6RMI0-04C
Models
AS-W093F2B2(LAN090HVP/LAU090HVP)
AS-W123F2B2(LAN120HVP/LAU120HVP)
AS-W093MMM9(LSN090HYV/LSU090HYV)
AS-W123MMM9(LSN120HYV/LSU120HYV)
AS-W093B1Y9(LSN091HSV2/LSU091HSV2)
AS-W093BRM9(LAN090HSV2/LAU090HSV2)
AS-W123B1Y9(LSN121HSV2/LSU121HSV2)
AS-W123BRM9(LAN120HSV2/LAU120HSV2)
AS-W183C2Y9(LSN181HSV2/LSU181HSV2)
AS-W183CRM9(LAN180HSV2/LAU180HSV2)
AS-W243DGY9(LSN240HSV2/LSU240HSV2)
AS-W243CRM9(LAN240HSV2/LAU240HSV2)
AS-W303DGY9(LSN307HV2/LSU307HV2)
AS-W363DGY9(LSN360HV2/LSU360HV2)
Indoor unit
A
B
Outdoor unit
Notes
Equivalent pipe length = actual pipe length + number of bends x 0.3
Additional Refrigerant Charge
Example: For model LS120HSV2 having 20m(65.6ft) pipe length, additional refrigerant to be charged is
(20m(65.6ft)-7.5m(24.6ft)) x 20g/m(0.22oz/ft) = 250g(9.02oz)
* Specially LS091HSV2 / LS121HSV2 / LA090HSV2 / LA120HSV2 / LS090HYV / LS120HYV/ LA090HVP/LA120HVP
Additional refrigerant must be charged after 12.5m(41ft) (there is no need to charge till 12.5m(41ft) based on reliability)
Max. Pipe
Length[m(ft)]
15(49.2)
15(49.2)
15(49.2)
15(49.2)
20(65.6)
20(65.6)
20(65.6)
20(65.6)
30(98.4)
30(98.4)
30(98.4)
30(98.4)
30(98.4)
30(98.4)
Outdoor unit
A
Indoor unit
B
Inverter Single
Max.
Additional
Elevation[m(ft)]
Refrigerant[g/m(oz/ft)
10(32.8)
10(32.8)
10(32.8)
10(32.8)
10(32.8)
10(32.8)
10(32.8)
10(32.8)
15(49.2)
15(49.2)
15(49.2)
15(49.2)
15(49.2)
15(49.2)
CAUTION:
• Capacity is based on standard length
and maximum allowance length is on
the basis of reliability.
20(0.22)
20(0.22)
20(0.22)
20(0.22)
20(0.22)
20(0.22)
20(0.22)
20(0.22)
35(0.38)
35(0.38)
35(0.38)
35(0.38)
35(0.38)
35(0.38)
47