APT XM Series Installation, Operation & Maintenance Manual

Surge protective device

Advertisement

Quick Links

XM Series
Surge Protective Device (SPD)
Installation, Operation
& Maintenance Manual
Thank you for choosing an APT Surge
Protective Device (SPD). The XM is a high quality,
high energy surge suppressor designed to protect
sensitive equipment from damaging transient
overvoltages. The SPD is parallel connected
such that circuit ampacity is unlimited. Proper
installation is important to maximize performance.
Please follow steps outlined herein. These
instructions are not intended to replace national or
local codes. Follow all applicable electrical codes
to ensure compliance.
XM complies with latest regulatory actions and is
UL 1449 Listed (VZCA.E321351). See National
Electrical Code (NEC
WARNING
Risk of Electric Shock
Only qualified licensed electricians should install or
service SPDs
SPDs should never be installed or serviced when
energized or during electrical storms
Use appropriate safety precautions including
Personal Protection Equipment
Failure to follow these instructions can result in
death, serious injury, and/or equipment damage
When used in outdoor applications, customer must
seal the conduit nipple using watertight fittings (not
included) to ensure a watertight connection
Read this manual in its entirety prior to installing
Advanced Protection Technologies
14550 58th Street North
(800) 237-4567
www.aptsurge.com
UL is a registered trademark of Underwriters Laboratories, NEC
registered trademarks of National Fire Protection Association, C62.41.1-2002, C62.41.2-2002,
C62.45-2002, C62.72-2007 are registered trademarks of IEEE.
) Article 285 regarding SPDs.
®
·
Clearwater, Florida 33760
·
(727) 535-6339
·
info@aptsurge.com
®
XM is a Type 2 SPD, intended for installation
on the load-side of the service disconnect. We
recommend connecting via a 20-30A circuit breaker
due to 10 AWG conductors. UL 1449 safety and
performance evaluations were performed with a
30A circuit breaker. The circuit breaker serves as
a disconnect switch and provides NEC
short circuit protection to the conductors in Type
2 applications.
Simplified Explanation of Operation
SPDs sense overvoltage and create a momentary
short circuit to redirect harmful surge energy to
earth ground. They reset automatically and wait
for the next surge. This is similar to the pressure
relief valve on a water heater: pressure goes up,
valve opens to relieve pressure and then resets. In
an electrical system, an SPD senses overvoltage,
shorts temporarily sending energy to ground and
then resets. SPDs are capable of repeating this
function thousands of times.
Parts List:
1 – XM suppressor including 3' (~1m) conductors
1 - Data Sheet
1 - Installation Sheet (this document)
Specifications
Temperature Operating
Temperature Storage
Wire Size & Installation Torque 10 AWG; 18 inch-pounds
Appropriate Circuit Breaker
NEMA 250 Enclosure Rating
·
Fax (727) 539-8955
and National Electrical Code are
imposed
®
-40
C (-40
F) to +85
C (+140
o
o
o
-55
C (-67
F) to +85
C (+149
o
o
o
20-30A
Type 4X with appropriate
sealing and sealing condulets
European Authorized Representative
Obelis s.a.
Boulevard Général Wahis 53
1030 Brussels, BELGIUM
Tel: +(32) 2. 732.59.54
Fax: +(32) 2. 732.60.03
E-Mail: mail@obelis.net
F)
o
F)
o

Advertisement

loading
Need help?

Need help?

Do you have a question about the XM Series and is the answer not in the manual?

Questions and answers

Summary of Contents for APT XM Series

  • Page 1 Surge Protective Device (SPD) Installation, Operation & Maintenance Manual Thank you for choosing an APT Surge XM is a Type 2 SPD, intended for installation Protective Device (SPD). The XM is a high quality, on the load-side of the service disconnect. We...
  • Page 2 INSTALLATION Pre-Plan your installation. You need to accomplish the following: ▪ Meet all National and Local codes. (NEC Article 285 and UL 1449 address SPDs). ® ▪ Confirm System voltage to SPD voltage. (120V SPD will fail instantly on 240V, 277V, etc.). ▪...
  • Page 3 See Three (3) 3’ (~1m) 18 AWG wires are included attached Data Sheet or call APT Tech Support at through the hub with this option. (These are (800) 237-4567 as appropriate. The SPD’s specifier smaller than the 10 AWG SPD conductors.) Gray...
  • Page 4 NORMAL OPERATION Maintenance Green LED Indicators – The SPD includes two SPDs require minimal maintenance. We green LED indicators per phase for redundancy recommend periodic inspection of diagnostic purposes. Full Protection is indicated when indicators to ensure proper operation. We also both LEDs for every phase are illuminated.