Lincoln Electric RANGER IM612 Operator's Manual page 15

Lincoln electric welder user manual
Table of Contents

Advertisement

A-7
CONNECTION OF RANGER 8+ DIESEL TO PREMISES WIRING
POWER
230 Volt
60 Hz.
COMPANY
3-Wire
Service
METER
DOUBLE POLE DOUBLE THROW
SWITCH RATING TO BE THE SAME
AS OR GREATER THAN PREMISES
SERVICE OVERCURRENT
PROTECTION.
50 AMP, 115/230
VOLT PLUG
NEMA TYPE 14-50
50 AMP, 115/230 VOLT
RECEPTACLE
INSTALLATION
Figure A.1
230 VOLT
115 VOLT
115 VOLT
230 VOLT
GND
WARNING
Connection of RANGER 8+ DIESEL to premises
wiring must be done by a licensed electrician and
must comply with the National Electrical Code and
all other applicable electrical codes.
RANGER 8+ DIESEL
GROUNDED CONDUCTOR
40AMP
230 VOLT
DOUBLE
POLE
CIRCUIT
BREAKER
N
NOTE: No. 8 COPPER CONDUCTOR CABLE SEE
NATIONAL ELECTRICAL CODE FOR ALTERNATE WIRE
NEUTRAL
BUS
N
PREMISES
DISCONNECT AND
SERVICE
GROUND
OVERCURRENT
PROTECTION
SIZE RECOMMENDATIONS.
A-7
LOAD