Minimum clearances for the outdoor module
Fig.: Front view of outdoor module BWL-1S(B)-10/14
≥ 100
Fig.: Plan view of outdoor module BWL-1S(B)-10/14
Air discharge
a ≥ 1000 to obstacles obstructing the air discharge
a ≥ 3000 to footpaths and patios due to the formation of ice, even when outside temperatures are above 0 °C
Clearance between outdoor module and ground
In areas with heavy snowfall, the minimum installation height must be increased or a canopy must be constructed
over the outdoor module.
18

9. Siting the outdoor module

Air intake
≥ 300
Air discharge
Fig.: Front view of outdoor module BWL-1S(B)-07
≥ 100
Fig.: Plan view of outdoor module BWL-1S(B)-07
Air intake
≥ 300
Air discharge