Viessmann VITOCROSSAL 300 Technical Data Manual page 17

For operation with natural gas and liquid propane gas floor mounted, gas-fired condensing boiler heating input 19 to 199 mbh 5.6 to 58 kw
Hide thumbs Also See for VITOCROSSAL 300:
Table of Contents

Advertisement

Vitocrossal 300 CU3A 26 to 57 Technical Data
Accessories for Vitocrossal 300 CU3A
Low-Loss Header (continued)
Principle of Operation
Legend
T1
Boiler supply temperature
T2
Boiler return temperature
T3
System supply temperature
T4
System return temperature
Vprimary
Boiler circuit flow rate
Vsecondary
Heating circuit flow rate
Vbypass
Bypass flow rate
Qprimary
Heat supplied by boiler
Qsecondary
Heat consumed by system
IMPORTANT
When installing a low-loss header, the system mixed
supply temperature (T3) must be calculated as follows:
Vprimary < Vsecondary
T1 > T3
T2 = T4
Qprimary = Qsecondary
T1 167° F (75° C)
Vsecondary=Vprimary+Vbypass
Model No.
Type 80/60
Type 120/80
Type 160/80 *1
Type 200/120 *1
*1 Floor-mounted version (typically used for
multiple-boiler installations).
Accessories
Max. system flow rate
17.6 USGPM (4 m
3
/h)
35.2 USGPM (8 m
3
/h)
44 USGPM (10 m
3
/h)
80 USGPM (18 m
3
/h)
17