Advertisement

5.3 — Service Maintenance Intervals
NOTE: Use only Genuine Generac parts to ensure warranty coverage.
*
All generator service must be performed by
nel
only.
It is important to perform all maintenance at the interval specified in the Service Maintenance Schedule. This ensures
safe and proper operation, as well as compliance with applicable emissions standards. Critical emissions maintenance
must be performed for the Emissions Warranty to remain valid. Service and repairs may be performed by an authorized
service provider, any qualified service technician, or repair shop.
Observe the maintenance tasks and intervals shown in the table below.
Service
Check Enclosure Louvers
Check Fuel Lines
Check Coolant Level and Hoses
Check Radiator for Clogging
Check Lubricating Oil Level and Drain Hose
Replace Lubricating Oil and Oil Filter
Check Battery Condition/Fluid Level
Check/Adjust Accessory/Drive Belt Tension
Replace Air Filter Element
Drain/Flush Coolant System
Clean/Gap/Replace Spark Plugs
Replace Timing Belt (2.4L Engines Only)
Tighten Critical Fasteners
NOTE: If the unit reaches a Schedule A or Schedule B maintenance interval with 900 to 999 total hours, have
an authorized service provider perform the Schedule C maintenance tasks as well (and reset the A-B-C/Year
maintenance schedule counter).
Owner's Manual for Stationary Emergency Generators
an authorized service provider or a qualified service person-
Daily If Running
30 Hours
Continuously
Engine Break In
Schedule A
Schedule B
Every
Every
Year or
2 Years or
250 Hours
125 Hours
Maintenance
Schedule C
Every
1000 Hours
29