Lochinvar ARMOR 151 - 801 Service Manual page 38

Lochinvar water heater user manual
Table of Contents

Advertisement

Locate the throttle adjustment screw on top of the gas valve, see
FIG. 3-4. Using a screwdriver, turn the screw a 1/4 turn
counterclockwise to increase CO
to decrease CO
levels. After one adjustment on the valve, follow
2
the Combustion Analysis Procedure on page 36 of this manual
to measure the combustion.
If combustion is still not within the specified range, repeat the
procedure. This procedure SHOULD NOT be performed more
than four (4) times. If after four (4) adjustments and the
combustion is still not within the specified range, revisit the
possible causes in Table 3H on page 36 or replace the gas valve.
Figure 3-4
38
levels or a 1/4 turn clockwise
2
Locate the throttle adjustment screw on top of the gas valve,
see FIG. 3-4. Using an Allen wrench, turn the screw a 1/4 turn
counterclockwise to increase CO
clockwise to decrease CO
the valve, follow the Combustion Analysis Procedure on page
36 of this manual to measure the combustion.
If combustion is still not within the specified range, repeat the
procedure. This procedure SHOULD NOT be performed
more than four (4) times. If after four (4) adjustments and
the combustion is still not within the specified range, revisit
the possible causes in Table 3H on page 36 or replace the gas
valve.
Figure 3-5
THROTTLE
ADJUSTMENT
SCREW
(REMOVE BLUE CAP)
Service Manual
levels or a 1/4 turn
2
levels. After one adjustment on
2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents