Xulux BT-PIR108 Install Manual

Xulux bt-pir108 ceiling pir presence detector

Advertisement

Quick Links

detection pattern
speci cation
LOAD
8 Amp resistive and incandescent lighting
4 Amp uorescent lighting
3 Amp compact uorescent lighting
3 Amp low energy lighting
3 Amp low voltage lighting (switch primary of transformer)
3 Amp fans and ventilation equipment
Switch SON lighting loads via a contactor
SUPPLY VOLTAGE
220 -240 Volts AC 50 Hz
TIME OUT PERIOD
Adjustable 10s to 30m
LIGHT LEVEL
Light to dark
2
TERMINAL CAPACITY
2.5 mm
MATERIAL
Flame retardant ABS
TYPE
Class 2
TEMPERATURE
-10°C to 35°C
CONFORMITY
EMC -89/336/EEC
LVD -73/23/EEC
IMPORTANT NOTICE!
This device should be installed by a quali ed electrician in
accordance with the latest edition of the IEE wiring regulations.
FM 45789
EMS 534520
Due to our policy of continual product improvement Xulux reserves the right
to alter the speci cation of this product without prior notice.
Xulux Pty Ltd
14/388 Newman Road
Geebung
4034
Australia
Tel:
(07) 3172 7131
Fax:
(07) 3161 5598
www.xulux.com.au
sales@xulux.com.au
BT-PIR108
Ceiling PIR Presence Detector
dimensions
wiring diagram
description and operation
The BT-PIR108 presence detector is designed to provide automatic control of lighting, heating or ventilation
loads. It detects movement using a PIR sensor and turns the load on. When an area is no longer oc-
cupied the load will switch o after an adjustable time out period.
An adjustable internal light sensor provides additional energy saving in lighting applications. When an
area is occupied lighting is only switched on when the level of natural light is below a preset level.
When the unit is rst powered up the PIR sensor will always detect immediately regardless of whether
the room is occupied.

Advertisement

loading

Summary of Contents for Xulux BT-PIR108

  • Page 1 14/388 Newman Road This device should be installed by a quali ed electrician in The BT-PIR108 presence detector is designed to provide automatic control of lighting, heating or ventilation Geebung accordance with the latest edition of the IEE wiring regulations.
  • Page 2 mounting installation The detector should be sited so that the occupants of the room fall inside the detection pattern FLUSH FIXING shown overleaf, at a recommended height of 2.8m on the ceiling. Note that the lower the sensor is Hole Ø64mm installed the smaller the detection range will be, subject to the parameters shown on the diagram.