POST HEATING SEASON MAINTENANCE

The water should be left in the outdoor furnace if the
outdoor furnace is not being used for an extended period
of time. Check pH and nitrite levels as described in the
Water Quality and Maintenance section.
1. At the end of the heating season, clean all the ashes
out of the outdoor furnace. Scrape the walls and
floor of the firebox taking special care to clean at the
ash line and below, especially in the corners.
2. Check behind the baffle and in the chimney flue.
Clean out any excessive buildup. Any large or dry
crusty deposits on the walls, baffle or heat exchanger
area should be removed. A thin, tar-like coating
of creosote above the ash line does not need to be
scraped clean as it works like a protective coating
on the metal. When cleaning the firebox, be sure to
wear the appropriate personal protective gear.
3. When the furnace is clean, carefully inspect the
firebox for any signs of excessive corrosion or
deterioration. If any corrosion or deterioration is
found, call your dealer. It is always better to do
maintenance during the non-heating season.
4. After the inspection is completed, apply a thin coat
of new motor oil to the firebox being sure to work oil
into all corners.
5. Place a cover over the chimney to keep rain from
entering the outdoor furnace. Clean and oil the
chimney flue (and on 4030 models only, the chimney
restrictor) to the firebox.

Flushing the System

If the system water is brown or orange, it is an indication
the Corrosion Inhibitor Plus™ level has not been
maintained and corrosion is present in the water jacket.
The water jacket should be thoroughly flushed and the
system refilled with the proper amount of Corrosion
Inhibitor Plus added. Be sure to test the system water to
verifiy the proper amount of Corrosion Inhibitor Plus.
1. De-energize the pumps and close the supply and
return valves on the outdoor furnace. Remove the
inspection panel and insulation covering the drain
to gain access to the drain. Remove the cap and
connect a hose to the drain.
NOTE: Refer to General Installation Information
for information on draining treated system water.
2. Open the drain to drain the system; then flush the top
of the firebox and bottom of the water jacket beneath
the firebox using a wand placed in the vent (Fig. 47).
CAUTION
Completely clean out the firebox before draining
water from the outdoor furnace.
42
Fig. 47
3. Close the drain valve securely and replace the cap
on the drain after flushing the outdoor furnace.
4. Fill the furnace following the procedure in Water
Quality and Maintenance making sure to operate the
pump(s) to thoroughly mix the Corrosion Inhibitor
Plus™.
5. Insulate the area using either canned urethane foam
insulation or a mat of fiberglass insulation.
6. Install the inspection panel and secure with self-
tapping screws.