit units. IEWING TEMPERATURES The readout can display values from - 40.0 F to 120...
Page 15
ST 5110 Press the push-button. The temperature reading from probe 1 is dis- played, alternating with the letters "Pr 1" and the on/off state of probe For each additional probe, press the push-button. The temperature reading from probe x is displayed, alternating with the letters "Pr x"...
Page 16
ST 5110 Turn the adjustment knob clockwise by one notch. The minimum temperature is displayed, alternating with the letters "Lo". Turn the adjustment knob clockwise one notch further. The maxi- mum temperature is displayed, alternating with the letters "Hi". Turn the adjustment knob clockwise a third notch. The room tem- perature is displayed again.
ST 5110 EMPERATURE SET POINT The temperature set point is the target room temperature. It can be adjusted between -40.0°F and 99.9°F (-40.0°C and 37.7°C). Adjusting the Temperature Set Point Set the selection knob to SET POINT / TEMP. CURVE.The current set point flashes on the display.
ST 5110 EMPERATURE CURVE The user can define a temperature curve to adjust the set point automatically over a given time period. Temperature Days A curve is defined using six points. Each point specifies a day number and a set point for that day. Once the points of the curve are defined, the curve must be activated.
Page 19
ST 5110 Specifying the Curve Set the selection knob to SET POINT / TEMP. CURVE. The current temperature set point flashes on the display. Press the push-button. The word OFF is displayed indicating that the termperature curve is deactivated. If this is not the case, see below to deactivate the curve.
Page 20
ST 5110 Activating the Temperature Curve If you have just finished specifying the points on the curve: Press the push-button once again. The word OFF flashes on the display. Turn the adjustment knob clockwise one notch. The word ON flashes on the display and the Temperature Curve Pilot Light flashes, indicat- ing that the temperature curve is now activated.
Page 21
ST 5110 Viewing Current Set Point and Day Number When the temperature curve is activated, the current temperature set point and day number can be viewed at any time. The current day number can also be adjusted in order to move forward or backward on the temperature curve.
ST 5110 • Below the Set Point: the stage 1 fans stop operating continuously and operate according to the minimum ventilation cycle at minimum speed. INIMUM VENTILATION CYCLE When the room temperature is below the set point, the Stage 1 fans operate according to the minimum ventilation cycle.
Page 24
ST 5110 Adjusting Minimum Speed The minimum speed can be adjusted between 10 and 100% of the full speed of the fans. Set the selection knob to STAGE 1 — MINIMUM SPEED/CURVE. The current minimum speed for Stage 1 flashes on the display.
ST 5110 ENTILATION SETTINGS Adjusting the Stage 1 Bandwidth The Stage 1 bandwidth is the temperature interval within which the Stage 1 variable-speed fans increase or decrease in speed proportionally to the temperature (see the diagram above). The hysteresis is fixed at 0.3...
ST 5110 INIMUM VENTILATION SPEED CURVE The user can define a minimum ventilation speed curve to adjust the Stage 1 minimum speed automatically over a given time period. Each curve is defined by six points. Each point specifies a day number and a fan speed for that day.
Page 27
ST 5110 Table 1. STAGE 2 THRESHOLD VALUE OPERATION ''Set Point - 5.0°F (2.8°C)'' Cooling Heater A Starting Temperature - 5.0°F (2.8°C) Heating Interaction Between the Temperature Curve and the Mini- mum Speed Curve • The minimum speed curve can be activated only if the temperature curve is already activated •...
Page 28
ST 5110 • When the minimum speed curve is activated, it will effectively be oper- ating (i.e. the controller will begin to adjust the minimum speed ac- cording to the specified points of the curve) only when the current day number of the temperature curve reaches the first day number of the minimum speed curve.
Page 29
ST 5110 Specifying the Minimum Speed Curve Set the selection knob to STAGE 1 — MINIMUM SPEED / CURVE. The current minimum speed flashes on the display. Press the push-button. The word OFF is displayed, indicating that the minimum speed curve is deactivated. If this is not the case, deacti- vate the curve as described below.
Page 30
ST 5110 iii) Certain restrictions apply to reduce the risk of errors: • decreasing minimum speeds are not allowed. • the minimum speed variation cannot exceed 10% per day. Activating the Minimum Speed Curve If you have just finished specifying the points on the curve: Press the push-button once again.
Page 31
ST 5110 Viewing Current Minimum Speed and Day When the minimum speed curve is activated, the current minimum speed and day number can be viewed at any time. To modify the day number, refer to the section on temperature curves.
ST 5110 IST COOLING Stage 2 can be configured as a mist stage if no heating stage is needed. To access the parameters, position the selector switch at the Stage 2 starting temperature. The parameter settings are as follows: Starting Temperature (...
Page 33
ST 5110 Adjusting the Mist Starting Temperature The difference between the mist starting temperature and the starting temperature of the preceding stage can go from 0.5°F to 20.0°F (0.3°C and 11.1°C). Set the parameter selection knob to STAGE 2 - START TEMP. The current starting temperature appears flashing on the display.
HEATER SETTINGS RINCIPLE OF OPERATION The graph below explains the operation of the heater using sample values. Heating Heater A ON Heater A Heater A OFF Room Temperature HEATER Set Point A / ON TEMP. = 75 TEMP. = 74 = 72 If the room temperature rises: - at 74...
Page 35
ST 5110 Adjusting the Heater Off Temperature The heater off temperature can provide substantial energy savings if cor- rectly adjusted according to the outside temperature. It is the temperature at which the heating units turn off (see diagram above). The off tempera-...
ALARM SETTINGS The controller sets off an alarm in the case of a power failure, a fault in the supply circuit or a high or low temperature. Temperature alarms are defined according to the set point as shown in the diagram below. Room High Temperature Alarm Temperature...
TROUBLESHOOTING GUIDE SOLUTION PROBLEM CAUSE The circuit breaker Correct the problem and reset There is no at the service panel the circuit breaker. display. is off or tripped. The wiring is Correct the wiring. incorrect. The voltage selector Set the switch to the correct switch is in the position.
Page 38
ST 5110 SOLUTION PROBLEM CAUSE A variation in The display Be sure the probes are dry. resistance is shows sudden Locate them away from drafts induced on a variations in the and sources of radiant heat- probe. room or outside ing.
Page 39
ST 5110 SOLUTION PROBLEM CAUSE The stage 1 Adjust the minimum speed to The minimum variable speed a higher value. speed is too low. cooling fans are not running. The fan motor is Check if the motor is defective (continued) defective.
Page 40
ST 5110 PROBLEM CAUSE SOLUTION Set the stage 1 time off to The stage 1 The stage 1 time off a value other than zero. variable speed is set to zero. cooling fans run continuously Correct the wiring. Be sure...
Page 41
ST 5110 SOLUTION PROBLEM CAUSE Be sure the cable is firmly The display board The cooling plugged in. interconnect cable fans are not is not properly running. plugged into the power supply board. The heaters are The fan motor or Check if the motor or heater is not turning on.
FACTORY SETTINGS i t r NOTES: i) These initial parameter settings will not be retained in the controller's memory. Each new setting will replace the preceding one. ii) If the power supply is cut off, the last parameter settings will be retained in memory until the power is restored.