Toshiba RAV-M240A-E Service Manual page 18

Split wall type
Table of Contents

Advertisement

Block level
Check
Check
Block
code
code
Indoor PC
board
Cable
connection/
Thermal fuse
Refrigerant
system
Table 8-5
Diagnosis function
Air conditioner
Symptom
status
Thermo sensor
Continued
short/break.
operation
Heat exchanger
Continued
sensor short/
operation
break.
Indoor fan lock,
All off.
abnormality of
indoor fan.
Abnormality of
Continued
other indoor unit
operation
PC board.
Wrong wiring or
All off.
disconnection of
connective cable.
• Thermal fuse
All off.
cut off.
• Indoor fan lock,
abnormality of
indoor fan.
• Gas shortage.
All off.
(gas leak)
• Other refriger-
ant cycle
trouble.
• Heat ex-
changer sensor
off/break/short.
• Overload relay
break
Compressor
All off.
break down.
– 18 –
Judgement and action
Condition
Indicated when
• Check thermo sensor.
detected abnor-
• If it is OK, check PC
mal.
board. (Around sensor
circuit)
Indicated when
• Check heat exchanger
detected abnor-
sensor.
mal.
• If it is OK, check PC
board. (Around sensor
circuit)
Indicated when
• Check motor.
detected abnor-
• Replace PC board, if
mal.
the same failure
occurs, after the
motor check.
Indicated when
Replace PC board.
detected abnor-
mal.
Indicated when
• Check flat cable
detected abnor-
correct if wiring is
mal.
wrong.
• If it is OK, check PC
board.
Indicated when
• Check thermal fuse.
detected abnor-
• If it is OK, check
mal.
motor.
• If motor is OK, check
PC board.
• Check gas quantity.
Indicated when
detected abnor-
(Check gas leakage)
mal.
• If it is OK, check heat
exchanger sensor.
• If heat exchanger
sensor is OK, check
overload relay.
• If overload relay is
OK, check refrigerant
cycle.
• If refrigerant cycle is
OK, check PC board.
Indicated when
• Check compressor.
detected abnor-
• If it is OK, check PC
mal.
board.