for fan continuous operation or is dependant upon connection
to the fan supply input . When internally wired for fan
continuous operation, the fan will be off when the system
switch is off. When dependant upon external connections the
fan may not be off with the system switch in the off position.
The fan supply input is switched to fan speed outputs (HI -
MED - LO).
SWITCHED POWER: L1 power is switched to this output any
time the system switch is out of the OFF position.

Ratings

Table 1: Fan and system switches
Inductive
Voltage
Resistive
Rating
Amps
FLA
LRA
24 VAC
N.A.
N.A.
N.A.
120
5.8
34.8
6.0
240
2.9
17.4
5.0
277
2.4
14.4
4.2
Wire Lead Colors (if applicable)
White with Orange Stripe
White with Red Stripe
White with Brown Stripe
Red
Blue
Black
Yellow
Orange
Violet
Brown
Brown

Application Notes

To use a remote sensor, remove jumper JP-1 to disable
1
local sensing. See
Figure
using a remote sensor will cause improper operation of
the thermostat. Some units do not have remote sensing
capability.
2
Units with remote sensing capability have a four-position
terminal block at TB1. If TB1 is two position the unit is
local sensing only.
Remote probe wiring should be located away from any
3
electrical motors or power wiring
Some units are internally wired for permanent fan
4
continuous operation.
On units with a Fan Supply input, the operation of the
5
fan is determined by wiring connection. For fan
continuous, jumper the Fan Supply input (TB2-5) to the
Switched Power output (TB3-3).
For fan cycling operation with a call for heat or cool, a
6
fan relay must be used.
Pilot
Thermostatic
Duty
Switching
24 VA
10 VA
125 VA
20 VA
125 VA
20 VA
125 VA
20 VA
Fan High
Fan Med.
Fan Low
Heat
Cool
L1
L2 or Neutral
Switched Power
Fan Supply
Remote Probe
Remote Probe
1. Failure to remove JP-1 when
© 2009 Daikin
7
Observe electrical ratings. Thermostatic outputs are pilot
duty only.

Wiring Diagrams

Figure 2: Units with remote sensing capability
TB3
TB2
L2 or NEUTRAL
TB1-4
NO CONNECTION
TB1-3
REMOTE PROBE 1
TB1-2
TB1-1
REMOTE PROBE 2
Figure 3: Units with switches used for local sensing only
TB3
TB2
L2 or NEUTRAL
TB1-4
NO CONNECTION
TB1-3
Figure 4: Units with no switches with local/remote sensing
capability
L2 or NEUTRAL
TB1-4
NO CONNECTION
TB1-3
REMOTE PROBE 1
TB1-2
TB1-1
REMOTE PROBE 2
Figure 5: Units with no switches used for local sensing
only
L2 or NEUTRAL
TB1-4
NO CONNECTION
TB1-3
800-432-1342
www.DaikinApplied.com
TB3-1
HEAT
OUTPUT
TB3-2
COOL
OUTPUT
TB3-3
SWITCHED POWER
TB2-1
L1
TB2-2
FAN HIGH
CONNECT
TB2-3
FAN MED
FOR FAN
FAN
CONTINUOUS
TB2-4
FAN LOW
TB2-5
FAN SUPPLY
TB3-1
HEAT
OUTPUT
TB3-2
COOL
OUTPUT
TB3-3
SWITCHED POWER
TB2-1
L1
TB2-2
FAN HIGH
CONNECT
TB2-3
FAN MED
FOR FAN
FAN
CONTINUOUS
TB2-4
FAN LOW
TB2-5
FAN SUPPLY
TB3-1
HEAT
OUTPUT
TB3-2
COOL
TB3
OUTPUT
TB3-3
L1
TB3-1
HEAT
OUTPUT
TB3-2
COOL
TB3
OUTPUT
TB3-3
L1
IM 1014/Page 46