Installation Overview; System Overview - Danfoss SH-E01 Installation Manual

Electronic solar heat regulator
Hide thumbs Also See for SH-E01:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1

1.0 Installation Overview

Please Note:
This product should only be installed by a qualifi ed electrician or
competent heating installer and should be in accordance with the
current edition of the IEEE wiring regulations.
GB

2.0 System Overview

D
DK
F
ES
PT
T1 : Temperature sensor in solar collector
T2 : Temperature sensor in hot-water tank
: Circulation pump
: Solar heat regulator
The SH-E01 regulator is used for controlling utility water installations
consisting of a solar collector circuit and a hot water tank, where the
utility water is heated by solar energy.
The solar heat circuit circulation pump is controlled by the diff erential
temperature between the solar collector and the tank bottom.
If the diff erential temperature is higher than the preset start-up
temperature diff erential, the circulation pump will run.
To avoid unnecessary pump operation the temperature of the solar
collector has to be higher than 15°C before the pump starts operating.
The pump will run until the temperature diff erential is below 2°C.
4
SHE01

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents