Check; Thermistor Resistance Check - Daikin 2MXS-N Series Service Manual

Hide thumbs Also See for 2MXS-N Series:
Table of Contents

Advertisement

Check

8. Check

8.1

Thermistor Resistance Check

Check No.01
Disconnect the connectors of the thermistors from the PCB, and measure the resistance of each
thermistor using multimeter.
166
The data is for reference purpose only.
Thermistor temperature
°C
–20
–15
–10
–5
0
5
10
15
20
25
30
35
40
45
50
(kΩ)
150
100
50
When the room temperature thermistor is soldered on a PCB, remove the PCB from the control
PCB to measure the resistance.
When the connector of indoor heat exchanger thermistor is soldered on a PCB, remove the
thermistor and measure the resistance.
Resistance (kΩ)
°F
–4
197.8
5
148.2
14
112.1
23
85.60
32
65.93
41
51.14
50
39.99
59
31.52
68
25.02
77
20.00
86
16.10
95
13.04
104
10.62
113
8.707
122
7.176
(R25°C (77°F) = 20 kΩ, B = 3950 K)
–15
0
15
30
45
5
32
59
86
113
Multimeter
Resistance range
(˚C)
(˚F)
(R14467)
Room temperature
thermistor
Multimeter
(R19752)
(R19751)
Service Diagnosis