eleCTriCAl dATA

Table 3: Single-Zone Art Cool Mirror System Electrical Data Table.
Model number
nominal Tons
LA090HSV4
3/4
LA120HSV4
1
LA180HSV4
1-1/2
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
MCA = Minimum Circuit Ampacity.
12 | Product data
Compressor
Compressor (A)
Qty.
Cool/Heat
1
8.3/8.3
1
8.3/8.3
1
14.6/14.6
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG " is a registered trademark of LG Corp.
Fan Qty.
oDU Fan (A) IDU Fan (A)
1
0.40
1
0.40
1
0.25
Maximum overcurrent Protection (MoP) is calculated as follows: (Largest motor FLA x 2.25) + (Sum of
other motor FLA) rounded down to the nearest standard fuse size.
MCA(A)
MoP(A)
0.40
10
15
0.40
10
15
0.40
19
25