Item
Function
w1
Capacity
w1
Total input
Service Ref.
Power supply (phase, cycle,voltage)
Input
Running current w2
Starting current w2
External finish
Heat exchanger
Fan (drive) o No.
Fan motor output
Fan
Airflow (Lo-Mi2-Mi1-Hi)
External static pressure
Booster heater
Operation control & Thermostat
Sound level (Lo-Mi2-Mi1-Hi)
Unit drain pipe I.D.
Dimensions
Weight
Service Ref.
Power supply (phase, cycle, voltage)
Running current
Starting current
External finish
Refrigerant control
Compressor
Model
Motor output
Starter type
Protection devices
Heat exchanger
Fan (drive) o No.
Fan
Fan motor output
Airflow
Crankcase heater
Defrost method
Sound level
Dimensions
Weight
Refrigerant
Charge
Oil (Model)
Pipe size O.D.
Connection method
Between the indoor &
outdoor units
NOTE:
1. Rating conditions (ISO T1)
Cooling : Indoor
: D.B. 27: (80˚F), W.B. 19: (66˚F)
Heating : Indoor : D.B. 20: (68˚F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Upper limit
Cooling
Lower limit
Upper limit
Heating
Lower limit
Service Ref.
Btu/h
W
k W
w2
kW
A
A
kW
K / min (CFM)
Pa (mmAq)
kW
dB
mm (in.)
W
mm (in.)
D
mm (in.)
H
mm (in.)
kg (lbs.)
A
A
kW
kW
K / min (CFM)
W
Cooling
dB
Heating
dB
W
mm (in.)
D
mm (in.)
H
mm (in.)
kg (lbs.)
kg (lbs.)
L
Liquid
mm (in.)
Gas
mm (in.)
Indoor side
Outdoor side
Height difference
Piping length
Outdoor
Outdoor
Indoor
Outdoor
D.B. 35:, W.B. 22.5:
D.B. 46:
D.B. 19: , W.B. 15:
D.B. -5:
D.B. 28:
D.B. 24: , W.B. 18:
D.B. 17:
D.B. -11: , W.B. -12:
PLH-P5AAH.UK / PLH-P5AAH
Cooling
43,700
12,800
5.00
PLH-P5AAH.UK / PLH-P5AAH
Single phase, 50Hz, 220–230–240V
0.30
1.43
2.0
Munsell 0.70Y 8.59/0.97
Plate fin coil
Turbo fan (direct) o 1
0.120
22-25-28-30 (775-880-990-1,060)
0 (direct blow)
<3.0>
Remote controller & built-in
35-38-41-43
32 (1-1/4)
UNIT : 840 (33-1/16) PANEL : 950 (37-3/8)
UNIT : 840 (33-1/16) PANEL : 950 (37-3/8)
UNIT : 298 (11-3/4)
UNIT : 32 (71)
PUH-P5YGAA.UK
3 phases, 50Hz, 380–400–415V (4wires)
7.60
65.5
Munsell 5Y 7/1
Linear expansion valve
Hermetic
ZR61KCE-TFD
3.5
Line start
Internal thermostat, Thermal relay, HPswitch, Discharge thermo.
Plate fin coil
Propeller (direct) o 2
0.070+0.070
95 (3,360)
38
Reverse cycle
55
56
1,050 (41-5/16)
330+20 (13+3/4)
1,260 (49-5/8)
122 (269)
R407C
4.6 (10.1)
1.690 (Ester) MMMA-POE
9.52 (3/8)
19.05 (3/4)
Flared
Flared
Max. 50m
Max. 50m
: D.B. 35: (95˚F) W.B. 24: (75˚F)
: D.B. 7: (45˚F)
W.B. 6 : (43˚F)
w1 : [ ] Shows the total rating.
w2 : < > Shows the only booster heater rating.
3. Above data based on indicated voltage
Indoor unit
Outdoor unit
16
.UK
1
Heating
50,800 [61,100]
14,900 [17,900]
5.34 [8.34]
.UK
1
0.30 <3.00>
1.43 <12.50>
2.0 <12.50>
PANEL : 30 (1-3/16)
PANEL : 5 (11)
8.15
Single phase 240V 50Hz
3 phases 415V 50Hz