Troubleshooting

12-2-15 Compressor lock error

1. Checklist :
1) Is the connection of cable for the compressor and power?
2) Is the interphase resistance of compressor normal?
2. Troubleshooting procedure
Restart after power off.
Is the lock error occurred again?
Is the interphase resistance value of
compressor (u v, v w, w u) normal?
Is the compressor body and
interphase resistance insulated?
Is the connection cable for the
compressor and power terminal normal?
Exchange the PCB.
12-17
141 Kinderkamack Rd, Park Ridge, NJ 07656 Tel: 201-782-1782 Fax: 201-782-1783 Web: www.amgair.com Email: info@amgair.com
No
Yes
No
Yes
No
Yes
No
Yes
Air Marketing Group LLC
Terminate the service.
Exchange the compressor.
Exchange the compressor.
Correct the cable connection.
Samsung Electronics